1-12
1
1
1-3. Other Component Specifications
Outdoor Units U-200PE2E8A
MODEL No.
Outdoor Unit
Power Transformer
Rated
VAC, Hz
Source
Secondary
Coil resistance
Ω
Thermistor (Coil / Air sensor): TH1, TH2, TH3, TH4
Resistance
kΩ
-20°C
:
38.48±2%
20°C
:
6.517±2%
-10°C
:
23.67±2%
30°C
:
4.448±2%
0°C
:
15.00±2%
40°C
:
3.100±2%
5°C
:
12.06±2%
45°C
:
2.607±2%
10°C
:
9.765±2%
50°C
:
2.203±2%
Thermistor (Discharge gas sensor): TH5
Resistance
kΩ
60°C
:
1.593±2%
85°C
:
0.7598±2%
65°C
:
1.363±2%
90°C
:
0.6623±2%
70°C
:
1.171±2%
95°C
:
0.5793±2%
75°C
:
1.010±2%
100°C
:
0.5083±2%
80°C
:
0.8746±2%
105°C
:
0.4473±2%
Relay (Comp. Magnetic Contactor)
VAC
Coil rated
VAC, A
Contact rating
Coil resistance (at 20°C)
Ω
Sol-Control-Valve
4 way valve
4 way valve
Electro magnetic coil
Thermal cut off temperature
Sol-control-valve
Magnetic coil
U-200PE2E8A
–
–
–
–
–
–
–
–
–
UKV32D322
SHF-20B-46-DC
SQ-D23015-002283
DC15.4V(898mA)
UKV-A392
Outdoor Units U-250PE2E8A
MODEL No.
Outdoor Unit
Power Transformer
Rated
VAC, Hz
Source
Secondary
Coil resistance
Ω
Thermistor (Coil / Air sensor): TH1, TH2, TH3, TH4
Resistance
kΩ
-20°C
:
38.48±2%
20°C
:
6.517±2%
-10°C
:
23.67±2%
30°C
:
4.448±2%
0°C
:
15.00±2%
40°C
:
3.100±2%
5°C
:
12.06±2%
45°C
:
2.607±2%
10°C
:
9.765±2%
50°C
:
2.203±2%
Thermistor (Discharge gas sensor): TH5
Resistance
kΩ
60°C
:
1.593±2%
85°C
:
0.7598±2%
65°C
:
1.363±2%
90°C
:
0.6623±2%
70°C
:
1.171±2%
95°C
:
0.5793±2%
75°C
:
1.010±2%
100°C
:
0.5083±2%
80°C
:
0.8746±2%
105°C
:
0.4473±2%
Relay (Comp. Magnetic Contactor)
VAC
Coil rated
VAC, A
Contact rating
Coil resistance (at 20°C)
Ω
Sol-Control-Valve
4 way valve
4 way valve
Electro magnetic coil
Thermal cut off temperature
Sol-control-valve
Magnetic coil
U-250PE2E8A
–
–
–
–
–
–
–
–
–
UKV32D322
SHF-35B-67-03
SQ-A2522G-005129
AC220-240V 50/60Hz
UKV-A392
SM830252-01_欧州_Single_8・10HP_TD_SM.indb 12
16/10/14 13:57:07