Air Intake
Strong wind
Intake side
Wall / Standing outer wall
Strong wind
Selecting the location for installation and service.
1. Install the unit once you have checked that the installation location matches the following conditions.
A location with suf
fi
cient ventilation.
Possibly a location that is sheltered from rain or direct sunlight and is well-ventilated so that hot and cool air does not build
up.
A location where the area around the discharge is not exposed to animals or plants which could adversely affect the release
of hot or cool air from the unit.
A location where the discharge and operation noise will not be a nuisance to the neighbours.
A location that can support the product’s weight or vibrations and secured for horizontal installation wherever possible.
A location that does not obstruct the air discharge or intake.
A location where there is no danger of
fl
ammable or corrosive gas leaks.
A location that provides space for installation and service.
A location that allows the pipe and cable length
fi
xture for internal and external connections.
It may need two or more people to carry out the installation work.
2. Refer to the diagram below for the installation location which is exposed to strong wind.
If a strong wind of more than 5 m/sec blows to the area directly in front of the discharge, the outdoor unit’s air
fl
ow is reduced
and the outfl
ow may re-enter (short circuit) causing the following outcome:
“Reduced capacity”, “Increased frost formation during heating” or “Operation stopped due to increased pressure”.
Should an exceptionally strong wind blow to the area directly in front of the discharge of the outdoor unit; there is the risk of
damage due to the fan’s high-speed reverse rotation.
If the direction of the prevailing wind is known when operating the unit, place the unit at an appropriate angle to the wind’s
direction so that the discharge faces towards a building or a wall.
3. If installing at locations prone to snowfall, install the unit as high as possible with suitable roo
fi
ng which shelters
the unit from snow.
4. Avoid installing the unit in locations where there are petroleum products (such as machine oil), saline content (such
as coastal areas), sulphurous gas and where high frequency noise is generated.
5. Place the indoor and outdoor unit, power cords and indoor/outdoor unit connection cables at a minimum distance
of 1 meter or more away from televisions and radios. This is to avoid interference to picture and/or sound.
(However, depending on the electromagnetic waves, noise interference may still occur even with the 1 meter separation.)
6. For restaurants and kitchens, avoid installing at locations which draws oil and steam.
Plastic parts can deteriorate from droplets of oil and steam or it can cause falling parts or water
7. Avoid installing at the location where cutting oil mist or iron powder is present.
8. If there is an immense voltage
fl
uctuation due to the location’s problem, ensure to split the power
9. When installing the product in a place where it will be affected by typhoon or strong wind such as
wind blowing between buildings, including the rooftop of a building and a place where there is no
building in surroundings,
fi
x the product with an overturn prevention wire, etc.
10. Ensure to assign several people or use a mechanical lift, etc. to transport the unit.
The following parts are supplied as accessories with each outdoor unit. Check that all accessory parts are present before
installing the outdoor unit.
3. SELECTING THE INSTALLATION SITE
SELECT THE OUTDOOR UNIT INSTALLATION LOCATION
Part name
Diagram
Quantity
Joint piping A (ø19.05
→
ø25.4)
1
Joint piping B (ø19.05)
1
Manual
A4 double-sided
printing (booklet)
1
Part name
Diagram
Quantity
Protective bushing
(for protecting electrical wires)
2
Banding strap
(for tying electrical wires together)
4
Installation Instruction
WARNING
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend
your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum
fi
ns on the air
conditioner can cut your
fi
ngers.
leakage.
supply.
Please secure necessary space to guarantee performance and service &
maintenance. For multiple installations, please secure enough space to
enable removal of side face screws between units. (unit: mm)
4. INSTALLATION SERVICE SPACE
Where there are obstacles at the intake
If upper part is open
1
Separate location
installation
2
Obstacles on both sides
More than 150
More than 250
More than
150
More than
200
3
Multiple units (more than 2 units)
Obstacles at the upper part (both sides open in separate location
installation)
Where there are obstacles at the discharge
If upper part is open
1
Separate location installation
More than 500
2
Multiple units (more than 2 units)
More than 150
More than 150
More than 1500
More than 250
More than 250
More than 250
More than 150
More
than 200
More than 150
More than 300
Where there are obstacles on the intake and discharge
Upper part and both side faces are open
1
Separate location installation
More than 150
More than 1000
2
Multiple units (more than 2 units)
More than 300
More than 250
More than 250
More than 1500
Caution: Please ensure that the height of obstacles at either the front
or rear faces is less than 2m.
In the case of front and rear multiple units
Upper part and both side faces are open
(More
than
1500)
(More
than 300)
More than 2000
More than 300
Caution: Please ensure that the height of obstacles at either the front or
rear faces is 2m or below.
Caution: We recommend a maintenance space of more than
500mm for every 3 units in multiple units installation.
More than 500