![Panasonic S-71WF3E Скачать руководство пользователя страница 32](http://html.mh-extra.com/html/panasonic/s-71wf3e/s-71wf3e_service-manual_1507724032.webp)
32
Setting Options / Display
Default Setting
Menu
6 Installer setup Operation setup
To access to the two major
functions or modes.
2 main modes
Heat / Tank
6.1
Heat
To set various water & ambient
temperatures for heating.
Water temp. for heating ON /
Outdoor temp. for heating OFF /
T for heating ON /
Heater ON/OFF
Water temp. for heating ON
Compensation curve
Heating ON
temperatures in
compensation curve
or direct input.
Water temp. for heating ON Compensation curve
X axis: -5 °C, 15 °C
Y axis: 55 °C, 35 °C
Input the 4
temperature points
(2 on horizontal X
axis, 2 on vertical Y
axis).
•
Temperature range: X axis: -20 °C ~ 15 °C, Y axis: See below
•
Temperature range for the Y axis input:
CU-2WZ71YBE5 : 20 °C ~ 55 °C
•
If 2 zone system is selected, the 4 temperature points must also be input for Zone
2.
•
“Zone 1” and “Zone 2” will not appear on the display if only 1 zone system.
Water temp. for heating ON Direct
35 °C
Temperature for
heating ON
•
Min. ~ Max. range is conditional as follows:
CU-2WZ71YBE5 : 20 °C ~ 55 °C
•
If 2 zone system is selected, temperature set point must input for Zone 2.
•
“Zone 1” and “Zone 2” will not appear on the display if only 1 zone system.