G 03902 - Edition 05 - August 12
3/4
C 42
M4 monitoring system function table
ENTER
SETTING
Selection
Selection
Setting limits
Initial configuration
PURGE SENSOR
WARNING time
0 to 60 mn / DISABLED
0 mn
ALARM time
0 to 60 mn / DISABLED
DISABLED
PURGE WARNING
Set WARNING
10 to 120 slm
15 slm
T° FB HIGH PRESS.
INPUT VALUE
70 to 100 °C
100
°C
Set ALARM
(Input value + 20 °C ) to 150 °C
120
°C
T° FB LOW PRESS.
INPUT VALUE
70 to 100 °C
70
°C
Set ALARM
(Input value + 20 °C ) to 140 °C
90
°C
T° ROOTS 2
(4)
INPUT VALUE
50 to 60 °C
Set ALARM
70 to 130 °C
FB POWER
Set WARNING
500 W to Set ALARM
2500 W
Set ALARM
Set warning to 5000 W
4000 W
ANALOG. INP. SENSOR
(4)
WARNING time
0 to 8000 mV
4000 mV
ALARM time
4000 to 9950 mV
8000 mV
LOG1 SENSOR
(4)
WARNING time
0 to 60 mn / DISABLED
DISABLED
ALARM time
0 to 60 mn / DISABLED
DISABLED
LOG3 SENSOR
(4)
WARNING time
0 to 60 mn / DISABLED
DISABLED
ALARM time
0 to 60 mn / DISABLED
DISABLED
PURGE PROLONGED
0 to 60 mn
10 mn
T° ROOTS 2
(4)
INPUT VALUE
50 to 60 °C
100
°C
Set ALARM
70 to 130 °C
100
°C
SERIAL LINK
TYPE
RS232 / RS485 / NETWORK
RS 232
ECHO
ENABLED / DISABLED
ENABLED
SPEED
1200/2400/4800/9600 Bauds
9600
PARITY
NO / EVEN / ODD
NO
2 STOP BITS
ENABLED / DISABLED
DISABLED
ADDRESS
(5)
0 to 999
0
DATE & TIME
Day /Month / Year
Hours/Minutes
TEMPERATURE UNIT*
CELSIUS / FARHENHEIT
CELSIUS
PRESSURE UNIT*
mbar / PSI / Torr / hPa
mbar
CONTRAST*
+/-
Contrast display setting
(4) : menus accessible only if the option is ENABLED
(5) : specific parameters to each hand held remote
SET
ENTER
adixen Vacuum Products - A3H Series Operating instructions