PACTware Multi-Input/Output Device Type Manager
2
0
1
8
-0
7
93
Adjusting the Diagnostics
1. Set or adjust the diagnostic information of the device as required.
2. Click on
Apply
to confirm.
10.4.3
Valve Coupler Connections 1 ... 4
The valve coupler mode offers the use of up to 4 connections. The following options for
channel settings are identical for all 4 valve coupler connections.
10.4.4
Tab "General"
This tab offers the option to view and enter general and batch information on the current
channel.
Figure 10.25
Channel "General" tab
The tab "General" contains the following parameters:
Section "Information":
■
Tag:
Tag assignment option.
Free text field, assign a unique tag to each of the 12 channels of the MIO sensor input in
the plant or process.
■
Strategy:
Code assignment option.
Free value field, assign a user-specific code value to each of the 12 channels of the MIO
sensor input. This code can be used for classifying and summarizing information, e. g., for
diagnosis reports.
■
Alert key:
Code assignment option.
Free value field, assign a user-specific code value to each of the 12 channels of the MIO
sensor input. This code can be used for classifying and summarizing alarm messages
and events, i. e., for quick localization.
More Information
For more information on diagnosis of the device, see chapter 6.3.