4. Mini VRF System Alarm Codes
Mini VRF SYSTEM
Trouble Diagnosis
2
Power on
2-1
Is the indoor unit powered off?
Is/was the power to the outdoor unit cut off?
1-1
1-2
Disconnect the connector mentioned above on the control PC board
of the indoor unit control PC board, and see whether the E04 goes off
after several minutes. (When doing so, if two remote controllers are
being used and the wireless remote controller is the main remote
controller, set the other remote controller as the main.)
Replace wireless remote control parts including wiring.
4-3
4-4
Is the LED on the indoor unit control PC board blinking?
4-5
Are all the remote controllers of the other indoor
units connected to that outdoor unit displaying E04?
4-7
The nonvolatile memory (EEPROM) on the indoor unit’s control PC board is either not installed,
improperly installed or the nonvolatile memory is faulty. Correct this or after replacing the
nonvolatile memory, write model data to it in the remote control detailed settings mode.
4-6
Are the CHK pin and/or TEST pin on the indoor unit control PC
board short-circuited?
4-1
Is the wireless remote controller connected to on the indoor unit’s
control PC board?
4-2
Is the indoor/outdoor operation line shorted, opened, grounded
or has a wrong contact?
2-1
Was a high voltage (over AC200V) applied in the indoor/outdoor
operations line circuit?
2-3
3-2
3-3
Was the number of indoor units increased or decreased after
auto address setting was complete?
3-1
Conduct checks prior to auto address setting.
3-2
3-2
After turning the power
on, wait three minutes
1-2
Correct the wiring
2-2
3-2
3-1
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
Normally the (SHORT)
setting is just one unit.
2-3
Yes
No
No
4-4
4-5
Yes
No
Remove the short
4-2
Yes
No
4-3
4-5
Yes
No
No
No 4-1
Check the indoor unit addresses from the remote control’s
detailed settings mode.
Is it Not Set (99), or is the indoor unit’s address duplicated?
3-3
When the network of indoor/outdoor operation line was wired,
was the (SHORT) setting of the terminal resistor switch
(CN-TERMINAL) on the outdoor control PC board set on multiple
units (four or more)?
2-2
Indoor/
outdoor
control line
4 Indoor
unit
control
PC board
3 No. of
Indoor
Units
1 Power
Source
E04 Error in Indoor Unit Receiving Signal from the Outdoor unit
Error Detection Method
Error Diagnosis
When there is no communication within a 3-minute period from the outdoor unit. Or, judged an error when no reply comes
from the outdoor unit.
The outdoor unit is not turned on.
When the network of indoor/outdoor operation line was wired, the (SHORT) setting of the terminal resistor switch on the
outdoor control PC board was set on multiple units (four or more).
When the power was turned on after auto address setting was completed, the number of indoor units had been changed.
Forgot to turn on the indoor unit.
The CHK pin and/or TEST pin on the indoor unit’s control PC board are shorted.
Forgot to install the nonvolatile memory (EEPROM) when replacing the indoor unit control PC board.
Mistakenly set the indoor unit address to Not Set in the remote control’s detailed settings mode.
When indoor unit addresses are duplicated.
•
•
•
•
•
•
There is a short, open, wrong contact or grounding of the indoor/outdoor operation line.
•
There is an error in the receiving circuit on the signal output PC board (optional control PC board).
•
Malfunctions of the outdoor unit
•
High voltage was applied (over AC200V) in the indoor/outdoor operations line circuit.
•
The thermistor inside the indoor unit is grounded.
•
•
•
1.
2.
4-6
4-7
Yes
No
Replace the outdoor unit control board
Replace the indoor unit control board
Yes
No
E06 Outdoor Unit Failed to Receive Serial Communication Signals from Indoor Unit
Error Detection Method
(When indoor unit(s) are connected)
Error Diagnosis
It is judged an error when there is no transmission (reply) from the indoor unit to the outdoor unit for a period of three minutes.
1.
2.
3
Remove the short
3-2
Are the DISP pin and CHK pin on the indoor unit control PC board
short-circuited?
Is the indoor unit powered off?
1-1
Is the indoor/outdoor operation line shorted, opened,
grounded or has a wrong contact?
2-1
3-1
Is the wireless remote controller connected to on the indoor unit’s
control PC board?
3-2
Power on
2-1
Correct the wiring
3-1
3-3
3-5
Yes
Yes
Yes
No
No
No
Disconnect the connector mentioned above on the control PC board
of the indoor unit control PC board, and see whether the E06 goes off
after several minutes. (When doing so, if two remote controllers are
being used and the wireless remote controller is the main remote
controller, set the other remote controller as the main.)
3-3
Replace wireless remote control parts including wiring.
3-4
3-5
3-4
3-5
Yes
No
Indoor
units
control
PC board
1 Indoor unit
power
2 Indoor/
outdoor
operation
line
Yes
No
The indoor unit is not turned on.
The DISP pin of the indoor unit is shorted.
The signal output control PC board (optional control PC board) inside the indoor unit has failed.
•
•
•
There is a short, open, wrong contact or grounding of the indoor/outdoor operation line.
•
The thermistor inside the indoor unit is grounded.
•
Indoor unit control PC board failure
Replace board.
For information on the procedures for replacing the indoor unit’s control board, refer to the manual that is packaged with
the indoor unit control PCB.
•
OPTION (CN060)
T10 (CN061)
CHK (CN062)
DISP
FAN DRIVE (CN032)
JP001
POWER LED (D002)
EXCT (CN073)
RC
EEPROM (IC010)
Indoor Unit Control PCB (A747661)
: S-200PE2E5, S-250PE2E5
Indoor Unit Control PCB (A7302060)
: S-100PU2E5A, S-125PU2E5A
POWER LED (D002)
EEPROM (IC010)
EMG (CN044) OC (CN040)
DISP (CN063)
CHK (CN062) T10 (CN061)
EXCT (CN073)
JP001
FAN DRIVE (CN032)