201
5-0
3
114
Pulscon LTC57 PROFIBUS PA
Operating menu
Advanced process conditions
Level unit
Blocking
Navigation
Setup
Advanced setup
Level
Adv. conditions
Description
Specify additional process conditions (if required).
Selection
• None
• Oil/water condensate
a
• Probe near tank bottom
b
• Build up
• Foam (> 5 cm/0.16 ft)
c
a
only for
Medium type
=
Liquid
b
only for
Medium type
=
Liquid
c
only for
Medium type
=
Liquid
Factory setting
None
Additional information
Meaning of the options
•
Oil/water condensate
Makes sure that in the case of two-phase media always the total level is
detected (example: oil/condensate application).
•
Probe near tank bottom
Improves the empty detection, especially if the probe is mounted close to the
tank bottom.
•
Build up
Increases
EOP range upper area
in order to ensure a safe empty-detection
even if the end-of-probe signal has shifted due to build-up. Enables a safe
empty-detection even if the end-of-probe signal has shifted due to build-up.
•
Foam (> 5 cm/0.16 ft)
Optimizes the signal evaluation in applications with foam formation.
Blocking
Navigation
Setup
Advanced setup
Level
Level unit
Description
Select level unit.
Selection
SI units
• %
• m
• mm
US units
• ft
• in
Factory setting
%
Additional information
The level unit may differ from the distance unit defined in the
Distance unit
parameter (page 101):
• The unit defined in the
Distance unit
parameter is used for the basic calibration
(
Empty calibration
(page 102) and
Full calibration
(page 102)).
• The unit defined in the
Level unit
parameter is used to display the
(unlinearized) level.