background image

HOR. & REC. HOR. SIDEWALL SPRINKLERS, RESIDENTIAL

MODEL F685 DESIGNER, BULB TYPE, 3.5 K-FACTOR, 155°F & 175°F

GENERAL DESCRIPTION

The 3.5 K-factor, Model F685 Designer
Residential Horizontal and Recessed
Horizontal Sidewall Sprinklers (Ref.
Figure A) are automatic sprinklers of
the frangible bulb type. They are to be
used in

wet pipe residential sprinkler sys-
tems for one- and two-family dwell-
ings and mobile homes per NFPA
13D,

wet pipe residential sprinkler sys-
tems for residential occupancies up
to four stories in height per NFPA
13R, and

wet pipe sprinkler systems for the
residential portions of any occu-
pancy per NFPA 13.

They are designed for installation
along a wall or lintel and just beneath
a smooth and level ceiling. Horizontal
sidewall sprinklers are generally used
in lieu of pendent or upright sprinklers
because of aesthetic, building con-
struction, or installation economy con-
siderations.

The recessed versions of the Model
F685 Sprinkler are obtained by utiliz-
ing the Model F705 Recessed Es-
cutcheon (Ref. Figures A and B-2). The
F705 Recessed Escutcheon provides
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush sidewall
position.

The F705 has a separable two-piece
design which allows installation of the
sprinklers and pressure testing of the
fire protection system,  prior to wall
construction and/or application of a fin-
ish coat to the wall. They also permit
refinishing  of  a  wall  surface without
having to first shut down the fire pro-
tection system and remove the sprin-
klers.

The F685 Sprinklers have been de-
signed to operate with a particular tem-
perature  rating and  heat responsive
thermal characteristic, as well as to
discharge water in a specific pattern
and quantity per square foot relation-
ship. The combination of the perform-
ance characteristics which are associ-
ated with  the F685 Sprinklers have

FIGURE A

3.5 K-FACTOR MODEL F685 (SIN G1685) RESIDENTIAL

HORIZONTAL AND RECESSED HORIZONTAL

SIDEWALL SPRINKLERS

Printed in U.S.A. 7-02

Components:

1 - Frame
2 - Button Assembly
3 - Gasketed Spring Plate

TD587F

4 - Bulb
5 - Compression Screw
6 - Deflector

7 - Bushing
8 - Ejection Spring

TYCO FIRE PRODUCTS

, 7071 S. 13th Street, Suite 103 Oak Creek, WI 53154 — www.gemsprinkler.com

Customer Service/Sales:

Tel: (800) 558-5236 / Fax: (800) 877-1295

Technical Services:

Tel: (800) 381-9312 / Fax: (800) 791-5500

SPRI

NKLERS

F

OR

REPLA

CEMENT

USE

ONL

Y

IN

EXIS

T

ING

SPRI

NKLER

SY

STEMS

OBSOLETE

Содержание Gem F685

Страница 1: ...or up to 1 2 inch 12 7 mm of total adjustment from the flush sidewall position The F705 has a separable two piece design which allows installation of the sprinklers and pressure testing of the fire pr...

Страница 2: ...his condition consult the authorities having jurisdiction for guidance and approval It is the responsibility of an in stalling contractor to provide a copy of this document to the owner or his represe...

Страница 3: ...SED DIMENSIONS Up to 1 4 inch adjustment from minimum 1 4 inch to maximum 1 2 inch recessed position HIGH ADJUSTMENT DIMENSIONS Up to 1 2 inch adjustment from the flush sidewall position to 1 2 inch r...

Страница 4: ...ided by the manu facturer NOTES 1 Residential Fire Sprinkler Sys tems should only be designed and installed by those compe tent and completely familiar with automatic sprinkler sys tem design installa...

Страница 5: ...nterlines along the boundaries separating adjacent sprinkler coverage areas It is recommended that as part of the sprinkler system design the designer review the dwelling plans and where appropriate a...

Страница 6: ...can be used to com pensate for the possible manufac turing variations in the take out of the fitting as well as in the make in of the sprinklers as permitted by ANSI B1 20 1 3 After installing the F7...

Страница 7: ...the heat responsive element Bulb can result Do NOT cleanse the sprinklers with soap and water detergents ammonia cleaning fluids or other chemicals Remove dust lint cobwebs cocoons insects and larvae...

Страница 8: ...sh 155 F 68 C PSN 51 685 9 155 Natural Brass Finish 155 F 68 C PSN 51 685 1 155 White Polyester Finish 155 F 68 C PSN 51 685 4 155 Chrome Plated Finish 175 F 79 C PSN 51 685 9 175 Natural Brass Finish...