Currently the blinking inspection display can be displayed only on the wired remote controller
and system remote controller.
Blinking inspection display (1) (Automatic backup)
Alarm code
(Blinking inspection display)
Alarm meaning
Automatic backup is in progress. A/C units can be operated.
Status: The compressor at one of the outdoor units where the outdoor unit fan is running should
be operating.
* Blinking inspection display also occurs when seizing of the compressor magnet SW
is detected. Because this may also be the case, refer to “Blinking inspection display
(compressor magnet SW seizing detection).”
Alarm conditions
When alarm P16, P22, P29, H03, Hx1, Hx2, or H31 has occurred, correcting the control device
(remote controller, etc.) input engages this mode.
Probable cause
Because alarm P16, P22, P29, H03, Hx1, Hx2, or H31 has occurred, check the alarm history
then refer to the corresponding items.
Correction
Follow the instructions in the corresponding items to correct the trouble.
Recovery
After repairing the malfunctioning locations, reset the power for the system (all outdoor units).
Caution: Automatic backup mode will not be canceled until the power is reset.
Notes
Automatic backup mode is not engaged in cases of alarms other than those listed above.
Reasons: • There is no need for automatic backup if recovery is possible by correcting the
remote controller input.
• With alarms for which automatic recovery is possible (such as sensor alarms), the
presence of electrical noise may result in a new alarm. However, it is believed that
this occurs for a comparatively short time only. In these cases, a mode (automatic
backup mode) that limits operation may be engaged.
• Control is not possible when a communications system alarm has occurred.
Automatic backup mode is not engaged in order to avoid causing secondary
damage.
WARNING
CAUTION
5. Blinking Inspection Display
SM830205-04_2WAY_VRF_Euro.indb 29
15/01/20 15:29:49
Содержание U-8ME1E81
Страница 8: ...vii MEMO SM830205 04_2WAY_VRF_Euro indb 8 15 01 06 17 34 51 ...
Страница 50: ...2 28 MEMO SM830205 04_2WAY_VRF_Euro indb 28 2015 01 23 11 53 29 ...
Страница 90: ...4 6 MEMO SM830205 04_2WAY_VRF_Euro indb 6 15 01 20 15 31 37 ...
Страница 105: ...201502 SM830205 04_2WAY_VRF_Euro indb 1 15 02 13 17 04 58 ...