Pulscon LTC57 PROFIBUS PA
Operating menu
2015
-0
3
113
Process property
Blocking
Navigation
Setup
Advanced setup
Level
Process property
Description
Specify typical rate of level change.
Selection
For
Medium type
=
Liquid
• Very fast > 10 m (400 in)/min
• Fast > 1 m (40 in)/min
• Standard. < 1 m (40 in)/min
• Medium < 10 cm (4 in)/min
• Slow < 1 cm (0.4 in)/min
• No filter/test
For
Medium type
=
Solid
• Very fast > 100 m (333 ft)/h
• Fast > 10 m (33 ft)/h
• Standard < 10 m (33 ft)/h
• Medium < 1 m (3 ft)/h
• Slow < 0.1 m (0.3 ft)/h
• No filter/test
Factory setting
Standard < 1 m (40 in)/min
Additional information
The device adjusts the signal evaluation filters and the damping of the output signal
to the typical rate of level change defined in this parameter:
For
Medium type
=
Liquid
Process property
Step response time/s
Very fast > 10 m (400 in)/min
5
Fast > 1 m (40 in)/min
5
Standard < 1 m (40 in)/min
14
Medium < 10 cm (4 in)/min
39
Slow < 1 cm (0.4 in)/min
76
No filter/test
< 1
For
Medium type
=
Solid
Process property
Step response time/s
Very fast > 100 m (333 ft)/h
37
Fast > 10 m (33 ft)/h
37
Standard < 10 m (33 ft)/h
74
Medium < 1 m (3ft)/h
146
Slow < 0.1 m (0.3ft)/h
290
No filter/test
< 1