Enabling web pages for using MRP in WBM
Activate WBM for the switches, e.g., using the Factory Manager. Switch to the "General
Configuration" menu, then the "User Interfaces" page. Activate "Redundancy" and confirm
by entering your password.
6.4
Configuration of MRP
6.4.1
MRP General
The "MRP General" web page shows the current parameters set for using the protocol. The
following information is displayed:
–
Operating mode (Disabled, MRP Client or MRP Manager)
–
Manager function (Present or Missing)
–
Ring status if the switch is operating as an MRP manager (OK (ring closed) or Fail (ring
open))
–
Topology modification counter
–
Time of last topology modification
–
Ring port numbers and status of the ports (Forwarding or Blocking)
Figure 6-4
"MRP General" web page for an MRP manager
Activating "Redundancy" under "General Configuration/User Interfaces" does not activate
a redundancy mechanism. In the WBM menu, the "Media Redundancy" page - under
which the function can be configured and activated - is enabled.
MRP can also be configured by the Profinet engeneering.