2.7
Installing the MMS or MCS
2.7.1
Connecting the supply voltage to the MMS/MCS
24 V DC
The system is operated using a 24 V DC voltage, which is applied at the head station or
MCS. If required, the voltage can also be supplied redundantly (see Figure 2-16).
Figure 2-15
Supplying the system using one voltage source
Redundant 24 V DC supply
Figure 2-16
Supplying the system using two voltage sources
If redundant power supply monitoring is active (default setting), an error is indicated if only
one voltage is applied. A bridge between US1 and US2 (dotted line connection) prevents
this error message. It is also possible to deactivate monitoring in web-based management
or via SNMP.