![Panasonic S-71WF3E Скачать руководство пользователя страница 58](http://html.mh-extra.com/html/panasonic/s-71wf3e/s-71wf3e_service-manual_1507724058.webp)
58
Table I - Maximum refrigerant charge allowed in a
room
A
room
(m
2
)
Maximum refrigerant charge in a room
(
m
max
) (k
g
)
H
=1.64m
1
0.378
2
0.755
3
1.133
4
1.510
5
1.888
6
2.266
7
2.479
8
2.650
9
2.811
10
2.963
11
3.107
12
3.246
For intermediate
A
room
values, the value that
corresponds to the lower
A
room
value from the
table is considered.
Example:
For
A
room
= 10.5 m
2
, the value that corresponds to
“
A
room
= 10 m
2
” is considered.
Table II - Minimum floor area
m
c
(k
g
)
Minimum floor area
(
A
min total
(m
2
))
m
c
(k
g
)
Minimum floor area
(
A
min total
(m
2
))
H
=1.64m
H
=1.64m
1.84
4.87
2.54
7.35
1.86
4.93
2.56
7.47
1.88
4.98
2.58
7.58
1.90
5.03
2.60
7.70
1.92
5.08
2.62
7.82
1.94
5.14
2.64
7.94
1.96
5.19
2.66
8.06
1.98
5.24
2.68
8.18
2.00
5.30
2.70
8.30
2.02
5.35
2.72
8.43
2.04
5.40
2.74
8.55
2.06
5.46
2.76
8.68
2.08
5.51
2.78
8.80
2.10
5.56
2.80
8.93
2.12
5.61
2.82
9.06
2.14
5.67
2.84
9.19
2.16
5.72
2.86
9.32
2.18
5.77
2.88
9.45
2.20
5.83
2.90
9.58
2.22
5.88
2.92
9.71
2.24
5.93
2.94
9.85
2.26
5.99
2.96
9.98
2.28
6.04
2.98
10.12
2.30
6.09
3.00
10.25
2.32
6.14
3.02
10.39
2.34
6.24
3.04
10.53
2.36
6.34
3.06
10.67
2.38
6.45
3.08
10.81
2.40
6.56
3.10
10.95
2.42
6.67
3.12
11.09
2.44
6.78
3.14
11.23
2.46
6.89
3.16
11.38
2.48
7.01
3.18
11.52
2.50
7.12
3.20
11.67
2.52
7.23
-
-
For intermediate
m
c
values, the value that
corresponds to the higher
m
c
value from the table
is considered.
Example:
If
m
c
= 1.85 k
g
, the value that corresponds to
“
m
c
= 1.86 k
g
” is considered.
Charges above 3.20 k
g
are not allowed in the unit.
Table III - Minimum venting opening area for
natural ventilation
m
c
(k
g
)
m
max
(k
g
)
m
excess
(k
g
) =
m
c
-
m
max
Minimum venting
opening area
(
VA
min
) (cm
2
)
H
=1.64m
3.2
0.1
3.1
759
3.2
0.3
2.9
710
3.2
0.5
2.7
661
3.2
0.7
2.5
612
3.2
0.9
2.3
563
3.2
1.1
2.1
514
3.2
1.3
1.9
465
3.2
1.5
1.7
416
3.2
1.7
1.5
367
3.2
1.9
1.3
318
3.2
2.1
1.1
269
3.2
2.3
0.9
220
3.2
2.5
0.7
178
3.2
2.7
0.5
132
3.2
2.9
0.3
82
3.2
3.1
0.1
28
3.2
3.2
0.0
0
For intermediate
m
excess
values, the value that
corresponds to the higher
m
excess
value from the
table is considered.
Example:
m
excess
= 1.45 k
g
, the value that corresponds to
“
m
excess
= 1.5 k
g
” is considered.