Pulscon LTC57 PROFIBUS PA
Commissioning (via operating menu)
10.3
Configuration of a level measurement
Figure 10.2
Parameters for level measurement with the guided radar
Configuring level measurement
1. Setup menu
Device tag
Enter tag for measuring point.
2. Navigate to: Setup menu
Device address
Enter the bus address of the device (only for software addressing).
3. Navigate to: Setup menu
Distance unit.
Select distance unit.
4. Navigate to: Setup menu
Bin type
Select bin type.
5. Navigate to: Setup menu
Empty calibration
Enter the distance E between the reference point R and the minimum level (0 %).
6. Navigate to: Setup menu
Full calibration.
Enter distance F between the minimum (0 %) and maximum (100 %) level.
7. Navigate to: Setup menu
Level.
Displays the measured level L.
LN
Probe length
D
Distance
L
Level
R
Reference point of measurement
E
Empty calibration (= zero)
F
Full calibration (= span)
F
L
D
E
100%
0%
LN
R
Note!
If for rope probes the DC value is less than 7, then measurement is not possible in the area of
the straining weight. In these cases, the maximum recommended value for the empty
calibration E is
LN
–
250 mm (
LN
–
10 in).