Pulscon LTC57 PROFIBUS PA
Operating menu
2015
-0
3
159
Logging interval
Clear logging data
Blocking
Navigation
Diagnostics
Data logging
Logging interval
Description
Define logging interval t
log
.
User entry
1.0 to 3600.0 s
Factory setting
30.0 s
Additional information
This parameter defines the interval between the individual data points in the data
log, and thus the maximum loggable process time T
log
:
• If 1 logging channel is used: T
log
= 500 x t
log
• If 2 logging channels are used: T
log
= 250 x t
log
• If 3 logging channels are used: T
log
= 166 x t
log
• If 4 logging channels are used: T
log
= 125 x t
log
Once this time elapses, the oldest data points in the data log are cyclically
overwritten such that a time of T
log
always remains in the memory (ring memory
principle).
Note:
The logged data are deleted if this parameter is changed.
Example
When using 1 logging channel
• T
log
= 500 x 1 s = 500 s
8.5 min
• T
log
= 500 x 10 s = 5000 s
1.5 h
• T
log
= 500 x 80 s = 40000 s
11 h
• T
log
= 500 x 3600 s = 1800000 s
20 d
Blocking
Navigation
Diagnostics
Data logging
Clear logging
Description
Initiate a deletion of the complete logging memory.
Selection
• Cancel
• Clear data
Factory setting
Cancel