201
5-0
3
164
Pulscon LTC57 PROFIBUS PA
Operating menu
15.4.10
Device check submenu
Device check
Start device check
Result device check
Last check time
Level signal
Navigation
Diagnostics
Device check
Blocking
Navigation
Diagnostics
Device check
Start dev. check
Description
Start a device check.
Selection
• No
• Yes
Factory setting
No
Additional information
In the case of a lost echo a device check can not be performed.
Navigation
Diagnostics
Device check
Result dev.check
Description
Displays the result of the device check.
Additional information
Meaning of the display options
•
Installation OK
Measurement possible without restrictions.
•
Accuracy reduced
A measurement is possible. However, the measuring accuracy may be reduced
due to the signal amplitudes.
•
Measurement capability reduced
A measurement is currently possible. However, there is the risk of an echo loss.
Check the mounting position of the device and the dielectric constant of the
medium.
•
Check not done
No device check has been performed.
Navigation
Diagnostics
Device check
Last check time
Description
Displays the operating time at which the last device check has been performed.
Navigation
Diagnostics
Device check
Level signal
Prerequisite
Device check has been performed.
Description
Displays result of the device check for the level signal.
User interface
• Check not done
• Check not OK
• Check OK
Additional information
For
Level signal
=
Check not OK
: Check the mounting position of the device and
the dielectric constant of the medium.