![Panasonic S-71WF3E Скачать руководство пользователя страница 16](http://html.mh-extra.com/html/panasonic/s-71wf3e/s-71wf3e_service-manual_1507724016.webp)
16
Item
Unit
CU-2WZ71YBE5
Performance Test Condition
EN14511
EN14825
Cooling Capacity
kW
7.10
BTU/h
24200
Cooling EER
W/W
3.40
ERP (Average Climate)
Pdesign
kW
7.10
SEER
W/W
5.60
Annual Consumption
kWh
444
Class
A+
Heating Capacity
kW
7.10
BTU/h
24200
Heating COP
W/W
3.90
ERP (Average Climate)
Pdesign
kW
4.80
Tbivalent
°C
-10
SCOP
W/W
3.90
Annual Consumption
kWh
1723.00
Class
A
Heating Erp
Low Temperature Application (W35)
Warmer
Average
Colder
Application
Climate
Pdesign
kW
7.0
7.0
6.0
Tbivalent/TOL
°C
2 / 2
-10 / -10
-15 / -15
SCOP/ns
(W/W)/%
5.69 / 224
4.00 / 157
3.61 / 141
Annual Consumption
kWh
1644
3614
4101
Class
A+++
A++
A+
Medium Temperature Application (W55)
Warmer
Average
Colder
Application
Climate
Pdesign
kW
6.0
7.0
6.0
Tbivalent/TOL
°C
2 / 2
-7 / -10
-15 / -15
SCOP/ns
(W/W)/%
3.69 / 145
3.20 / 125
2.80 / 109
Annual Consumption
kWh
2170
4524
5289
Class
A++
A++
A+
DHW
Warmer
Average
Colder
Application
Climate
COP/nwh
(W/W)/%
3.35 / 134
2.60 / 104
2.30 / 92
AEC
kWh
760
957
1074
Class
A+
A
A
Heat Recovery Capacity
Total
kW
16.1
A2A / A2W
kW
7.1 / 9.0
Heat Recovery COP
W/W
5.11