The structure of the second byte, containing the status of the data, is as follows:
Frequency Input Variables
The OUT variable consists of 5 bytes. The first 4 bytes contain the process value of the
frequency or counter. The 5th byte contains the status of the process value.
The OUT long variable represents the value for the frequency input with the corresponding
status. Module description in long format. Not applicable to the FD0-BI-Ex12.PA compatibility
mode.
The OUT short variable represents the value for the frequency input with the corresponding
status. Module description in short format. Not applicable to the FD0-BI-Ex12.PA compatibility
mode.
For the frequency input, the sensor value is formatted in float format according to IEEE 754.
The structure of the 5th byte, containing the input status, is as follows:
Classic Status Value Mnemonic
Description
0x80
GOOD-OK
No error, the input value is valid.
0x12
BAD-SF
(Sensor failure.)
Lead breakage.
0x11
BAD-SF
(Sensor failure.)
Lead short circuit.
0x0C
BAD-DF
(Device failure.)
Hardware fault.
0x1C
BAD-OS
(Out of specification.)
No valid value of the sensor has been read
(after power-up of the device).
Classic Status Value Mnemonic
Description
0x80
GOOD-OK
No error, the input value is valid.
0x12
BAD-SF
(Sensor failure.)
Lead breakage.
0x11
BAD-SF
(Sensor failure.)
Lead short circuit.
0x0C
BAD-DF
(Device failure.)
Hardware fault.
0x1C
BAD-OS
(Out of specification.)
No valid value of the sensor has been read
(after power-up of the device).