2WAY SYSTEM
Address Settings
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
3. Auto Address Setting
2
3
4
5
6
7
8
3WAY SYSTEM
Address Settings
Adjustment of Termination Resistor (Plug)
Communication error will occur if improper adjustment is made.
• When connecting the centralized control system, it is necessary to adjust the termination resistor (terminal plug: CN67).
Even if no connection is made, confirmation is required for VRF systems.
• Termination resistor is placed on the outdoor unit control PCB.
• Centralized control system: Intelligent Controller (CZ-256ESMC2)
System Controller (CZ-64ESMC2)
Schedule Timer (CZ-ESWC2)
ON/OFF Controller (CZ-ANC2)
P-AIMS Basic software (CZ-CSWKC2)
• If the termination resistor of this inter-outdoor unit control wiring is 1 refrigerant system, short-circuit 1 location (remains
unchanged at shipment).
If there are more than 2 refrigerant systems, short-circuit 2 locations (remains unchanged at shipment).
In order to stabilize communication, 2 short circuit locations shall be at both sides (remains unchanged at shipment).
Open-circuit the refrigerant systems except for 2 locations mentioned above.
More than 3 short circuit locations of the termination resistors are prohibited (remains unchanged at shipment).
• There is no necessary to adjust the termination resistor (short circuit remained at shipment) because VRF systems for
combination of sub outdoor units are not connected to the control wiring.
If link wiring is not used
Short-circuit 1 termination resistor plug of the unit No.1 main outdoor unit (remains unchanged at shipment).
Setting of terminal plug (CN67)
Unit No. 1 (Main) : short-circuit (at shipment)
Unit No. 2 (Sub) : short-circuit (at shipment)
Unit No. 3 (Sub) : short-circuit (at shipment)
1-1
1-2
1-3
1-10
CN67
Centralized
control
system
Unit
No. 1
(Main)
Unit
No. 2
(Sub)
Unit
No. 3
(Sub)
SHORT
Outdoor unit control PCB
Short-circuit 1 termination resistor plug (remains unchanged
at shipment).
Remote control
communication wiring
Remote controller
Outdoor unit
Indoor unit
Inter-outdoor unit
control wiring
Inter-outdoor unit
control wiring
Inter-unit control wiring
3. Auto Address Setting
SM830229-00̲3WAY̲TEST RUN.indb 11
2013/02/23 18:38:19
2
3
4
5
6
7
8
3WAY SYSTEM
Address Settings
If link wiring is used
Short-circuit 2 termination resistors plug (remains unchanged at shipment).
In order to stabilize communication, 2 short circuit locations shall be at both sides (remains unchanged at shipment).
1-1
1-2
1-10
1-3
2-10
n-1
n-2
2-1
2-2
2-3
n-10
n-3
Final Check
Be sure to check before operation.
Final check must be done under the conditions of inter-outdoor unit control wiring
connected to the centralized control system and the resistor between conductors
must be measured by a Megger. Check if it is showing between 30Ω and 120Ω.
If the resistance value is out of range, check adjustment of the termination resistor again.
Even if it is out of range, the problem is caused by wiring.
• Is the wiring connection properly completed?
• Are there any scratches or deterioration on the coverage?
Measure between conductors and also between wiring and ground by 500V Megger
insulation resistance tester. Make sure the Megger is showing more than 100MΩ.
When measuring, remove both ends of the wiring from the terminal board.
If not removed, it will be damaged. If it is less than 100MΩ, a new wiring connection
should be made.
•
Centralized
control
system
No. 1
Refrigerant
circuit
No. 2
Refrigerant
circuit
No. n
Refrigerant
circuit
Unit
No. 1
(Main)
Unit
No. 2
(Sub)
Unit
No. 3
(Sub)
Remote control
communication wiring
Outdoor unit
system 1
Indoor unit
Outdoor unit
system n
Inter-outdoor unit control wiring
Inter-outdoor unit control wiring
Leave the socket that is
used to short-circuit the
terminal plug.
(CN67)
Between conductors
Between wiring and ground
Wire
Wire
Ground
Ground
Wire
Wire
Inter-unit control wiring
Indoor unit
Unit
No. 1
(Main)
Unit
No. 2
(Sub)
Unit
No. 3
(Sub)
Remote control
communication wiring
Remote
controller
Remote
controller
Remote
controller
Outdoor unit
system 2
Indoor unit
Inter-outdoor control wiring
Inter-outdoor unit control wiring
Move the sockets to the
“OPEN” side. (CN67)
Inter-unit control wiring
Unit
No. 1
(Main)
Unit
No. 2
(Sub)
Unit
No. 3
(Sub)
Remote control
communication wiring
Inter-outdoor unit control wiring
Inter-outdoor unit control wiring
Leave the socket that is
used to short-circuit the
terminal plug.
(CN67)
Inter-unit control wiring
Setting of terminal plug (CN67)
Unit No. 1 (Main)
Unit No. 2 (Sub)
Unit No. 3 (Sub)
open-circuit
short-circuit (at shipment)
short-circuit (at shipment)
short-circuit (at shipment)
short-circuit (at shipment)
short-circuit (at shipment)
short-circuit (at shipment)
short-circuit (at shipment)
short-circuit (at shipment)
Refrigerant circuit No.
No. 1
No. 2 to n-1
No. n
3. Auto Address Setting
SM830229-00̲3WAY̲TEST RUN.indb 12
2013/02/23 18:38:19
SM830205-04_2WAY_VRF_Euro.indb 11
15/01/20 15:15:25
Содержание U-8ME1E81
Страница 8: ...vii MEMO SM830205 04_2WAY_VRF_Euro indb 8 15 01 06 17 34 51 ...
Страница 50: ...2 28 MEMO SM830205 04_2WAY_VRF_Euro indb 28 2015 01 23 11 53 29 ...
Страница 90: ...4 6 MEMO SM830205 04_2WAY_VRF_Euro indb 6 15 01 20 15 31 37 ...
Страница 105: ...201502 SM830205 04_2WAY_VRF_Euro indb 1 15 02 13 17 04 58 ...