2WAY SYSTEM
Service Checker
2WAY SYSTEM
Service Checker
1-4. Monitoring Operations
Display the indoor unit and outdoor unit sensor temperatures.
<Operating procedure>
Press and hold the (CHECK) and (CANCEL) buttons
simultaneously for 4 seconds or longer to engage temperature
monitor mode. During temperature monitoring, (CHECK)
illuminates.(The display and operations are the same as for
monitor mode using the indoor unit remote controller.)
Press the (UNIT) button and select the indoor unit to
monitor.
Press the temperature setting and buttons and
select the item code of the temperature to monitor.
The unit No. of the selected indoor unit, and the temperature data,
are displayed.
To end monitoring, press the (CHECK) button.
The display returns to the normal display.
The display does not blink.
NOTE
Display of unit No. 1 (main unit)
0A and subsequent items are outdoor unit data. 0A – 24 are for unit No. 1.
2A – 44 are for unit No. 2. 4A – 64 are for unit No. 3.
NOTE
1
2
3
4
1. Outdoor Unit Maintenance Remote Controller
Remarks
Description
DN
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
Indoor unit intake temp. (TA)
Indoor unit heat exchanger temp. E1 (E1)
—
Indoor unit heat exchanger temp. E3 (E3)
Indoor unit
Discharge air temp. (BL)
Discharge air temp. setting
Indoor unit MOV pulse (MOV)
STEP
Discharge temp. 1 (DISCH1)
Discharge temp. 2 (DISCH2)
High-pressure sensor temp.
Heat exchanger gas 1 (EXG1)
Heat exchanger liquid 1 (EXL1)
Heat exchanger gas 2 (EXG2)
Heat exchanger liquid 2 (EXL2)
Outdoor air temp. (TO)
—
A
Inverter primary current 1
A
A
CT2
Outdoor unit
STEP
MOV pulse 1 (MOV1)
STEP
MOV pulse 2 (MOV2)
Discharge temp. 3 (DISCH3)
CT3
Actual operating frequency
STEP
MOV pulse 4 (MOV4)
—
—
Low-pressure sensor temp.
Suction temp. (SCT)
Detected oil temp. 1 (OIL1)
Detected oil temp. 2 (OIL2)
Detected oil temp. 3 (OIL3)
—
Temp. sensor at refrigerant gas outlet of dual-tube temp. (SCG)
Hz
1. Outdoor Unit Maintenance Remote Controller
SM830205-04_2WAY_VRF_Euro.indb 7
2015/01/23 11:53:55
Содержание U-8ME1E81
Страница 8: ...vii MEMO SM830205 04_2WAY_VRF_Euro indb 8 15 01 06 17 34 51 ...
Страница 50: ...2 28 MEMO SM830205 04_2WAY_VRF_Euro indb 28 2015 01 23 11 53 29 ...
Страница 90: ...4 6 MEMO SM830205 04_2WAY_VRF_Euro indb 6 15 01 20 15 31 37 ...
Страница 105: ...201502 SM830205 04_2WAY_VRF_Euro indb 1 15 02 13 17 04 58 ...