2WAY SYSTEM
Remote Controller Functions
3. Detailed Settings Function
Selecting the DC fan motor tap (When setting from the PCB)
<How to Set on PC Board>
1.
2.
3.
Turn off the power breaker to halt the supply of electricity
to the PC board.
Open the lid of electrical equipment box and check where
the short-circuit pin on the indoor unit control PC board is
located.
Short circuit the applicable short-circuit pin in accordance
with the selected short-circuit pin connected.
150 Pa : TP3 (2P: yellow) short-circuit
140 Pa : TP1 (2P: red) short-circuit
* Use the short-circuit connector (2P: yellow) supplied.
Table of selection of connected short-circuit pins
External static pressure at the
time of rated airflow volume
Short-circuit pin
Unusable
150 Pa
140 Pa
TP6 (2P: white)
TP3 (2P: yellow)
TP1 (2P: red)
TP6 TP3 TP1
TP6 TP3 TP1
White Yellow Red
Indoor Unit control PC board