1-11. ELECTRICAL WIRING
General Precautions on Wiring
(1)
(4)
(5)
(6)
(7)
(8)
Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following
the wiring diagram.
(2)
(3)
This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current
Device (RCD). Otherwise, it may cause electrical shock and fire in case of equipment breakdown or insulation breakdown.
Earth Leakage Circuit Breaker (ELCB) must be incorporated in the fixed wiring in accordance with the wiring regulations.
The Earth Leakage Circuit Breaker (ELCB) must be an approved 10-16 A, having a contact separation in all poles.
To prevent possible hazards from insulation failure, the unit must be grounded.
Each wiring connection must be done in accordance with the wiring system diagram.
Wrong wiring may cause the unit to misoperate or become damaged.
Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.
Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any
damage or misoperation that occurs as a result of such unauthorized changes.
Regulations on wire diameters differ from locality to locality. For field wiring rules, please refer to your LOCAL ELECTRICAL
CODES before beginning.
You must ensure that installation complies with all relevant rules and regulations.
To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as follows:
The remote control wiring and the inter-unit control wiring should be wired apart from the inter-unit power wiring.
Use shielded wires for inter-unit control wiring between units and ground the shield on both sides.
(9) If the power supply cord of this appliance is damaged, it must be replaced by a repair shop designated by the manufacturer,
because special-purpose tools are required.
Recommended Wire Length and Wire Diameter for Power Supply System
Indoor unit
(B) Power supply
Type
Time delay fuse or
circuit capacity
2.5 mm
2
E2
Max. 30 m
10-16 A
U2
Max. 130 m
10-16 A
Control wiring
(C) Inter-unit control wiring
(between outdoor and indoor units)
(D) Remote control wiring
0.75 mm
2
(AWG #18)
0.75 mm
2
(AWG #18)
Use shielded wiring*
Max. 500 m
(E) Control wiring
for group control
0.75 mm
2
(AWG #18)
Max. 200 m (Total)
Max. 1,000 m
NOTE
* With ring-type wire terminal.
WARNING
NOTE
Wiring System Diagrams
<Type E2>
(1) Refer to “Recommended Wire Length and Wire
Diameter for Power Supply System” for the explanation
of “B”, “C”, “D” and “E” in the above diagram.
(2) The basic connection diagram of the indoor unit shows
the terminal boards, so the terminal boards in your
equipment may differ from the diagram.
(3) Refrigerant Circuit (R.C.) address should be set before
turning the power on.
(4) Regarding R.C. address setting, refer to the installation
instructions supplied with the outdoor unit. Auto address
setting can be executed by remote controller automatically.
Refer to the installation instructions supplied with the
remote controller (optional).
Power
supply
Inter-unit
control
wiring
U2
U1
SG
(SG: Shows the ground for the shielded cable.)
R2
R1
L
N
2
1
D
B
L
N
2
1
L1
L2
L3
N
C
L1
L2
L3
N
U2
U1
SG
Power supply
220/230/240V ~ 50 Hz
Remote
controller
WHT
BLK
Ground
Ground
Outdoor unit
INV unit
Power supply
380/400/415V, 3 N~, 50 Hz
Indoor unit
L
N
U1
U2
R1
R2
7P terminal board
Type E2
Remote
control
wiring
U1
U2
N
L
R1
R2
4P terminal board
2P terminal board
Unit
control
line
Remote
control
line
Power
supply
Type U2
U2
R2
U1
R1
R2
R1
L
N
U2
U1
2
1
D
C
B
L
N
L
N
2
1
B
E
C
L
N
SG
SG
Power supply
220/230/240V ~ 50Hz
Remote
controller
WHT
BLK
Power supply
220/230/240V ~ 50Hz
Ground
Ground
Indoor unit
(No. 1)
Indoor unit
(No. 2)
<Type U2>
(SG: Shows the ground for the shielded cable.)
L1
L2
L3
N
L1
L2
L3
N
U2
U1
SG
Ground
Outdoor unit
INV unit
Power supply
380/400/415V, 3 N~, 50 Hz