6
-8
2WAY SYSTEM
Service Checker
1
2
3
4
5
6
7
8
1-5. Outdoor Unit Alarm History Monitor
Recalls and displays the outdoor unit alarm history.
•
This is for the outdoor unit only. Indoor unit alarms
cannot be recalled.
•
The indoor unit alarm history can be viewed on the
indoor unit remote controller or other controller.
<Operating procedure>
Press and hold the (CHECK) button and
(SET) button simultaneously for 4 seconds or
longer to engage outdoor unit alarm history mode.
During temperature monitoring, illuminates.
The display and operations are the same as for
the alarm history monitor performed from the
indoor unit remote controller. However the “unit
No.” display shows the outdoor unit address.
Press the (UNIT) button, and select the
outdoor unit for which to monitor the alarm history.
Press the temperature setting and
buttons and select the item code for the alarm
history. The selected outdoor unit address, the
item code, and the alarm history (alarm data) are
displayed.
The outdoor unit address is displayed as R.C.
XX – YY.
(R.C. XX = Outdoor unit system address
YY = Outdoor unit address
Item codes 01 – 08 are displayed. 01 indicates the
most recent alarm.
The alarm history displays the alarm code.
(If no alarms are present, then is
displayed.)
To clear the alarm history, press the (CANCEL)
button.
(The outdoor unit alarm history will be cleared.)
To exit, press the (CHECK) button.
The display returns to the normal display.
3
2
4
1
5
1. Outdoor Unit Maintenance Remote Controller
2WAY SYSTEM
Service Checker
2
2
3
1
3
1
5
5
1-6. Setting the outdoor unit EEPROM data
This function is used to make the outdoor unit EEPROM
data settings.
Setting mode 1
Press and hold the (CHECK) button and the
(VENTILATION) button simultaneously for
4 seconds or longer.
Press the temperature setting and
buttons to change the item code. The item codes
and setting data are shown in the table of
“List of Item Codes” on the next page.
Press the timer time and buttons to
change the setting data.
To confirm the changed setting data, press the
(SET) button.
(At this time, the “ ” display stops
blinking and remains lit.)
To exit setting mode, press the (CHECK)
button.
Snowfall sensor usage
Outdoor unit fan Quiet mode
Demand 1 current
Demand 2 current
0000 = Sensor input not present. Control is performed.
0001 = Sensor input present. Control is performed.
0002 = Sensor input not present. Control is not performed.
0003 = Sensor input present. Control is not performed.
0000 = Disabled
0002 = Quiet mode 2
0001 = Quiet mode 1
0003 = Quiet mode 3
0000 = 0%
0009 = 140
0001 = 40 ...
0010 = 160
0004 = 70
0011 = 200
0007 = 100 0008 = 120
0012 = –1 (no limit)
0000 = 0%
0009 = 140
0001 = 40 ...
0010 = 160
0004 = 70
0011 = 200
0007 = 100 0008 = 120
0012 = –1 (no limit)
0004 = Quiet mode 4
Code
No.
)
A
T
A
D
T
E
S
(
n
o
it
p
ir
c
s
e
D
r
e
t
e
m
a
r
a
P
During this mode, “ ” is displayed,
blinking. The outdoor unit address display section
displays “ ,” the item code and number (DN
value in the table), and the setting data (6 digits).
(The setting data is displayed in 6 digits. The
display changes between the first 3 digits (Fig. (A))
and the last 3 digits (Fig. (B)).
When the first 3 digits are displayed, the bottom dot
of the colon is illuminated.)
(A) and (B) are displayed alternately.
(Example shows display of 000 001.)
(A) Display of first 3 digits
(B) Display of last 3 digits
1. Outdoor Unit Maintenance Remote Controller
Description
Parameter
DN
Snowfall sensor usage
000 = Sensor input not present. Control is performed.
001 = Sensor input present. Control is performed.
002 = Sensor input not present. Control is not performed.
003 = Sensor input present. Control is not performed.
Outdoor unit fan Quiet
mode
000 = Disabled
002 = Quiet mode 2
001 = Quiet mode 1
003 = Quiet mode 3
Energy saving mode
000 = None
001 = Discharge temp. control only (Mode 3)
002 = Demand only (Mode 2)
003 = Discharge temp. c Demand (Mode 1)
Energy saving operation
plug
000 = Independent
001 = All indoor units linked
Demand 1 current
000 = 0% 040 = 40% ... 070 = 70% ... 100 = 100% ...
130 = 130% ... -001 = no limit
Demand 2 current
000 = 0% 040 = 40% ... 070 = 70% ... 100 = 100% ...
130 = 130% ... -001 = no limit
High static pressure mode
000 = Disabled
001 = High static pressure mode
* Charge when the external static pressure is increased to over 30 Pa.
004 = Quiet mode 4 ... 012 = Quiet mode 12
SM830205-04_2WAY_VRF_Euro.indb 8
2015/01/23 11:53:56
Содержание U-8ME1E81
Страница 8: ...vii MEMO SM830205 04_2WAY_VRF_Euro indb 8 15 01 06 17 34 51 ...
Страница 50: ...2 28 MEMO SM830205 04_2WAY_VRF_Euro indb 28 2015 01 23 11 53 29 ...
Страница 90: ...4 6 MEMO SM830205 04_2WAY_VRF_Euro indb 6 15 01 20 15 31 37 ...
Страница 105: ...201502 SM830205 04_2WAY_VRF_Euro indb 1 15 02 13 17 04 58 ...