
6
-10
2WAY SYSTEM
Service Checker
1
2
3
4
5
6
7
8
2
3
1
5
Setting mode 2
Press and hold the (CHECK) button,
(SET) button and the (CANCEL) button
simultaneously for 4 seconds or longer.
Press the temperature setting and
buttons to change the item code. The item codes
and setting data are shown in the table below.
Press the timer time and buttons to
change the setting data.
To confirm the changed setting data, press the
(SET) button.
(At this time, the “ ” display stops blinking
and remains lit.)
To exit setting mode, press the (CHECK)
button. Returns to normal display mode.
2
Refrigerant type:
(C) and (D) are displayed alternately.
Example shows 000, 410 (R410A).
(C) Display of first 3 digits
(D) Display of last 3 digits
3
1
5
During this mode, “ ” is displayed,
blinking. The display shows the set outdoor unit
address “System XX-YY” (System XX = System
address, YY = Address at outdoor unit sub-bus),
item code number (DN value in the table below),
and the setting data (6 digits).
(The setting data is displayed in 6 digits. The
display changes between the first 3 digits
(Fig. (C)) and the last 3 digits (Fig. (D)). When the
first 3 digits are displayed, the bottom point of the
colon is illuminated.)
List of Item Codes
Outdoor unit capacity
Description (SET DATA)
000
Disabled
Parameter
CODE
NO.
Type 16HP
Type 18HP
Type 20HP
Type 8HP
224
Type 10HP
Type 12HP
Type 14HP
280
335
400
450
500
560
1. Outdoor Unit Maintenance Remote Controller
SM830205-04_2WAY_VRF_Euro.indb 10
2015/01/23 11:53:57
Содержание U-8ME1E81
Страница 8: ...vii MEMO SM830205 04_2WAY_VRF_Euro indb 8 15 01 06 17 34 51 ...
Страница 50: ...2 28 MEMO SM830205 04_2WAY_VRF_Euro indb 28 2015 01 23 11 53 29 ...
Страница 90: ...4 6 MEMO SM830205 04_2WAY_VRF_Euro indb 6 15 01 20 15 31 37 ...
Страница 105: ...201502 SM830205 04_2WAY_VRF_Euro indb 1 15 02 13 17 04 58 ...