Configuration
The coding of the status is as follows:
ROUT_D
The variable ROUT_D consists of 2 bytes providing the setpoint value of the valve which is re-
transferred by RIN_D for monitoring and the status. This setpoint value does not include
information of the states of the position feedback sensors. The status is mainly used to control
the sequence of module change in case of failure.
The coding of the status is as follows:
Classic Status Value Mnemonic
Description
0x80
GOOD (NC)-OK
Feedback value valid.
0x84
GOOD (NC)-UE
(Update event.)
10-s message for parameter changes.
0x0C
BAD (NC)-DF
(Device failure.)
Electric hardware fault. Send the device to
Fuchs for repair.
0x10
BAD (NC)-SF
Position feedback sensor combination not
allowed.
0x11
BAD (NC)-SF
Lead short circuit
0x12
BAD (NC)-SF
Lead breakage
Classic Status Value Mnemonic
Description
0xC0
GOOD (C)-OK
Valid setpoint value.
0xC2
GOOD (C)-IR
(Initialization request.)
Clearance request from slave to master in
order to change to the RCas mode.
0xCC
GOOD (C)-NI
(Not invited.)
RCas is not set as the target mode.
0x0C
BAD-DF
(Device failure.)
Electric hardware fault. Send device to
Fuchs for repair.
0x1C
BAD-OS
(Out of service.)
Is set in the OoS mode.