Flow of External Static Pressure
Finish the ducting and electrical wiring and prepare it for use. (Note (1))
External static pressure should be set during initial operations after
installation (before the cooling and heating test run).
Start external static pressure
setting
No
No
No
Yes
Yes
Yes
Line A (set at shipment)
on the PQ diagram was designed
and installed.
Set static pressure setting
to manual setting mode.
Wired remote controller
available
a. No setting modification
b. Manual setting
(set with the indoor unit
control PCB)
Change the dip switch.
See the section “12.1.10.1”.
c. Manual setting
Item code “b0” : 0~10 setting
(*Note (3))
See the section “12.1.10.2 or
12.1.10.3”.
d. Auto airflow volume
setting
Item code “b0” : -2 setting
See the section “12.1.10.2 or
12.1.10.3”.
Auto airflow volume control
operations
(*Note (4))
See the section “12.1.10.2 or
12.1.10.3”.
Operation checks for external static pressure settings
(*Note (2))
See the section “12.1.10.2 or 12.1.10.3”.
Check if the setting is within the range of use on the PQ diagram.
If out of range, adjust until it becomes within the range of use.
In the case of identical setup, it is possible to omit this operation check if judged
unnecessary.
Test operation display will disappear.
External static pressure setting completed
(1) Check the following items before performing the setting-check operations or auto airflow volume operations.
1) Check to make sure that the electrical wiring and ducting have been completed. Activate the stand-by mode.
In particular, make sure that the closed damper located in the middle of the duct is open, if installed. Also,
make sure that air filters have been installed inside the air inlet duct.
Check to make sure air is not leaking from the joints.