Pulscon LTC57 PROFIBUS PA
Operating menu
2015
-0
3
135
Figure 15.11
Switch-on delay
Switch-off value
Switch-on value
<
Switch-off value
• The output is closed if the measured value is smaller than
Switch-on value
.
• The output is opened if the measured value is larger than
Switch-off value
.
A
Switch-on value
B
Switch-off value
C
Output closed (conductive)
D
Output opened (non-conductive)
t
t
B
A
C
D
Blocking
Navigation
Setup
Advanced setup
Switch output
Switch-on delay
Prerequisite
•
Switch output function
(page 132) =
Limit
•
Assign limit
Off
Description
Define switch-on delay.
User entry
0.0 to 100.0 s
Factory setting
0.0 s
Blocking
Navigation
Setup
Advanced setup
Switch output
Switch-off value
Prerequisite
Switch output function
(page 132) =
Limit
Description
Enter measured value for the switch-off point.
User entry
Signed floating-point number
Factory setting
0
Additional information
The switching behavior depends on the relative position of the
Switch-on value
and
Switch-off value
parameters (description: see the
Switch-on value
parameter