2WAY SYSTEM
Remote Controller Functions
<Procedure of CZ-RTC3>
1 Keep pressing the
,
and
buttons simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the
LCD display.
2 Press the
or
button to see each
menu.
If you wish to see the next screen instantly, press
the
or
button.
Select "5. Sensor info." on the LCD display and
press the
button.
Select the “Unit no.” by pressing the
or
button for changes.
Then press the
button.
Display sensor information of the unit.
Refer the information by pressing the
or
button.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
] Confirm
20:30 (THU)
Maintenance func
5. Sensor info.
6. Servicing check
8. Detailed settings
Sel.
Page [
] Confirm
20:30 (THU)
7. Simple settings
Sensor info.
Unit no.
Code no.
Data
Sel.
Next
20:30 (THU)
01
02
00
0028
0026
0026
1-1
Sensor info.
Unit no.
Code no.
Data
Scroll
20:30 (THU)
01
02
00
0028
0026
0026
1-1
CZ-RTC3
2WAY SYSTEM
Remote Controller Functions
3. Remote Controller Servicing Functions
Sensor info.
Unit no.
Code no.
Data
Scroll
20:30 (THU)
01
02
00
0028
0026
0026
1-1
Fig. 2-12
4. Remote Controller Servicing Functions
2WAY SYSTEM
Remote Controller Functions
4. Remote Controller Servicing Functions
Indoor unit sensors
Remote controller temp.
Indoor unit intake temp. (TA)
Indoor unit heat exchanger
temp. E1 (E1)
—
Indoor unit heat exchanger
temp. E3 (E3)
Discharge air temp. (BL)
Discharge air temp. setting
01
Room temp. controlled*
00
02
03
04
05
06
07
08
Indoor unit MOV pulse (MOV)
Outdoor unit sensors
Unit No.1
Unit No.2
Unit No.3
Discharge temp. 1 (DISCH1)
Discharge temp. 2 (DISCH2)
High-pressure sensor temp.
Heat exchanger gas 1 (EXG1)
Heat exchanger liquid 1 (EXL1)
Heat exchanger gas 2 (EXG2)
Heat exchanger liquid 2 (EXL2)
Outdoor air temp. (TO)
—
Inverter primary current 1
CT2
CT3
MOV pulse 1 (MOV1)
MOV pulse 2 (MOV2)
Discharge temp. 3 (DISCH3)
Actual operating frequency
MOV pulse 4 (MOV4)
—
—
Low-pressure sensor temp.
Suction temp. (SCT)
Detected oil temp. 1 (OIL1)
Detected oil temp. 2 (OIL2)
Detected oil temp. 3 (OIL3)
—
—
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
2A
2B
2C
2D
2E
2F
30
31
32
33
34
35
36
37
38
39
3A
3B
3C
3D
3E
3F
40
41
42
43
44
4A
4B
4C
4D
4E
4F
50
51
52
53
54
55
56
57
58
59
5A
5B
5C
5D
5E
5F
60
61
62
63
64
Temp. sensor at refrigerant gas
outlet of dual-tube temp. (SCG)
*Room temp. controlled: = Controlled room temperature
•When body thermostat controlled:
Controlled room temperature = Indoor unit intake temp. (TA) – Intake temperature shift (*1)
•Remote control thermostat controlled:
Controlled room temperature = Remote controller temp.
*1 Intake temperature shift: This is the shift value considered the temperature difference between the upper area
and lower area of the room in heating mode.
It is the value of the code “06” in the indoor unit’s EEPROM setting.
Cooling mode: = 0
SM830205-04_2WAY_VRF_Euro.indb 27
2015/01/23 11:53:29
Содержание U-8ME1E81
Страница 8: ...vii MEMO SM830205 04_2WAY_VRF_Euro indb 8 15 01 06 17 34 51 ...
Страница 50: ...2 28 MEMO SM830205 04_2WAY_VRF_Euro indb 28 2015 01 23 11 53 29 ...
Страница 90: ...4 6 MEMO SM830205 04_2WAY_VRF_Euro indb 6 15 01 20 15 31 37 ...
Страница 105: ...201502 SM830205 04_2WAY_VRF_Euro indb 1 15 02 13 17 04 58 ...