2WAY SYSTEM
Remote Controller Functions
3. Detailed Settings Function
Setting data
Item
code
Item
n
o
it
p
ir
c
s
e
D
.
o
N
DC fan tap
operating mode
Purpose
0000 Standard
Standard (setting at time of shipping)
High ceiling use
High ceiling setting 1 (with standard panel)
0001 For low
static-pressure
filter
Ultra long-life filter, oil guard panel, ammonia
deodorizing filter, optical regenerative deodorizing
filter
High ceiling use
High ceiling setting 2 (with standard panel)
For low
static-pressure
filter
(Antibacterial) high-performance filter (90%)
(Antibacterial) high-performance filter (65%)
Air-cleaning unit, air-cleaning unit + optical
regenerative deodorizing filter, deodorant (activated
charcoal) filter
0003
For air-blocking
material
For 3-way discharge, when discharge duct is
connected.
Fan tap setting
(Fan tap change
in order to prevent
drop in air
discharge caused
by filter
installation)
0006
For air-blocking
material
For 2-way discharge
0000 No humidifier output
0001 1
second
0002 2
seconds
0058 58
seconds
0059 59
seconds
Humidifier ON
time
(ON time per 60
seconds)
0060 Continuously ON
0000 Function disabled
Repeat timer
switching
0001 Function enabled
0000 Function disabled
Timer function
change prohibit
0001 Function enabled
Smudging control
0000 No smudging control
=91
=90
Flap 1
(Motor No. 4)
(Motor No. 1)
(Motor No. 2)
(Motor No. 3)
Flap 3
Flap 2
Flap 4
=92
=93
Electrical
component
box
Flap position
1
2
3
4
5
Setting the Flap
Separately
* Only for 4-way
Cassette type
Setting the Flap
Separately
* Only for 4-way
Cassette type
Setting the Flap
Separately
* Only for 4-way
Cassette type
Setting the Flap
Separately
* Only for 4-way
Cassette type
0001
0002
0003
0004
0005
0006
0000
Flap position during operation
Setting data
Move to position 1 and stay
Without separate setting
Swing
Move to position 2 and stay
Move to position 3 and stay
Move to position 4 and stay
Move to position 5 and stay
When the flap position is set to
4 or 5 and the unit is in the
cooling or dry mode, the flap
position is moved to 3 and the
operation is started.
The flap swings during the
operation under "Setting the
Flap Separately".
At this time, the unselected flaps
are moved to the position 1 .
NOTE
Air discharge
port
Flap
(adjustment for
up-down
airflow direction)
SM830205-04_2WAY_VRF_Euro.indb 13
2015/01/23 11:53:24
Содержание U-8ME1E81
Страница 8: ...vii MEMO SM830205 04_2WAY_VRF_Euro indb 8 15 01 06 17 34 51 ...
Страница 50: ...2 28 MEMO SM830205 04_2WAY_VRF_Euro indb 28 2015 01 23 11 53 29 ...
Страница 90: ...4 6 MEMO SM830205 04_2WAY_VRF_Euro indb 6 15 01 20 15 31 37 ...
Страница 105: ...201502 SM830205 04_2WAY_VRF_Euro indb 1 15 02 13 17 04 58 ...