![Panasonic S-71WF3E Скачать руководство пользователя страница 15](http://html.mh-extra.com/html/panasonic/s-71wf3e/s-71wf3e_service-manual_1507724015.webp)
15
ITEM
Unit
S-71WF3E
Performance Test Condition
EN 14511
EN 14825
Remote Control
*CZ-RTC4, *CZ-RTC5B, *CZ-RTC6 Series (Wired) (Optional part)
Cooling Capacity (min. ~max.)
kW
7.10 (1.20 ~ 8.10)
BTU/h
24200 (4090 ~ 27600)
Cooling EER
W/W
3.40 (2.55 ~ 2.47)
Heating Capacity (min. ~max.)
kW
7.10 (2.00 ~ 10.20)
BTU/h
24200 (6820 ~ 34800)
Heating COP
W/W
3.90 (4.65 ~ 3.00)
Condition
Cooling
Heating
Current
A
10.1
8.7
Input Power
W
2.09k (470 ~ 3.28k)
1.82k (430 ~ 3.40k)
Standard Air Volume
m
3
/min
Cooling: 22.7
Heating: 22.7
ft
3
/min
Cooling: 800
Heating (800)
Outside Dimension (H x W X D)
mm
250 x 1000 x 730
inch
9-27/32 x 39-3/8 x 28-3/4
Net Weight
kg (lbs)
30 (66)
Piping
Connection
Refrigerant
Gas
mm (inch)
O.D. Ø 12.70 (1/2) Flared Type
Liquid
mm (inch)
O.D. Ø 6.35 (1/4) Flared Type
Fan
Type, Number of Set
Sirocco fan-2
Motor
Type
10-pole DC motor
Rated Output
kW
0.165
Fan Speed
Hi
rpm
Cooling: 960
Heating: 960
Me
rpm
Cooling: 800
Heating: 800
Lo
rpm
Cooling: 640
Heating: 640
Air-heat Exchanger (Row x Stage x FPI)
Slit fin type (2 x 16 x 19)
Running
Adjustment
Control Switch
Wired Remote Control
Room Temperature
Thermistor
Safety Devices
PCB current & temp. protector control for compressor
Condition
Cooling
Heating
Noise Level
Pressure Level
dB (A) H/L/QLo
34 / 26 / -
34 / 26 / -
Power Level
dB (A) H/L/Qlo
57 / - / -
57 / - / -
Moisture Removal
L/h
2.7