6. Inspection and Characteristics of Parts
2WAY SYSTEM
Trouble Diagnosis
U - V
8.8
8HP
10HP
12HP
14HP
16HP
18HP
20HP
U - W
Resistance
(at 20°C)
DMSBG75SY
unit : ohm
8.8
V - W
8.8
U - V
U - W
Outdoor unit
Inverter compressor (at 20°C)
Constant speed compressor (at 25°C)
unit : ohm
V - W
U - V
U - W
V - W
0.570
0.587
0.580
0.570
0.587
0.580
1.083
1.123
1.096
1.695
1.716
1.667
0.570
0.587
0.580
1.865
1.884
1.835
0.570
0.587
0.580
1.695
1.716
1.667
0.570
0.587
0.580
1.865
1.884
1.835
8HP
10HP
12HP
14HP
16HP
18HP
20HP
0.570
0.587
0.580
1.695
1.716
1.667
(4) Coil Resistance of Outdoor Unit Fan Motor
(5) Coil Resistance of Compressor Motor
(6) Characteristics of Thermistor
Resistor (kΩ
)
Resistor (kΩ
)
●
Ambient air temperature
thermistor (TO)
●
Suction temperature
thermistor (SCT)
Temperature(
°C
)
Temperature(
°C
)
●
Refrigerant gas outlet of
dual-tube thermistor (SCG)
●
Heat exchanger liquid
temperature thermistor (EXL)
●
Heat exchanger gas
temperature thermistor (EXG)
40
35
30
25
20
15
10
5
0
-10
-15
-20
20
20
30
40
50
60
15
10
5
0
-5
8
7
6
5
4
3
2
1
0
Resistor (kΩ
)
Temperature(
°C
)
●
Discharge temperature (DISCH) thermistor
0
90
80
70
60
50
40
30
20
10
0
40
60
80
100
120
140
160
180
200
20
5JD650ZBA22
5JD650ZBA22
5JD420ZCA22
C-SDN523H8B
C-SDN453H8B
C-SDN523H8B
C-SDN453H8B
C-SDN523H8B
5JD650ZBA22
5JD650ZBA22
5JD650ZBA22
5JD650ZBA22
7. Test Pin
7. Test Pin
2WAY SYSTEM
Trouble Diagnosis
When the test pin on the outdoor unit control PCB is short-circuited, each part can be operated individually.
•
After turning OFF the main unit power, short-circuit the test pin (CN22, black), then turn the power back ON.
Output is performed in the sequence shown in the table below, for 0.5 seconds each.
Operation
Operation
Output
Relay RY12 4-way valve (20s)
Relay RY8
Save valve (SAVE)
Output
Relay RY2
6
7
8
9
Relay RY1
1
2
3
4
5
Relay RY4
Bypass valve (BPV)
Relay RY6
Oil recovery valve (ORVR)
Relay RY3
Crankcase 2 (CH2)
Crankcase 1 (CH1)
Crankcase 3 (CH3)
Relay RY11 Refrigerant balance valve (RBV)
Relay RY10 Refrigerant control valve (RCV)
SM830205-04_2WAY_VRF_Euro.indb 33
15/01/20 15:29:49
Содержание U-8ME1E81
Страница 8: ...vii MEMO SM830205 04_2WAY_VRF_Euro indb 8 15 01 06 17 34 51 ...
Страница 50: ...2 28 MEMO SM830205 04_2WAY_VRF_Euro indb 28 2015 01 23 11 53 29 ...
Страница 90: ...4 6 MEMO SM830205 04_2WAY_VRF_Euro indb 6 15 01 20 15 31 37 ...
Страница 105: ...201502 SM830205 04_2WAY_VRF_Euro indb 1 15 02 13 17 04 58 ...