2WAY SYSTEM
Remote Controller Functions
3. Detailed Settings Function
2WAY SYSTEM
Remote Controller Functions
Operating the Remote Controller
Low Silhouette Ducted Type (Type F2)
<Procedure of CZ-RTC2>
1. Press and hold down the
,
and
buttons
simultaneously for 4 or more seconds.
(
, the Unit No., Item Code and Detailed Data will
blink on the remote controller’s LCD display.)
2. The indoor unit numbers in the group control will be
sequentially displayed whenever the Unit Select button is
pressed
.
Only the fan motor for the selected indoor unit will operate
during this.
3. Specify the “
” item code by pressing the
/
buttons for the temperature setting
buttons and confirm the values.
(“
” set at shipment )
4. Press the
/
buttons for the time to amend the
values for the set data.
Refer to table at right and select a value between
“
” and “
”.
Select “
” if the auto airflow volume setting is
activated.
5. Press the
button.
The display will stop blinking and remain illuminated.
6. Press the
button. The fan motor will stop operating
and the LCD display will return to the normal stop mode.
Auto Airflow Volume Control Operations and
External Static Pressure Setting-Check Operation
1. Press and hold down the
button for 4 or more
seconds. “
” will be displayed on the remote
controller’s LCD display.
2. Press the
button to commence the test run.
[Test Run] will be displayed on the remote controller’s LCD
display.
3. Select the fan mode and set it to “H” by pressing the
button.
Auto airflow volume control operations and external static
pressure setting-check operations will not be performed
unless [H] has been selected for the fan mode.
4.
The fan motor will be activated and auto airflow volume
control operations or external static pressure setting-check
operations will commence.
The power of the airflow will change while these operations
are in progress.
The external static pressure setting-check operations and
auto airflow volume control operations will be completed in
about 3 to 30 minutes.
The “
” display will be extinguished from the remote
controller’s LCD display.
5.
Press the
button to halt the test run.
Table of setting the external static pressure
Indoor unit
Item code
15, 22, 28, 36, 45,
56, 60, 73, 90
106, 140, 160
b0
External static pressure of the rated
air flow volume
150 Pa
140 Pa
130 Pa
120 Pa
100 Pa
70 Pa
60 Pa
50 Pa
30 Pa
10 Pa
150 Pa
140 Pa
130 Pa
120 Pa
110 Pa
100 Pa
70 Pa
50 Pa
30 Pa
10 Pa
No auto airflow volume setting
Auto airflow volume setting
6
2
1
5
1
4
3
* Failure to set this parameter may result in decreased
airflow and condensation.
2
1
5
3
CAUTION
3. Detailed Settings Function
3. Detailed Settings Function
2WAY SYSTEM
Remote Controller Functions
How to set the external static pressure
1. Keep pressing the
,
and
buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the LCD
display.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
] Confirm
20:30 (THU)
2. Press the
or
button to see each menu.
If you wish to see the next screen instantly, press the
or
button.
Select “8. Detailed settings” on the LCD display and
press the
button.
Maintenance func
5. Sensor info.
6. Servicing check
7. Simple settings
8. Detailed settings
Sel.
Page [
] Confirm
20:30 (THU)
The “Detailed settings” screen appears on the LCD
display.
Select the “Unit no.” by pressing the
or
button for changes.
Detailed settings
Unit no.
Code no.
Set data
B0
3-1
0001
Sel.
Next
20:30 (THU)
3. Select the “Code no.” by pressing the
or
button.
Change the “Code no.” to “B0” by pressing the
or
button (or keeping it pressed).
Detailed settings
Unit no.
Code no.
Set data
1
0
0
0
1
-
3
Sel.
Next
20:30 (THU)
B0
4. Select the “Set data” by pressing the
or
button.
Select one of the “Set data” among “0001” – “0015”
according to the desired external static pressure
setting by pressing the
or
button.
Then press the
button.
(See the table below. For details, refer to the section
“8. EXTERNAL STATIC PRESSURE SETTING” of the
Installation Instructions.)
When setting to auto airflow volume control:
Select the setting data to “-002”.
Then press the
button.
Indoor unit
Item code
B0
15, 22, 28, 36, 45,
56, 60, 73, 90
106, 140, 160
External static pressure of the rated air
fl ow volume (Pa)
150
0015
140
0014
130
0013
120
0012
100
0011
70
0008
60
0006
50
0005
30
0003
10
150
140
130
120
110
100
70
50
30
10
0001
No auto airfl ow volume setting
-001
Auto airfl ow volume setting
-002
5. Select the “Unit no.” by pressing the
or
button and press the
button.
The “Exit detailed settings and restart?” (Detailed
setting-end) screen appears on the LCD display.
Select “YES” and press the
button.
When the setting is completed, perform the test run
for the external static pressure setting described in
“Auto External Static Pressure Setting Operation”.
Detailed settings
Unit no.
Code no.
Set data
10
1-1
0001
Sel.
Next
20:30 (THU)
Exit detailed settings
and restart?
NO
YES
<Procedure of CZ-RTC3>
START
[ ]
20:30 (THU)
SM830205-04_2WAY_VRF_Euro.indb 19
2015/01/23 11:53:27
Содержание U-8ME1E81
Страница 8: ...vii MEMO SM830205 04_2WAY_VRF_Euro indb 8 15 01 06 17 34 51 ...
Страница 50: ...2 28 MEMO SM830205 04_2WAY_VRF_Euro indb 28 2015 01 23 11 53 29 ...
Страница 90: ...4 6 MEMO SM830205 04_2WAY_VRF_Euro indb 6 15 01 20 15 31 37 ...
Страница 105: ...201502 SM830205 04_2WAY_VRF_Euro indb 1 15 02 13 17 04 58 ...