![Panasonic S-71WF3E Скачать руководство пользователя страница 235](http://html.mh-extra.com/html/panasonic/s-71wf3e/s-71wf3e_service-manual_1507724235.webp)
235
ON: Blinking:
OFF:
Abnormal
display
Wireless remote
controller
receiver display
Alarm contents
Error location
O
p
er
at
ion
Timer
Stand
by
Remote controlle
r • Indoor
Unit
F01
Operating
and timer
lamp blinking
alternately
Indoor heat exchanger temperature sensor
(E1) trouble
Check the indoor unit heat exchanger
temperature sensor (E1)
Check the indoor unit control PCB
F02
Indoor heat exchanger temperature sensor
(E2) trouble
Check the indoor unit heat exchanger
temperature sensor (E2)
Check the indoor unit control PCB
F10
Indoor air temperature sensor (TA) trouble
Check the indoor unit air temperature sensor
(TA)
Check the indoor unit control PCB
F29
Operating
and timer
lamp blinking
simultaneously
Indoor unit EEPROM trouble
Check the indoor unit EEPROM
Check the indoor unit control PCB
L02
Setting error, indoor / outdoor unit type / model
miss-matched
Address re-setting after correcting the
combination of units
L03
Operating
and standby
lamps blinking
simultaneously
Duplication of main indoor unit address in
group control
Correct the group (main and addition)
L07
Group control wiring is connected to individual
control indoor unit
Correct the indoor unit address
L08
Indoor unit address is not set
Correct the indoor unit address
L09
Indoor unit capacity is not set
Correct the capacity setting of indoor units
P01
Indoor unit fan motor locked
Remove the cause
Indoor unit fan motor layer short
Replace the fan motor
Contact failure in thermostat protector circuit
Correct the wiring
P09
Faulty wiring connections of (ceiling) indoor unit
panel
Correct the wiring connection
P10
Timer and
standby
lamp blinking
alternately
Faulty drain pump
Repair / Replace
Drainage failure
Correct
Contact failure of float switch wiring
Correct the wiring
Float switch : High water alarm
For vertical installation, set the detailed
settings Code No. “3F” to “0001”. (See pages
108 to 109.)
P11
Faulty drain pump
Repair / Replace
Drain pump locked
Remove the cause
P12
Indoor unit fan motor locked
Faulty wiring connections of indoor unit fan
motor
Remove the cause
Correct the wiring
Outdoo
r Unit
E06
Disconnection / Contact failure of inter-unit
wiring
Correct the inter-unit control wiring
Check the electrical connection of fuse
(F302) on indoor unit control PCB
In the case of the fuse opened on an indoor
unit control PCB, after correcting wiring
connection, it substitutes an EMG plug for
OC plug
Standby lamp
blinking
Disconnection of inter-unit wiring
Communication circuit fuse (F302) on indoor
unit control PCB opened
Indoor unit control PCB address settings error
Indoor unit address re-setting