The fan motor will be activated, the auto external
static pressure setting operation and setting-check
operation will be performed for about 3 to 30
minutes. The fan speed will change automatically
while these operations are in progress. When
these operations completed, “TEST” will be
disappeared from the LCD display.
20:30 (THU)
NOTE:
The auto external static pressure setting operation
and setting-check operation will not be performed
unless “
(MODE FAN)” and “
(FAN
SPEED)” have been selected.
11. Press the
button.
The LCD display will be returned to the initial
screen.
20:30 (THU)
START
[ ]
NOTE:
Failure to set this parameter may result in
decreased airflow and condensation.
12.1.10.3 Operating the Timer Remote
Controller (CZ-RTC4)
12.1.10.3.1 Setting Item Code “
”
1. Press and hold down the
,
and
buttons simultaneously for 4 or more seconds.
(
, the unit no., item code and detailed
data will blink on the LCD display.)
2. The indoor unit numbers in the group control will
be sequentially displayed whenever the Unit
Select button is pressed
.
Only the fan motor for the selected indoor unit will
operate during this time.
3. Specify the “
” item code by pressing the
/
buttons for the temperature setting buttons
and confirm the values.
(“
” set at shipment)
4. Press the
/
buttons for the time to
amend the values for the set data.
See Table 10-3 and Page 303 and select a value
between “
” and “
”.
Select “
” if the auto airflow volume setting
is activated.
5. Press the
button.
The display will stop blinking and remain
illuminated.
6. Press the
button. The fan motor will stop
operating and the LCD display will return to the
normal stop mode.
Table 10-3 Setting the external static pressure
Indoor unit type
Item code
S-71WF3E
Outdoor unit type
CU-2WZ71YBE5
External static pressure of the rated
airflow volume (Pa)
150
140
130
120
110
90
70
50
30 *
10
No auto airflow volume setting
Auto airflow volume setting
* Setting at shipment