2WAY SYSTEM
Remote Controller Functions
3. Detailed Settings Function
Selecting cooling discharge temperature for only Type K2
(Using with the timer remote controller)
<Procedure>
Stop the system before performing these steps.
In order to prevent dew condensation or dewdrops during cooling or drying operation,
the setting of the discharge temperature can be set no lower than temperature needed.
If the installation is in a fear of high humidity area (over 80% humidity),
install the indoor unit in the following procedure.
(However, as the indoor unit capacity in the same refrigerant system
may sometimes deteriorate, make settings according to necessity.)
Press and hold the
buttons
and
,
simultaneously for 4 seconds or longer.
If group control is in effect, press the
button and
select the address (unit No.) of the indoor unit to set.
At this time, the fan at the indoor unit begins operating.
Use the temperature setting buttons to select item code
“1C.”
Make a choice from 6-level of numeric display “0000” to
“0005”.
Press the timer time
buttons to select the
/
desired setting data.
Press the
button. (The display stops blinking and
remains lit, and setting is completed.)
To change the selected indoor unit, go to step 2 .
Press the
button to return to normal remote controller
display.
The larger the numeric display, the more effectively
dew condensation or dewdrops can be prevented.
However, as the indoor unit capacity may sometimes
deteriorate, make settings according to necessity.
SM830205-04_2WAY_VRF_Euro.indb 21
2015/01/23 11:53:27
Содержание U-8ME1E81
Страница 8: ...vii MEMO SM830205 04_2WAY_VRF_Euro indb 8 15 01 06 17 34 51 ...
Страница 50: ...2 28 MEMO SM830205 04_2WAY_VRF_Euro indb 28 2015 01 23 11 53 29 ...
Страница 90: ...4 6 MEMO SM830205 04_2WAY_VRF_Euro indb 6 15 01 20 15 31 37 ...
Страница 105: ...201502 SM830205 04_2WAY_VRF_Euro indb 1 15 02 13 17 04 58 ...