![Panasonic S-71WF3E Скачать руководство пользователя страница 133](http://html.mh-extra.com/html/panasonic/s-71wf3e/s-71wf3e_service-manual_1507724133.webp)
133
A
3
* Failure to set this parameter may result in
decreased airflow and condensation.
12.1.10.3.2 Auto Airflow Volume
Control Operations and
External Static Pressure
Setting-Check Operation
1. Press and hold down the
button for 4 or more
seconds. “ TEST ” will be displayed on the LCD
display.
2. Press the
button to start the test run.
3. Select the operation mode
(Fan) by pressing
the
(Mode select) button.
Then select the fan speed
by pressing the
(Fan speed) button.
Auto airflow volume control operations and
external static pressure setting-check operations
will not be performed unless the above settings
are made.
4. The fan motor will be activated and auto airflow
volume control operations or external static
pressure setting-check operations will be started.
The power of the airflow will change while these
operations are in progress.
The external static pressure setting-check
operations and auto airflow volume control
operations will be completed in about 3 to
30 minutes.
“ TEST ” display will be disappeared from the LCD
display.
5. Press the
button to halt the test run.
A
°
°
1
3
2, 5
12.1.10.3.3 Fresh Air Intake
The amount of external air intake that is possible to feed when it is fed directly into the unit
Type
S-71WF3E
Permissible Air Intake Volume (m
3
/h)
105