5-34
5
(1) Press and hold the
and
buttons
simultaneously for 4 seconds or longer.
(2) The unit No. “X-X” (main unit No.), item code “
”
(sensor address), and servicing monitor “
”
(sensor temperature) are displayed on the remote
controller LCD display.
(3) Press the temperature setting
/
and select the item code to the address of the
buttons
sensor to monitor.
(4) If group control is in effect, press the
to select the unit to monitor.
button
Press the temperature setting buttons to select the
item code to change.
(5) Press the
button to return to normal remote
controller display.
A
°
°
(4)
(3)
(4)
(3)(4)
(5)
(1)
(2)
5-6. Sensor Temperature Display Function
(Displayed regardless of operation and stop)
The procedure below displays the sensor temperatures from the remote controller, indoor unit, and outdoor unit on
the remote controller.
NOTE
The temperature display appears as “- - - -” for units that are not connected.
* If monitor mode is engaged while normal operation is in progress, only the parts of the LCD display shown in the
figure will change. Other parts continue to display the same information as during normal operation.
Item code
Meaning of Code
Indoor unit data
02
Indoor unit intake temp.
03
Indoor unit heat exchanger temp. (E1)
04
Indoor unit heat exchanger temp. (E2)
05
–
06
–
07
–
08
–
–
09
Outdoor unit data
0A
Discharge temp. (TD)
0b
–
–
0C
Outdoor unit heat exchanger temp. (C2)
0d
Intake temp. (TS)
0E
Outdoor unit heat exchanger temp. (C1)
0F
10
–
11
Outdoor air temp. (TO)
12
–
–
13
14
Current value (CTL1)
Current value (CTL2)
15
Outdoor MV value (MOV1)
16
19
Frequency
* Depending on the model, some items may not be displayed.
Sensor Temperature Correlation Table
SM830252-01_欧州_Single_8・10HP_TD_SM.indb 34
16/10/12 20:02:42
AMP Air Conditioning
www.ampair.co.uk | [email protected]