Pulscon LTC57 PROFIBUS PA
Operating menu
2015
-0
3
121
Table mode
Blocking
Navigation
Setup
Advanced setup
Linearization
Table mode
Prerequisite
Linearization type
(page 116) =
Table
Description
Select editing mode of the linearization table.
Selection
• Manual
• Semi-automatic
a
• Clear table
• Sort table
a
Visibility depends on order options or device settings
Factory setting
Manual
Additional information
Meaning of the options
•
Manual
The level and the associated linearized value are entered manually for each
linearization point.
•
Semi-automatic
The level is measured by the device for each linearization point. The associated
linearized value is entered manually.
•
Clear table
Deletes the existing linearization table.
•
Sort table
Rearranges the linearization points into an ascending order.
Conditions the linearization table must meet:
• The table may consist of up to 32 pairs of values "Level - Linearized Value".
• The table must be monotonic (monotonically increasing or decreasing).
• The first linearization point must refer to the minimum level.
• The last linearization point must refer to the maximum level.
Note:
Before entering a linearization table, the values for
Empty calibration
Full calibration
(page 102) must be set correctly. If values of the
table need to be changed after the full or empty calibration have been changed, a
correct evaluation is only ensured if the existing table is deleted and the complete
table is entered again. To do so delete the existing table (
Table mode
=
Clear
table
). Then enter a new table.
How to enter the table
• Via PACTware
The table points can be entered via the
Table number
Level
(page 122) and
Customer value
(page 122) parameters. As an alternative, the
graphic table editor may be used: Device Operation
Device Functions
Additional Functions
Linearization (Online/Offline)
• Via local display
Select the
Edit table
(page 124) submenu to call up the graphic table editor.
The table is displayed and can be edited line by line.
Note:
The factory setting for the level unit is "%". If you want to enter the
linearization table in physical units, you must select the appropriate unit in the
Level
unit
parameter (page 114) beforehand.