Channel-Related Parameters for the Sensor Input Modes
The following modes are available:
■
1: Sensor input enabled
■
0: Sensor input disabled
In frequency or counter mode, the channels 4, 7, and 10 are disabled.
9.2.2
Sensor-On Time
The Sensor-On Time parameter defines the time (in 10 ms ... 11000 ms) the input is turned ON
to determine the sensor input state. The parameter is valid for the sensor inputs 1, 4, 7, and 10.
In the frequency or counter mode, the sensor input 1 is turned on constantly and the sensor
inputs 4, 7, and 10 are turned off.
9.3
Diagnostic Parameters
This section describes the channel-related diagnostic parameters.
9.3.1
Sensor Wire Check
You can activate or deactivate the monitoring of wire faults. The following parameters exist:
The following monitoring modes are available:
■
Bit 0: Short circuit monitoring:
•
0: channel disabled
•
1: channel enabled
■
Bit 1: Lead breakage monitoring:
•
0: channel disabled
•
1: channel enabled
Parameter
Description
SENSOR_WIRE_CHECK
Enables/disables the lead short circuit and lead breakage
monitoring of the sensor connection for the hardware
channels 1, 4, 7, 10 (transducer-block-specific)
SENSOR_A_WIRE_CHECK
Enables/disables the lead short circuit and lead breakage
monitoring of the position feedback sensor A connection for
the hardware channels 2, 5, 8, 11 (transducer-block-specific)
SENSOR_B_WIRE_CHECK
Enables/disables the lead short circuit and lead breakage
monitoring of the position feedback sensor B connection for
the hardware channels 3, 6, 9, 12 (transducer-block-specific)