2WAY SYSTEM
Remote Controller Functions
2. Simple Settings Function
List of Simple Setting Items
Item code
Item
Setting data
Description
No.
Filter sign ON time
(filter life time)
Not displayed
150 hours
2,500 hours
5,000 hours
10,000 hours
0000
0001
0002
0003
0004
0005 Use the filter clogging sensor.
Degree of filter fouling
Standard (setting at time of shipping)
0000
0001 Highly fouled
(Filter sign ON time is reduced to one-half the set time.)
Central control
address
0001
0002
0003
Central control address 1
Central control address 2
Central control address 3
0064
0099
Central control address 64
No central control address set (setting at time of shipping)
Operating mode
priority change
0000
0001
Normal (setting at time of shipping)
Priority
Fan speed when
heating thermostat is
OFF
Compressor OFF
Compressor ON
LL
LL
LL
Lo
Lo
Lo
Lo 1 min., LL 3 min.
Lo
LL
Lo 1 min., LL 3 min.
Lo
LL
0000
0001
0002
0004
0005
0006
Heating intake
temperature shift
0000
0001
0002
0003
0004
0005
0006
No shift
Shifts intake temperature 1°C down.
Shifts intake temperature 2°C down.
Shifts intake temperature 3°C down.
Shifts intake temperature 4°C down.
Shifts intake temperature 5°C down.
Shifts intake temperature 6°C down.
Electric heater
installation
Humidifying when
heater thermostat is
OFF
0000
0001
0000
0001
No heater
Heater installed
No (setting at time of shipping)
Yes
Permit/prohibit
Function of EXCT
plug short-circuit
Change to remote
controller sensor
thermostat differential
automatic
heating/cooling
(0D)
(0B)
Cool-only
0000
0001
0000 Indoor unit does thermostat OFF (factory preset mode)
Indoor unit gives “P14” alarm and transmits the refrigerant leakage signal.
0001
0000 Thermostat OFF differential: – 1°C (setting at time of shipping)
Thermostat OFF differential: – 0.5°C
0001
0000
0001
Permit
Prohibit
Normal
Cool only (Set “1” for item code OD.)
In order to avoid water leakage and damage to the fan, do not set for humidifying when the thermostat is OFF unless a
vaporizing humidifier is used.
Consider the device purpose and type when changing the settings. Incorrect settings may result in malfunction.
Do not change any setting data that does not appear in this list.
1
Keep pressing the
,
and
buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the
LCD display.
2
Press the
or
button to see each
menu.
If you wish to see the next screen instantly, press
the
or
button.
Select “7. Simple settings” on the LCD display and
press the
button.
The “Simple settings” screen appears on the LCD
display.
Select the “Unit no.” by pressing the
or
button for changes.
Simple settings
Unit no.
Code no.
Set data
3-1
20:30 (THU)
01
0002
Sel [
] Confirm
3
Select the “Code no.” by pressing the
or
button.
Change the “Code no.” by pressing the
or
button.
4
Select the “Set data” by pressing the
or
button.
Select one of the “Set data” by pressing the
or
button.
Then press the
button.
5
Select the “Unit no.” by pressing the
or
button and press the
button.
The “Exit simple settings and restart?” (Simple
setting-end) screen appears on the LCD display.
Select “YES” and press the
button.
<Procedure of CZ-RTC3>
Fig. 2-2
CZ-RTC3
START
[ ]
20:30 (THU)
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
] Confirm
20:30 (THU)
Maintenance func
5. Sensor info.
6. Servicing check
8. Detailed settings
Sel.
Page [
] Confirm
20:30 (THU)
7. Simple settings
Simple settings
Unit no.
Code no.
Set data
01
3-1
0001
Sel.
Next
20:30 (THU)
Simple settings
Unit no.
Code no.
Set data
3-1
0001
Sel.
Next
20:30 (THU)
01
Simple settings
Unit no.
Code no.
Set data
ALL
Sel.
Next
20:30 (THU)
01
0002
Exit simple settings
and restart?
NO
YES
SM830205-04_2WAY_VRF_Euro.indb 5
2015/01/23 11:53:22
Содержание U-8ME1E81
Страница 8: ...vii MEMO SM830205 04_2WAY_VRF_Euro indb 8 15 01 06 17 34 51 ...
Страница 50: ...2 28 MEMO SM830205 04_2WAY_VRF_Euro indb 28 2015 01 23 11 53 29 ...
Страница 90: ...4 6 MEMO SM830205 04_2WAY_VRF_Euro indb 6 15 01 20 15 31 37 ...
Страница 105: ...201502 SM830205 04_2WAY_VRF_Euro indb 1 15 02 13 17 04 58 ...