2WAY SYSTEM
Remote Controller Functions
Setting data
Item
code
Item
No.
Description
0000 No forced operation
0001 Forced operation for 1 minute
Automatic drain pump
operation
0060 Continuous operation
0000
None
Ventilation fan operation
0001 Ventilation fan operated by remote controller.
0000 Not used. (Body sensor is used.)
Wired remote controller sensor
0001 Remote control sensor is used.
0000 Normal (displayed)
“Operation change control in
progress” display
0001 Not displayed
0000
None
OFF reminder function for
when weekly timer is used
Discharge temperature control
0001 Only stop time setting is enabled.
0013
Control temperature 13°C
0000 Discharge temperature control OFF
0001 Discharge temperature control ON
0014
Control temperature 14°C
0025
Control temperature 25°C
Heat exchanger temperature
for cold air discharge
(Heat exchanger control point
for control to prevent cold air)
0026
Control temperature 26°C
0000
Output linked with fan. (ON when indoor unit fan is
operating.)
Fan output switching
0001 Fan mode operation output
0000 No delayed start
0001 1 second delayed start
0002 2 seconds delayed start
0058
Except
Indoor unit
Type
U1, F2,
T1, E1
Indoor unit
Type
U1, F2,
T1, E1
58 seconds delayed start
0059 59 seconds delayed start
Drain pump delayed start time
0060 60 seconds delayed start
1 minute delayed start
2 minutes delayed start
58 minutes delayed start
59 minutes delayed start
60 minutes delayed start
0000 Humidifier output OFF. Drain pump stopped.
0001 Humidifier output ON. Drain pump operates.
0002
Humidifier output ON. Drain pump operates for 1 minute
when total humidifier operating time reaches 60 minutes.
Humidifier setting
0003 Humidifier output ON. Drain pump stopped.
0000
Standard setting
Flap operation mode
Draft reduction mode (Flap lower-limit position is
shifted upwards.)
0001
0000
Smudging reduction mode (Flap swing upper-limit position
is shifted downwards.)
0001 Normal mode
Flap swing mode
0002
Draft reduction mode (Flap swing lower-limit position is shifted
upwards.)
3. Detailed Settings Function
SM830205-04_2WAY_VRF_Euro.indb 12
2015/01/23 11:53:24
Содержание U-8ME1E81
Страница 8: ...vii MEMO SM830205 04_2WAY_VRF_Euro indb 8 15 01 06 17 34 51 ...
Страница 50: ...2 28 MEMO SM830205 04_2WAY_VRF_Euro indb 28 2015 01 23 11 53 29 ...
Страница 90: ...4 6 MEMO SM830205 04_2WAY_VRF_Euro indb 6 15 01 20 15 31 37 ...
Страница 105: ...201502 SM830205 04_2WAY_VRF_Euro indb 1 15 02 13 17 04 58 ...