Activate write protection in either of the following ways:
■
Hardware write protection: Use DIP switch 8 on the device (see below).
■
Software write protection: Activate the respective parameter in the DTM software. For
more information see description of user interface no. 8, see chapter 10.2.3.
Figure 3.3
DIP switch 8 to activate the hardware write protection
Both write protection methods work the same way, regardless of which one is activated.
3.3
PROFIBUS Ident Number Setting
For each PROFIBUS field device type of each manufacturer at least 1 unique PROFIBUS ident
number is assigned for device identification. *D0-MIO-Ex12.PA support different ident numbers
and thus, different GSD files, to configure the required mode of operation.
Depending on the required mode of operation of the device, select the ident number in the
device type manager (DTM) software. Use the PROFIBUS Ident Number parameter.
For setting the PROFIBUS ident number, see chapter 10.4 and see chapter 10.3.
Manufacturer-Specific MIO Mode Ident Number
■
Manufacturer-specific MIO mode ident number:
0x0F8B
For selecting the corresponding device mode in the DTM, see chapter 10.4 and see chapter
10.3.
FD0-VC-Ex4.PA Compatible Mode Ident Number
■
FD0-VC-Ex4.PA compatible mode ident number:
0x0841
FD0-BI-Ex12.PA Compatible Mode Ident Number
■
FD0-BI-Ex12.PA compatible mode ident number:
0x0461
PROFIBUS Profile 3.02 Valve Coupler Mode Ident Number
■
PROFIBUS profile 3.02 valve coupler mode ident number:
0x9733
PROFIBUS Profile 3.02 Sensor Input Mode Ident Number
■
PROFIBUS profile 3.02 sensor input mode ident number:
0x972B
Activating Write Protection via the DIP Switch
Position ON = Active
Position OFF = Not active (default setting)
PROFIBUS
address setting
1 2 3 4 5 6 7
8
OFF
ON
Hardware
write
protection