Pulscon LTC57 PROFIBUS PA
Operating menu
2015
-0
3
127
Blocking distance
Figure 15.9
Blocking distance (UB) for bulk solid measurements
Blocking
Navigation
Setup
Advanced setup
Safety sett.
Blocking dist.
Description
Specify upper blocking distance UB.
User entry
0 to 200 m
Factory setting
• For coax probes: 0 mm (0 in)
• For rod and rope probes up to 8 m (26 ft): 200 mm (8 in)
• For rod and rope probes above 8 m (26 ft): 0.025 x length of probe
Additional information
No echoes are evaluated within the blocking distance UB. Therefore, UB can be
used to: Suppress interference echoes within the upper end of the probe.
UB