Tank side (Tank mode):
When tank mode select and force heater bit received, turn ON backup heater (INTERNAL) or Booster Heater
(External) depend on the tank heater selection.
If tank heater selection is INTERNAL, follow normal thermo judgement to switch 3 ways valve to tank side and
room side.
Tank Heater selection is INTERNAL:
Backup Heater ON Condition:
After water pump operate 2 mins
AND
When tank temperature < Tank set temperature - [Remocon Set Tank Re-heat Temp]
AND
20 minutes since previous Backup heater OFF
AND
Backup Heater Enable
Backup Heater OFF condition:
Force mode off
OR
When tank temperature > Tank set temperature for continuous 15 secs
OR
Tank Operation OFF
14.9 Quiet Operation
Quiet mode is use to reduce the noise of outdoor unit by reducing the frequency or fan speed.
Quiet level
There are 3 level (Level 1, Level 2, Level 3) to set by quick menu function on remote control.
Control content
Once the quiet function is select, the remote control will transmit the signal to indoor and outdoor unit.
Start condition
Quiet mode is set on remote control.
Quiet mode is request ON by weekly timer.
Stop condition
If any of below condition is achieve.
OFF/ON button is pressed.
Quiet mode is OFF by remote control.
Quiet mode is request OFF by weekly timer.
14.10 Sterilization Mode
Purpose:
o
To sterilize water tank by setting the required boiling temperature.
Remote control setting
o
Days for sterilization function to start can be select.
o
Time of selected day to start sterilization function.
o
Boiling temperature (Internal heater is 55°C ~ 65°C)
o
Maximum operation time is 5 minutes to 1 hour.
Start condition
o
Tank connection set to “YES” by remote control
o
Sterilization function selects “YES”.
o
Sterilization signal received from remote controller by timer.
o
Tank mode request ON.
Stop condition
o
When boiling timer is completed. Boiling timer (Remote control set maximum operation time) start counting
once tank achieve boiling set temperature
OR
o
After 8 hours of operation since sterilization start.
o
Tank mode request OFF.