Section "Wire check";
■
Valve wire check:
Enabling/disabling lead wire monitoring of the valve.
■
Sensor A wire check:
Enabling/disabling lead wire monitoring of sensor A.
■
Sensor B wire check:
Enabling/disabling lead wire monitoring of sensor B.
Section "Breakaway/transit time monitoring"
If required, you can set the MIO to monitor the breakaway and transit times of a valve.
■
Enabled:
Enabling/disabling monitoring for breakaway and transit times and tolerances.
■
Breakaway time, open to close:
Setpoint for the time between setting "Positioning
value" to CLOSE and the indication that the valve leaves the state OPEN.
■
Breakaway time, tolerance, open to close:
Maximum allowed time difference between
regular and measured breakaway time during OPEN to CLOSE.
■
Breakaway time, close to open:
Setpoint for the time between setting "Positioning
value" to OPEN and the indication that the valve leaves the state CLOSE.
■
Breakaway time, tolerance, close to open:
Maximum allowed time difference between
regular and measured breakaway time during CLOSE to OPEN.
■
Transit time, open to close:
Setpoint for the time between the changes of the state from
OPEN to CLOSE.
■
Transit time, tolerance, open to close:
Maximum allowed time difference between
regular and measured transit time during OPEN to CLOSE.
■
Transit time, close to open:
Setpoint for the time between the changes of the state from
CLOSE to OPEN.
■
Transit time, tolerance, close to open:
Maximum allowed time difference between
regular and measured transit time during CLOSE to OPEN.
Section "Stroke count monitoring"
If required, you can set the MIO to monitor the number of strokes of a valve.
■
Enabled:
Enabling/disabling monitoring for number of strokes.
■
Stroke count:
Contains the current value of stroke counter. If changed, the stroke
counter is set to the entered value
■
Stroke count limit:
Maximum allowed value for the stroke counter.
More Information
For more information on the wire check, see chapter 8.4.1.
More Information
For more information on time monitoring, see chapter 8.4.3.
More Information
For more information on stroke count monitoring, see chapter 8.4.2.