Outdoor ambient is updated every 5 minutes when operation ON.
Setting water outlet temperature always follow W
(LO)
or W
(HI)
whenever is higher if outdoor ambient sensor or
indoor communication error happen.
Compensation curve set shift value:
Tw
Tw_Hi
Tw_Lo
To_Hi
To
Shift value
+ 5
± 5
- 5
To_Lo
14.1.4 Target Water Temperature at Extension System (Optional PCB is connected)
Target water temperature is calculated as below.
Heat Mode:
o
Target water temperature setting:
o
Max= 55°C Min= 20°C
When buffer tank selection is “YES:”
Target water temperature = Target buffer tank tempe [2°C]
When buffer tank selection is “NO”
o
If both zone 1 and zone 2 is active
Target Water Temperature = Higher zone target water temperature of Zone 1 and Zone 2.
o
If only one zone is active
Target Water Temperature = Zone target water temperature of active zone.