214
19.4 Cooling overload control (Cool)
This control detect compressor discharge pressure and perform the compressor frequency restriction during
cooling operation.
Comp stop
Comp freq
restricted
37.0kgf/cm
2
35.0kgf/cm
2
Comp freq
free
40.0kgf/cm
2
High Pressure
* The high pressure value may be lower by 0 ~ 6kgf/cm
2
. Depends on the compressor frequency.
19.5 Heating overload control (Heat)
This control detect compressor discharge pressure and perform the compressor frequency restriction during
heating operation.
Comp stop
Comp freq
restricted
37.0kgf/cm
2
35.0kgf/cm
2
Comp freq
free
40.0kgf/cm
2
High Pressure
This control detect outdoor ambient temperature and perform the fan speed adjustment during heating operation.
19.6 Extreme Low Temperature Compressor low pressure protection control
(Heat)
This control is to prevent low pressure drops too low during extremely low outdoor ambient temperature to
improve the compressor reliability.
During heating operation, when outdoor ambient temperature is in Zone 1, this control will be activated.
Compressor frequency restriction will be based on outdoor piping temperature.