Installing the Drain Pipe
Before Performing the Installation Drain Piping
(1) Limitations of Raising the Drain Pipe Connection
CAUTION
●
The drain pipe can be raised to a maximum height of
850 mm from the bottom of the ceiling.
Do not attempt to raise it higher than 850 mm.
Doing so will result in water leakage.
A
B
300 mm or less
Indoor unit
Bottom of the Ceiling board
* Length of supplied drain pipe = 250 mm
A : 850 mm or lower
B : 666 mm or lower
(as short as possible)
(2) Limitations of Drain Pipe Connection
CAUTION
●
Do not install the drain pipe with an upward gradient from
the drain port connection. This will cause the drain water
to flow backward and leak when the unit is not operating.
●
Do not install an air bleeder as this may cause water to
spray from the drain pipe outlet.
●
Do not provide U-trap or bell-shaped trap in the middle of
the drain pipe. Doing so will cause abnormal sound.
Indoor unit
Air bleeder prohibited
Trap prohibited
Upward gradient
prohibited
●
Make sure the drain pipe has a downward gradient (1/100
or more; downward from drain port connection).
Indoor unit
Separation of support bracket = 1.5 m ~ 2 m
Downward gradient = 1/100 or more
(3) Limitations of Drain Hose Connection
CAUTION
●
Do not bend the supplied drain hose 90° or more.
Bend it less than 45°.
Bend angle 90° prohibited
Bend angle less than 45°
●
Do not make a trap in the middle of the supplied drain
hose. Doing so will cause abnormal sound.
Trap prohibited
281258_EU.indb 10
2016-9-1 13:03:42
Installing the Drain Pipe
CAUTION
●
Do not apply force to the drain port when connecting the
drain pipe. Install and fix it near the indoor unit as close
as possible.
●
Do not use adhesive when connecting the drain port pipe
and the drain hose.
(1) How to Install the Drain Pipe
1) First insert the supplied hose band into the drain port
pipe. Then make sure the head of the screw is facing
toward a technical engineer when placing the screw of
the hose band at an upward angle.
2) Insert the soft PVC socket of the supplied drain hose
to the drain port pipe. Do not use adhesive when
connecting the drain hose to the drain port pipe.
Insert it until the tip of the drain hose contacts the uneven
surface of the drain port pipe.
3) Move the hose band so that the center position of the
hose band can be placed approx. 30 mm away from the
external plate of the indoor unit. See diagram below.
4) Screw the drain hose tightly facing the screw of the hose
band upward. (Torque: 2.5 N·m - 3.4 N·m) (If the screw
is tightened beneath the drain hose, the troubles will be
generated.)
5) Apply approx. 2
g
of adhesive on both sides of the drain
hose without connection of the hard PVC socket and the
hard PVC pipe joint (VP25) in the local supply.
6) Connect the drain hose and the hard PVC pipe joint so
that the adhesive area of both sides can be overlapped.
Wipe off the protrusion-adhesive with a soft cloth.
Drain port
Do not use adhesive here.
* Drain port may possibly
be damaged and cause
the water leakage if
PVC adhesive is used.
* After checking the drainage, wrap the supplied packing and drain pipe insulator around the pipe.
Fasten the hose band as shown the diagram
below. (Torque: 2.5 N·m - 3.4 N·m)
Note:
Be sure to tightly insert the hard PVC pipe joint
(including elbow) minimum 20 mm or more.
57 mm
20 mm or more
Drain insulator
(supplied)
* However, do not use the hard PVC
pipe joint allowable more than 55 mm
insertion.
Packing
(supplied)
Adhere with PVC adhesive.
* Apply approx. 2
g
of adhesive on both sides
of supplied the drain hose and the hard
PVC pipe joint (VP25) in the local supply.
Wipe off the protrusion-adhesive with a soft
cloth.
Hard PVC pipe joint
(VP25 field supplied)
Hard PVC socket
Hose band (supplied)
Soft PVC socket
Drain hose
(supplied)
Uneven
surface
Indoor
unit
Indoor
unit
Uneven surface
5 mm
(Drainage check section
on drain port, transparent)