![Panasonic S-71WF3E Скачать руководство пользователя страница 121](http://html.mh-extra.com/html/panasonic/s-71wf3e/s-71wf3e_service-manual_1507724121.webp)
121
12.1.8.5 Auto Address Setting Using the Remote Controller
Auto Address Setting from the High-spec Wired Remote Controller (CZ-RTC5B)
(1) Keep pressing the
,
and
buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the
LCD display.
(2) Press the
or
button to see each menu.
If you wish to see the next screen instantly, press
the
or
button.
Select “9. Auto address” on the LCD display and
press the
button.
20:30 (THU)
(3) The “Auto address” screen appears on the LCD
display.
Change the “Code no.” to “A1” by pressing the
or
button.
20:30 (THU)
20:30 (THU)
START
[ ]
CZ-RTC5B
(4) Select the “O/D unit no.” by pressing the
or
button.
Select one of the “O/D unit no.” for auto address
by pressing the
or
button.
Approximately 10 minutes are required.
When auto address setting is completed, the units
return to normal stopped status.
Auto Address Setting* from the Remote Controller (CZ-RTC4)
* Auto address setting in Cooling mode cannot be done from the remote controller.
Selecting each refrigerant system individually for auto address setting
Auto address setting for each system : Item code “A1”
(1) Press the remote controller timer time
button
and
button at the same time.
(Press and hold for 4 seconds or longer.)
(2) Next, press either the temperature setting
/
button.
(Check that the item code is “A1”.)
(3) Use either the
button to set the system No. to
perform auto address setting.
(4) Then press the
button.
(Auto address setting for one refrigerant system
begins.)
(When auto address setting for one system is
completed, the system returns to normal stopped
status.)
<Approximately 10 minutes are required.>
(During auto address setting, “
” is
displayed on the remote controller.
(3)
(1)
(4)
(2)
(4)
CZ-RTC4
This message disappears when auto address setting is completed.)
(5) Repeat the same steps to perform auto address setting for each successive system.