manualshive.com logo in svg
background image

TECHNICAL DATA & SERVICE MANUAL

85464849331002

REFERENCE NO.

SM830231-02

R410A Models

Model No.

Indoor Units

50

60

71

100

125

140

Outdoor Units

U-60PE1E5A U-71PE1E5A U-100PE1E5A U-125PE1E5A U-140PE1E5A

U-71PE1E8A U-100PE1E8A U-125PE1E8A U-140PE1E8A

U-50PE1E5

Type

PE1

PEY1

Outdoor Units Type

Single Split (1-phase)

Single Split (3-phase)

Single Split (1-phase)

Single Split (3-phase)

U-100PEY1E8 U-125PEY1E8

U-60PEY1E5

U-71PEY1E5 U-100PEY1E5 U-125PEY1E5

U-140PEY1E8

Indoor Unit

Outdoor Unit

Wall Mounted

Ceiling

Low Silhouette Ducted

4-Way Cassette

4-Way Cassette 60 x 60

Ducted

Order No. SBPAC1406003CE

 

Indoor 
Units Type

36

45

50

60

71

100

125

140

4-Way Cassette

S-36PU1E5A S-45PU1E5A S-50PU1E5A S-60PU1E5A S-71PU1E5A S-100PU1E5A S-125PU1E5A S-140PU1E5A

S-36PF1E5A S-45PF1E5A S-50PF1E5A S-60PF1E5A S-71PF1E5A S-100PF1E5A S-125PF1E5A S-140PF1E5A

S-36PN1E5A S-45PN1E5A S-50PN1E5A S-60PN1E5A S-71PN1E5A S-100PN1E5A S-125PN1E5A S-140PN1E5A

S-36PT2E5A S-45PT2E5A S-50PT2E5A S-60PT2E5A S-71PT2E5A S-100PT2E5A

S-100PK1E5A

S-125PT2E5A S-140PT2E5A

S-36PK1E5A S-45PK1E5A S-50PK1E5A S-60PK1E5A S-71PK1E5A

Wall Mounted

Low Silhouette 
Ducted

Ducted

S-36PY2E5A S-45PY2E5A S-50PY2E5A

4-Way 
Cassette 60 x 60

Y2

Type

U1

K1

F1

N1

T2 Ceiling

SM830231-02̲Single̲欧州.indb   1

SM830231-02̲Single̲欧州.indb   1

2014/09/11   17:38:46

2014/09/11   17:38:46

Содержание S-100PF1E5A

Страница 1: ...0 x 60 Ducted Order No SBPAC1406003CE Indoor UnitsType 36 45 50 60 71 100 125 140 4 Way Cassette S 36PU1E5A S 45PU1E5A S 50PU1E5A S 60PU1E5A S 71PU1E5A S 100PU1E5A S 125PU1E5A S 140PU1E5A S 36PF1E5A S 45PF1E5A S 50PF1E5A S 60PF1E5A S 71PF1E5A S 100PF1E5A S 125PF1E5A S 140PF1E5A S 36PN1E5A S 45PN1E5A S 50PN1E5A S 60PN1E5A S 71PN1E5A S 100PN1E5A S 125PN1E5A S 140PN1E5A S 36PT2E5A S 45PT2E5A S 50PT2E...

Страница 2: ...use overheating at connection points and a possible fire hazard To prevent possible hazards from insulation failure the unit must be grounded Provide a power outlet exclusively for each unit and full disconnection means having a contact separation in all poles must be incorporated in the fixed wiring in accordance with the wiring rules This equipment is strongly recommended to be installed with Ea...

Страница 3: ...ep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced WARNING This product must not be modified or disassembled under any circumstances Modified or disassembled unit may cause fire electric shock or injury Do not clean inside the indoor and outdoor units by...

Страница 4: ...tive use of floor space individual control and energy conservation by curtailing heat and carrying power etc Most importantly the multi air conditioner system is able to replenish a large amount of refrigerant compared to conventional individual air conditioners If a single unit of the multi air conditioner system is to be installed in a small room select a suitable model and installation procedur...

Страница 5: ... field and 1 2 the total refrigerant charge on the refrigerant charge label supplied with the product The filled out label must be adhered in the proximity of the product charging port e g onto the inside of the service cover 1 4 2 3 5 6 1 Factory refrigerant charge of the product see unit name plate 2 Additional refrigerant amount charged in the field 3 Total refrigerant charge 4 Contains fluorin...

Страница 6: ...5A S 50PF1E5A U 50PE1E5 S 50PF1E5A x2 U 100PE1E5A S 71PF1E5A U 71PE1E5A S 71PF1E5A x2 U 140PE1E5A S 100PF1E5A U 100PE1E5A S 125PF1E5A U 125PE1E5A P76 P77 P78 P79 P80 P83 P88 P85 P87 P86 P89 P81 P84 P82 N1 S 140PN1E5A U 140PE1E5A S 45PN1E5A x3 U 125PE1E5A S 50PN1E5A x3 U 140PE1E5A S 60PN1E5A U 60PE1E5A S 36PN1E5A x4 U 125PE1E5A S 36PN1E5A x2 U 71PE1E5A S 36PN1E5A x3 U 100PE1E5A S 60PN1E5A x2 U 125P...

Страница 7: ... x2 U 100PE1E8A S 50PN1E5A x3 U 140PE1E8A S 71PN1E5A U 71PE1E8A S 71PN1E5A x2 U 140PE1E8A S 100PN1E5A U 100PE1E8A S 125PN1E5A U 125PE1E8A P116 P117 P118 P119 P120 P122 P126 P123 P125 P124 P127 P121 S 45PK1E5A x3 U 125PE1E8A S 60PK1E5A x2 U 125PE1E8A S 36PK1E5A x4 U 125PE1E8A S 36PK1E5A x2 U 71PE1E8A S 36PK1E5A x3 U 100PE1E8A S 50PK1E5A x2 U 100PE1E8A S 50PK1E5A x3 U 140PE1E8A S 71PK1E5A U 71PE1E8A...

Страница 8: ... 100PEY1E8 S 125PT2E5A U 125PEY1E8 P161 P162 P165 S 140PT2E5A U 140PEY1E8 P166 P163 P176 K1 S 60PK1E5A x2 U 125PEY1E8 S 50PK1E5A x2 U 100PEY1E8 S 71PK1E5A x2 U 140PEY1E8 P173 P174 P175 3 phase F1 S 36PF1E5A x2 U 71PEY1E5 P177 S 60PF1E5A U 60PEY1E5 S 60PF1E5A x2 U 125PEY1E5 S 50PF1E5A x2 U 100PEY1E5 S 71PF1E5A U 71PEY1E5 S 100PF1E5A U 100PEY1E5 S 125PF1E5A U 125PEY1E5 P178 P179 P183 P181 P182 P180 ...

Страница 9: ... Wiring Diagram Schematic Diagram 3 2 3 2 Outdoor Units Electric Wiring Diagram 3 9 Section 4 CONTROL FUNCTIONS 3 1 4 1 4 1 Room Temperature Control 4 2 Heating Standby 4 3 Automatic Fan Speed Control 4 4 Drain Pump Control 4 5 Automatic Heating Cooling Control 4 6 Automatic Flap Control 4 7 Filter Sign 4 8 Fan Control during Dry Mode 4 9 Ventilation Fan Output 4 10 T10 Terminal 4 11 Parameter 4 1...

Страница 10: ...OW TO INSTALL THE WIRELESS REMOTE CONTROLLER RECEIVER Important Safety Instructions Optional Controller Remote Controller 8 3 8 1 8 3 8 2 8 5 8 3 8 5 8 4 8 6 8 5 8 7 8 6 8 8 8 8 8 7 8 8 8 9 8 9 8 9 Names and Functions Installing Batteries Setting the Current Time Operation Timer Operation Adjusting the Wind Direction Operating Multiple In Outdoor Units Simultaneously Group Control Using the Remote...

Страница 11: ... 1 222 1 223 1 234 1 251 1 262 1 273 1 4 Way Cassette Type U1 1 342 1 354 1 273 1 273 1 322 Outdoor Unit 1 342 Indoor Unit 2 Ceiling Type T2 1 154 3 Wall Mounted Type K1 1 167 1 177 4 Low Silhouette Ducted Type F1 5 Ducted Type N1 U 50PE1E5 U 60PEY1E5 U 71PEY1E5 U 60PE1E5A U 140PE1E5A U 71PE1E8A U 140PE1E8A U 100PEY1E5 U 125PEY1E5 U 100PEY1E8 U 125PEY1E8 U 140PEY1E8 1 190 6 4 Way Cassette 60 x 60 ...

Страница 12: ... I N G CAPACITY kW 8 0 8 0 8 0 2 0 9 0 BTU h 27300 27300 27300 6800 30700 CURRENT A 0 17 2 0 17 2 0 16 2 9 30 9 00 8 70 INPUT POWER W 20 2 20 2 20 2 1 960k 1 960k 1 960k TOTAL W 2 000k 2 000k 2 000k 400 2 900k COP COP CLASS TOTAL W W 5 A G 4 00 4 00 A 4 00 5 00 3 10 Erp 6 Pdsign kW 7 1 Tbivalen C 8 SCOP W W 4 1 Annual consumption kWh 2424 Class A POWER FACTOR 96 95 94 NOISE INDOOR H M L dB A 30 28...

Страница 13: ... T I N G CAPACITY kW 11 2 11 2 11 2 4 1 14 0 BTU h 38200 38200 38200 14000 47800 CURRENT A 0 17 3 0 17 3 0 16 3 11 9 11 5 11 1 INPUT POWER W 20 3 20 3 20 3 2 540k 2 540k 2 540k TOTAL W 2 600k 2 600k 2 600k 900 4 400k COP COP CLASS TOTAL W W 5 A G 4 31 4 31 A 4 31 4 56 3 18 Erp 6 Pdsign kW 10 0 Tbivalen C 10 SCOP W W 4 2 Annual consumption kWh 3333 Class A POWER FACTOR 97 96 95 NOISE INDOOR H M L d...

Страница 14: ...A T I N G CAPACITY kW 14 0 14 0 14 0 4 1 16 0 BTU h 47800 47800 47800 14000 54600 CURRENT A 0 17 4 0 17 4 0 16 4 16 0 15 5 15 0 INPUT POWER W 20 4 20 4 20 4 3 420k 3 420k 3 420k TOTAL W 3 500k 3 500k 3 500k 900 5 200k COP COP CLASS TOTAL W W 5 A G 4 00 4 00 A 4 00 4 56 3 08 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 30 28 27 Power...

Страница 15: ...I N G CAPACITY kW 14 0 14 0 14 0 4 1 16 0 BTU h 47800 47800 47800 14000 54600 CURRENT A 0 17 3 0 17 3 0 17 3 16 1 15 5 15 1 INPUT POWER W 20 3 20 3 20 3 3 440k 3 440k 3 440k TOTAL W 3 500k 3 500k 3 500k 900 5 200k COP COP CLASS TOTAL W W 5 A G 4 00 4 00 A 4 00 4 56 3 08 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 31 28 27 Power Lev...

Страница 16: ...565 477 424 HEAT m3 min ft3 min 16 13 5 12 565 477 424 O D AIR FLOW COOL m3 min ft3 min 30 1067 HEAT m3 min ft3 min 35 1225 REFRIGERANT TYPE AMOUNT g oz R410A 1 65k 58 2 P R O D I M HEIGHT H mm inch WIDTH W mm inch DEPTH D mm inch 256 10 3 32 840 33 3 32 840 33 3 32 569 22 13 32 790 31 7 64 285 11 7 32 P A C D I M HEIGHT H mm WIDTH W mm DEPTH D mm 298 929 929 645 921 386 MASS NET kg lb GROSS kg lb...

Страница 17: ... I N G CAPACITY kW 11 2 11 2 11 2 4 1 14 0 BTU h 38200 38200 38200 14000 47800 CURRENT A 0 20 2 0 20 2 0 19 2 11 9 11 5 11 1 INPUT POWER W 25 2 25 2 25 2 2 550k 2 550k 2 550k TOTAL W 2 600k 2 600k 2 600k 900 4 400k COP COP CLASS TOTAL W W 5 A G 4 31 4 31 A 4 31 4 56 3 18 Erp 6 Pdsign kW 10 0 Tbivalen C 10 SCOP W W 4 2 Annual consumption kWh 3333 Class A POWER FACTOR 97 96 96 NOISE INDOOR H M L dB ...

Страница 18: ... N G CAPACITY kW 16 0 16 0 16 0 4 1 18 0 BTU h 54600 54600 54600 14000 61400 CURRENT A 0 20 3 0 20 3 0 19 3 19 9 19 3 18 7 INPUT POWER W 25 3 25 3 25 3 4 255k 4 255k 4 255k TOTAL W 4 330k 4 330k 4 330k 900 5 900k COP COP CLASS TOTAL W W 5 A G 3 70 3 70 A 3 70 4 56 3 05 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 32 29 27 Power Leve...

Страница 19: ...T I N G CAPACITY kW 7 0 7 0 7 0 2 0 8 0 BTU h 23900 23900 23900 6800 27300 CURRENT A 0 30 0 30 0 29 8 50 8 20 7 95 INPUT POWER W 35 35 35 1 775k 1 775k 1 775k TOTAL W 1 810k 1 810k 1 810k 400 2 480k COP COP CLASS TOTAL W W 5 A G 3 87 3 87 A 3 87 5 00 3 23 Erp 6 Pdsign kW 6 0 Tbivalen C 10 SCOP W W 4 1 Annual consumption kWh 2047 Class A POWER FACTOR 95 94 93 NOISE INDOOR H M L dB A 36 31 28 Power ...

Страница 20: ... N G CAPACITY kW 14 0 14 0 14 0 4 1 16 0 BTU h 47800 47800 47800 14000 54600 CURRENT A 0 30 2 0 30 2 0 29 2 16 0 15 5 15 0 INPUT POWER W 35 2 35 2 35 2 3 430k 3 430k 3 430k TOTAL W 3 500k 3 500k 3 500k 900 5 200k COP COP CLASS TOTAL W W 5 A G 4 00 4 00 A 4 00 4 56 3 08 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 36 31 28 Power Leve...

Страница 21: ...7 600 494 HEAT m3 min ft3 min 22 17 14 777 600 494 O D AIR FLOW COOL m3 min ft3 min 60 2119 HEAT m3 min ft3 min 60 2119 REFRIGERANT TYPE AMOUNT g oz R410A 2 35k 82 9 P R O D I M HEIGHT H mm inch 256 10 3 32 996 39 7 32 WIDTH W mm inch 840 33 3 32 940 37 1 32 DEPTH D mm inch 840 33 3 32 340 13 13 32 P A C D I M HEIGHT H mm 298 1136 WIDTH W mm 929 1055 DEPTH D mm 929 485 MASS NET kg lb 24 53 69 152 ...

Страница 22: ... N G CAPACITY kW 16 0 16 0 16 0 4 1 18 0 BTU h 54600 54600 54600 14000 61400 CURRENT A 0 35 2 0 32 2 0 31 2 19 9 19 3 18 7 INPUT POWER W 40 2 40 2 40 2 4 250k 4 250k 4 250k TOTAL W 4 330k 4 330k 4 330k 900 5 900k COP COP CLASS TOTAL W W 5 A G 3 70 3 70 A 3 70 4 56 3 05 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 37 31 28 Power Leve...

Страница 23: ...I N G CAPACITY kW 11 2 11 2 11 2 4 1 14 0 BTU h 38200 38200 38200 14000 47800 CURRENT A 0 66 0 65 0 64 11 8 11 4 11 0 INPUT POWER W 85 85 85 2 515k 2 515k 2 515k TOTAL W 2 600k 2 600k 2 600k 900 4 400k COP COP CLASS TOTAL W W 5 A G 4 31 4 31 A 4 31 4 56 3 18 Erp 6 Pdsign kW 10 0 Tbivalen C 10 SCOP W W 4 2 Annual consumption kWh 3333 Class A POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 44 38 32 Po...

Страница 24: ...G CAPACITY kW 14 0 14 0 14 0 4 1 16 0 BTU h 47800 47800 47800 14000 54600 CURRENT A 0 75 0 73 0 73 15 9 15 4 14 9 INPUT POWER W 100 100 100 3 400k 3 400k 3 400k TOTAL W 3 500k 3 500k 3 500k 900 5 200k COP COP CLASS TOTAL W W 5 A G 4 00 4 00 A 4 00 4 56 3 08 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 45 39 33 Power Level dB 63 56 5...

Страница 25: ... CAPACITY kW 16 0 16 0 16 0 4 1 18 0 BTU h 54600 54600 54600 14000 61400 CURRENT A 0 83 0 80 0 79 19 8 19 2 18 6 INPUT POWER W 105 105 105 4 225k 4 225k 4 225k TOTAL W 4 330k 4 330k 4 330k 900 5 900k COP COP CLASS TOTAL W W 5 A G 3 70 3 70 A 3 70 4 56 3 05 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 46 40 34 Power Level dB 64 57 51...

Страница 26: ...E A T I N G CAPACITY kW 8 0 8 0 8 0 2 8 9 0 BTU h 27300 27300 27300 9600 30700 CURRENT A 0 17 2 0 17 2 0 16 2 3 10 3 00 2 90 INPUT POWER W 20 2 20 2 20 2 1 960k 1 960k 1 960k TOTAL W 2 000k 2 000k 2 000k 500 2 900k COP COP CLASS TOTAL W W 5 A G 4 00 4 00 A 4 00 5 60 3 10 Erp 6 Pdsign kW 7 1 Tbivalen C 8 SCOP W W 4 0 Annual consumption kWh 2485 Class A POWER FACTOR 96 94 94 NOISE INDOOR H M L dB A ...

Страница 27: ... T I N G CAPACITY kW 11 2 11 2 11 2 4 1 14 0 BTU h 38200 38200 38200 14000 47800 CURRENT A 0 17 3 0 17 3 0 16 3 4 10 3 90 3 80 INPUT POWER W 20 3 20 3 20 3 2 540k 2 540k 2 540k TOTAL W 2 600k 2 600k 2 600k 900 4 400k COP COP CLASS TOTAL W W 5 A G 4 31 4 31 A 4 31 4 56 3 18 Erp 6 Pdsign kW 10 0 Tbivalen C 10 SCOP W W 4 2 Annual consumption kWh 3333 Class A POWER FACTOR 94 94 93 NOISE INDOOR H M L d...

Страница 28: ...A T I N G CAPACITY kW 14 0 14 0 14 0 4 1 16 0 BTU h 47800 47800 47800 14000 54600 CURRENT A 0 17 4 0 17 4 0 16 4 5 55 5 25 5 10 INPUT POWER W 20 4 20 4 20 4 3 420k 3 420k 3 420k TOTAL W 3 500k 3 500k 3 500k 900 5 200k COP COP CLASS TOTAL W W 5 A G 4 00 4 00 A 4 00 4 56 3 08 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 94 94 93 NOISE INDOOR H M L dB A 30 28 27 Power...

Страница 29: ...I N G CAPACITY kW 14 0 14 0 14 0 4 1 16 0 BTU h 47800 47800 47800 14000 54600 CURRENT A 0 17 3 0 17 3 0 17 3 5 55 5 30 5 10 INPUT POWER W 20 3 20 3 20 3 3 440k 3 440k 3 440k TOTAL W 3 500k 3 500k 3 500k 900 5 200k COP COP CLASS TOTAL W W 5 A G 4 00 4 00 A 4 00 4 56 3 08 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 94 94 94 NOISE INDOOR H M L dB A 31 28 27 Power Lev...

Страница 30: ...I N G CAPACITY kW 11 2 11 2 11 2 4 1 14 0 BTU h 38200 38200 38200 14000 47800 CURRENT A 0 20 2 0 20 2 0 19 2 4 10 3 90 3 80 INPUT POWER W 25 2 25 2 25 2 2 550k 2 550k 2 550k TOTAL W 2 600k 2 600k 2 600k 900 4 400k COP COP CLASS TOTAL W W 5 A G 4 31 4 31 A 4 31 4 56 3 18 Erp 6 Pdsign kW 10 0 Tbivalen C 10 SCOP W W 4 2 Annual consumption kWh 3333 Class A POWER FACTOR 94 94 93 NOISE INDOOR H M L dB A...

Страница 31: ...N G CAPACITY kW 16 0 16 0 16 0 4 1 18 0 BTU h 54600 54600 54600 14000 61400 CURRENT A 0 20 3 0 20 3 0 19 3 6 90 6 55 6 30 INPUT POWER W 25 3 25 3 25 3 4 255k 4 255k 4 255k TOTAL W 4 330k 4 330k 4 330k 900 5 900k COP COP CLASS TOTAL W W 5 A G 3 70 3 70 A 3 70 4 56 3 05 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 94 94 94 NOISE INDOOR H M L dB A 32 29 27 Power Level...

Страница 32: ... N G CAPACITY kW 14 0 14 0 14 0 4 1 16 0 BTU h 47800 47800 47800 14000 54600 CURRENT A 0 30 2 0 30 2 0 29 2 5 55 5 25 5 10 INPUT POWER W 35 2 35 2 35 2 3 430k 3 430k 3 430k TOTAL W 3 500k 3 500k 3 500k 900 5 200k COP COP CLASS TOTAL W W 5 A G 4 00 4 00 A 4 00 4 56 3 08 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 94 94 94 NOISE INDOOR H M L dB A 36 31 28 Power Leve...

Страница 33: ... 600 494 HEAT m3 min ft3 min 22 17 14 777 600 494 O D AIR FLOW COOL m3 min ft3 min 60 2119 HEAT m3 min ft3 min 60 2119 REFRIGERANT TYPE AMOUNT g oz R410A 2 35k 82 9 P R O D I M HEIGHT H mm inch 256 10 3 32 996 39 7 32 WIDTH W mm inch 840 33 3 32 940 37 1 32 DEPTH D mm inch 840 33 3 32 340 13 13 32 P A C D I M HEIGHT H mm 298 1136 WIDTH W mm 929 1055 DEPTH D mm 929 485 MASS NET kg lb 24 53 71 157 G...

Страница 34: ... N G CAPACITY kW 16 0 16 0 16 0 4 1 18 0 BTU h 54600 54600 54600 14000 61400 CURRENT A 0 35 2 0 32 2 0 31 2 6 90 6 55 6 30 INPUT POWER W 40 2 40 2 40 2 4 250k 4 250k 4 250k TOTAL W 4 330k 4 330k 4 330k 900 5 900k COP COP CLASS TOTAL W W 5 A G 3 70 3 70 A 3 70 4 56 3 05 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 94 94 94 NOISE INDOOR H M L dB A 37 31 28 Power Leve...

Страница 35: ...I N G CAPACITY kW 11 2 11 2 11 2 4 1 14 0 BTU h 38200 38200 38200 14000 47800 CURRENT A 0 66 0 65 0 64 4 05 3 85 3 75 INPUT POWER W 85 85 85 2 515k 2 515k 2 515k TOTAL W 2 600k 2 600k 2 600k 900 4 400k COP COP CLASS TOTAL W W 5 A G 4 31 4 31 A 4 31 4 56 3 18 Erp 6 Pdsign kW 10 0 Tbivalen C 10 SCOP W W 4 2 Annual consumption kWh 3333 Class A POWER FACTOR 94 94 93 NOISE INDOOR H M L dB A 44 38 32 Po...

Страница 36: ... CAPACITY kW 14 0 14 0 14 0 4 1 16 0 BTU h 47800 47800 47800 14000 54600 CURRENT A 0 75 0 73 0 73 5 50 5 20 5 05 INPUT POWER W 100 100 100 3 400k 3 400k 3 400k TOTAL W 3 500k 3 500k 3 500k 900 5 200k COP COP CLASS TOTAL W W 5 A G 4 00 4 00 A 4 00 4 56 3 08 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 94 94 94 NOISE INDOOR H M L dB A 45 39 33 Power Level dB 63 56 50...

Страница 37: ... CAPACITY kW 16 0 16 0 16 0 4 1 18 0 BTU h 54600 54600 54600 14000 61400 CURRENT A 0 83 0 80 0 79 6 85 6 50 6 25 INPUT POWER W 105 105 105 4 225k 4 225k 4 225k TOTAL W 4 330k 4 330k 4 330k 900 5 900k COP COP CLASS TOTAL W W 5 A G 3 70 3 70 A 3 70 4 56 3 05 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 94 94 94 NOISE INDOOR H M L dB A 46 40 34 Power Level dB 64 57 51...

Страница 38: ...APACITY kW 8 0 8 0 8 0 2 0 9 0 BTU h 27300 27300 27300 6800 30700 CURRENT A 0 37 2 0 36 2 0 36 2 8 90 8 60 8 30 INPUT POWER W 35 2 35 2 35 2 1 875k 1 875k 1 875k TOTAL W 1 945k 1 945k 1 945k 400 2 900k COP COP CLASS TOTAL W W 5 A G 4 11 4 11 A 4 11 5 00 3 10 Erp 6 Pdsign kW 7 1 Tbivalen C 9 SCOP W W 4 0 Annual consumption kWh 2485 Class A POWER FACTOR 96 95 94 NOISE INDOOR H M L dB A 36 32 29 Powe...

Страница 39: ...PACITY kW 11 2 11 2 11 2 4 1 14 0 BTU h 38200 38200 38200 14000 47800 CURRENT A 0 37 3 0 36 3 0 35 3 11 8 11 4 11 0 INPUT POWER W 35 3 35 3 35 3 2 520k 2 520k 2 520k TOTAL W 2 625k 2 625k 2 625k 900 4 400k COP COP CLASS TOTAL W W 5 A G 4 27 4 27 A 4 27 4 56 3 18 Erp 6 Pdsign kW 10 0 Tbivalen C 10 SCOP W W 4 3 Annual consumption kWh 3256 Class A POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 36 32 2...

Страница 40: ...CITY kW 14 0 14 0 14 0 4 1 16 0 BTU h 47800 47800 47800 14000 54600 CURRENT A 0 37 4 0 36 4 0 35 4 16 0 15 4 14 9 INPUT POWER W 35 4 35 4 35 4 3 400k 3 400k 3 400k TOTAL W 3 540k 3 540k 3 540k 900 5 210k COP COP CLASS TOTAL W W 5 A G 3 95 3 95 A 3 95 4 56 3 07 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 36 32 29 Power Level dB 54 5...

Страница 41: ...Y kW 14 0 14 0 14 0 4 1 16 0 BTU h 47800 47800 47800 14000 54600 CURRENT A 0 39 3 0 38 3 0 37 3 16 0 15 4 14 9 INPUT POWER W 40 3 40 3 40 3 3 400k 3 400k 3 400k TOTAL W 3 520k 3 520k 3 520k 900 5 210k COP COP CLASS TOTAL W W 5 A G 3 98 3 98 A 3 98 4 56 3 07 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 37 33 29 Power Level dB 55 51 4...

Страница 42: ...ITY kW 5 6 5 6 5 6 1 5 6 5 BTU h 19100 19100 19100 5100 22200 CURRENT A 0 39 0 38 0 37 6 70 6 40 6 15 INPUT POWER W 40 40 40 1 370k 1 370k 1 370k TOTAL W 1 410k 1 410k 1 410k 220 2 300k COP COP CLASS TOTAL W W 5 A G 3 97 3 97 A 3 97 6 82 2 83 Erp 6 Pdsign kW 4 0 Tbivalen C 10 SCOP W W 4 0 Annual consumption kWh 1400 Class A POWER FACTOR 93 93 93 NOISE INDOOR H M L dB A 37 33 29 Power Level dB 55 5...

Страница 43: ...TY kW 11 2 11 2 11 2 4 1 14 0 BTU h 38200 38200 38200 14000 47800 CURRENT A 0 39 2 0 38 2 0 37 2 11 8 11 4 11 0 INPUT POWER W 40 2 40 2 40 2 2 520k 2 520k 2 520k TOTAL W 2 600k 2 600k 2 600k 900 4 400k COP COP CLASS TOTAL W W 5 A G 4 31 4 31 A 4 31 4 56 3 18 Erp 6 Pdsign kW 10 0 Tbivalen C 10 SCOP W W 4 3 Annual consumption kWh 3256 Class A POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 37 33 29 Po...

Страница 44: ...Y kW 16 0 16 0 16 0 4 1 18 0 BTU h 54600 54600 54600 14000 61400 CURRENT A 0 39 3 0 38 3 0 37 3 19 8 19 2 18 5 INPUT POWER W 40 3 40 3 40 3 4 240k 4 240k 4 240k TOTAL W 4 360k 4 360k 4 360k 900 5 930k COP COP CLASS TOTAL W W 5 A G 3 67 3 67 A 3 67 4 56 3 04 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 37 33 29 Power Level dB 55 51 4...

Страница 45: ...CITY kW 7 0 7 0 7 0 2 0 8 0 BTU h 23900 23900 23900 6800 27300 CURRENT A 0 42 0 41 0 40 8 10 7 80 7 60 INPUT POWER W 50 50 50 1 690k 1 690k 1 690k TOTAL W 1 740k 1 740k 1 740k 400 2 480k COP COP CLASS TOTAL W W 5 A G 4 02 4 02 A 4 02 5 00 3 23 Erp 6 Pdsign kW 6 0 Tbivalen C 10 SCOP W W 4 1 Annual consumption kWh 2049 Class A POWER FACTOR 95 94 93 NOISE INDOOR H M L dB A 38 34 30 Power Level dB 56 ...

Страница 46: ...Y kW 14 0 14 0 14 0 4 1 16 0 BTU h 47800 47800 47800 14000 54600 CURRENT A 0 42 2 0 41 2 0 40 2 16 0 15 4 14 9 INPUT POWER W 50 2 50 2 50 2 3 410k 3 410k 3 410k TOTAL W 3 510k 3 510k 3 510k 900 5 210k COP COP CLASS TOTAL W W 5 A G 3 99 3 99 A 3 99 4 56 3 07 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 38 34 30 Power Level dB 56 52 4...

Страница 47: ...CITY kW 8 0 8 0 8 0 2 0 9 0 BTU h 27300 27300 27300 6800 30700 CURRENT A 0 45 0 44 0 43 8 90 8 60 8 30 INPUT POWER W 55 55 55 1 875k 1 875k 1 875k TOTAL W 1 930k 1 930k 1 930k 400 2 900k COP COP CLASS TOTAL W W 5 A G 4 15 4 15 A 4 15 5 00 3 10 Erp 6 Pdsign kW 7 1 Tbivalen C 10 SCOP W W 4 0 Annual consumption kWh 2485 Class A POWER FACTOR 96 95 94 NOISE INDOOR H M L dB A 39 35 31 Power Level dB 57 ...

Страница 48: ...Y kW 16 0 16 0 16 0 4 1 18 0 BTU h 54600 54600 54600 14000 61400 CURRENT A 0 45 2 0 44 2 0 43 2 19 9 19 2 18 6 INPUT POWER W 55 2 55 2 55 2 4 250k 4 250k 4 250k TOTAL W 4 360k 4 360k 4 360k 900 5 930k COP COP CLASS TOTAL W W 5 A G 3 67 3 67 A 3 67 4 56 3 04 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 39 35 31 Power Level dB 57 53 4...

Страница 49: ...TY kW 11 2 11 2 11 2 4 1 14 0 BTU h 38200 38200 38200 14000 47800 CURRENT A 0 69 0 67 0 65 11 8 11 4 11 0 INPUT POWER W 80 80 80 2 520k 2 520k 2 520k TOTAL W 2 600k 2 600k 2 600k 900 4 400k COP COP CLASS TOTAL W W 5 A G 4 31 4 31 A 4 31 4 56 3 18 Erp 6 Pdsign kW 10 0 Tbivalen C 10 SCOP W W 4 3 Annual consumption kWh 3256 Class A POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 42 37 35 Power Level dB...

Страница 50: ...W 14 0 14 0 14 0 4 1 16 0 BTU h 47800 47800 47800 14000 54600 CURRENT A 0 89 0 86 0 83 16 0 15 4 14 9 INPUT POWER W 110 110 110 3 400k 3 400k 3 400k TOTAL W 3 510k 3 510k 3 510k 900 5 210k COP COP CLASS TOTAL W W 5 A G 3 99 3 99 A 3 99 4 56 3 07 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 46 40 36 Power Level dB 64 58 54 NOISE OUTD...

Страница 51: ... 16 0 16 0 16 0 4 1 18 0 BTU h 54600 54600 54600 14000 61400 CURRENT A 0 94 0 91 0 88 19 8 19 2 18 5 INPUT POWER W 120 120 120 4 240k 4 240k 4 240k TOTAL W 4 360k 4 360k 4 360k 900 5 930k COP COP CLASS TOTAL W W 5 A G 3 67 3 67 A 3 67 4 56 3 04 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 47 41 37 Power Level dB 65 59 55 NOISE OUTDO...

Страница 52: ... CAPACITY kW 8 0 8 0 8 0 2 0 9 0 BTU h 27300 27300 27300 6800 30700 CURRENT A 0 37 2 0 36 2 0 35 2 3 00 2 90 2 80 INPUT POWER W 35 2 35 2 35 2 1 875k 1 875k 1 875k TOTAL W 1 945k 1 945k 1 945k 400 2 900k COP COP CLASS TOTAL W W 5 A G 4 11 4 11 A 4 11 5 00 3 10 Erp 6 Pdsign kW 7 1 Tbivalen C 9 SCOP W W 4 0 Annual consumption kWh 2485 Class A POWER FACTOR 95 93 93 NOISE INDOOR H M L dB A 36 32 29 Po...

Страница 53: ...APACITY kW 11 2 11 2 11 2 4 1 14 0 BTU h 38200 38200 38200 14000 47800 CURRENT A 0 37 3 0 36 3 0 35 3 4 05 3 85 3 75 INPUT POWER W 35 3 35 3 35 3 2 520k 2 520k 2 520k TOTAL W 2 625k 2 625k 2 625k 900 4 400k COP COP CLASS TOTAL W W 5 A G 4 27 4 27 A 4 27 4 56 3 18 Erp 6 Pdsign kW 10 0 Tbivalen C 10 SCOP W W 4 3 Annual consumption kWh 3256 Class A POWER FACTOR 95 94 93 NOISE INDOOR H M L dB A 36 32 ...

Страница 54: ...CITY kW 14 0 14 0 14 0 4 1 16 0 BTU h 47800 47800 47800 14000 54600 CURRENT A 0 37 4 0 36 4 0 35 4 5 50 5 20 5 05 INPUT POWER W 35 4 35 4 35 4 3 400k 3 400k 3 400k TOTAL W 3 540k 3 540k 3 540k 900 5 210k COP COP CLASS TOTAL W W 5 A G 3 95 3 95 A 3 95 4 56 3 07 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 94 94 94 NOISE INDOOR H M L dB A 36 32 29 Power Level dB 54 5...

Страница 55: ...Y kW 14 0 14 0 14 0 4 1 16 0 BTU h 47800 47800 47800 14000 54600 CURRENT A 0 39 3 0 38 3 0 37 3 5 50 5 20 5 05 INPUT POWER W 40 3 40 3 40 3 3 400k 3 400k 3 400k TOTAL W 3 520k 3 520k 3 520k 900 5 210k COP COP CLASS TOTAL W W 5 A G 3 98 3 98 A 3 98 4 56 3 07 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 94 94 94 NOISE INDOOR H M L dB A 37 33 29 Power Level dB 55 51 4...

Страница 56: ...CITY kW 11 2 11 2 11 2 4 1 14 0 BTU h 38200 38200 38200 14000 47800 CURRENT A 0 39 2 0 38 2 0 37 2 4 05 3 85 3 75 INPUT POWER W 40 2 40 2 40 2 2 520k 2 520k 2 520k TOTAL W 2 600k 2 600k 2 600k 900 4 400k COP COP CLASS TOTAL W W 5 A G 4 31 4 31 A 4 31 4 56 3 18 Erp 6 Pdsign kW 10 0 Tbivalen C 10 SCOP W W 4 3 Annual consumption kWh 3256 Class A POWER FACTOR 95 94 93 NOISE INDOOR H M L dB A 37 33 29 ...

Страница 57: ...Y kW 16 0 16 0 16 0 4 1 18 0 BTU h 54600 54600 54600 14000 61400 CURRENT A 0 39 3 0 38 3 0 37 3 6 85 6 50 6 25 INPUT POWER W 40 3 40 3 40 3 4 240k 4 240k 4 240k TOTAL W 4 360k 4 360k 4 360k 900 5 930k COP COP CLASS TOTAL W W 5 A G 3 67 3 67 A 3 67 4 56 3 04 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 94 94 94 NOISE INDOOR H M L dB A 37 33 29 Power Level dB 55 51 4...

Страница 58: ...Y kW 14 0 14 0 14 0 4 1 14 0 BTU h 47800 47800 47800 14000 54600 CURRENT A 0 42 2 0 41 2 0 40 2 5 50 5 25 5 05 INPUT POWER W 50 2 50 2 50 2 3 410k 3 410k 3 410k TOTAL W 3 510k 3 510k 3 510k 900 5 210k COP COP CLASS TOTAL W W 5 A G 3 99 3 99 A 3 99 4 56 3 07 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 94 94 94 NOISE INDOOR H M L dB A 38 34 30 Power Level dB 56 52 4...

Страница 59: ...PACITY kW 8 0 8 0 8 0 2 0 9 0 BTU h 27300 27300 27300 6800 30700 CURRENT A 0 45 0 44 0 43 3 00 2 90 2 80 INPUT POWER W 55 55 55 1 875k 1 875k 1 875k TOTAL W 1 930k 1 930k 1 930k 400 2 900k COP COP CLASS TOTAL W W 5 A G 4 15 4 15 A 4 15 5 00 3 10 Erp 6 Pdsign kW 7 1 Tbivalen C 9 SCOP W W 4 0 Annual consumption kWh 2485 Class A POWER FACTOR 95 93 93 NOISE INDOOR H M L dB A 39 35 31 Power Level dB 57...

Страница 60: ...Y kW 16 0 16 0 16 0 4 1 18 0 BTU h 54600 54600 54600 14000 61400 CURRENT A 0 45 2 0 44 2 0 43 2 6 85 6 50 6 30 INPUT POWER W 55 2 55 2 55 2 4 250k 4 250k 4 250k TOTAL W 4 360k 4 360k 4 360k 900 5 930k COP COP CLASS TOTAL W W 5 A G 3 67 3 67 A 3 67 4 56 3 04 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 94 94 94 NOISE INDOOR H M L dB A 39 35 31 Power Level dB 57 53 4...

Страница 61: ...CITY kW 11 2 11 2 11 2 4 1 14 0 BTU h 38200 38200 38200 14000 47800 CURRENT A 0 69 0 67 0 65 4 05 3 85 3 75 INPUT POWER W 80 80 80 2 520k 2 520k 2 520k TOTAL W 2 600k 2 600k 2 600k 900 4 400k COP COP CLASS TOTAL W W 5 A G 4 31 4 31 A 4 31 4 56 3 18 Erp 6 Pdsign kW 10 0 Tbivalen C 10 SCOP W W 4 3 Annual consumption kWh 3256 Class A POWER FACTOR 95 94 93 NOISE INDOOR H M L dB A 42 37 35 Power Level ...

Страница 62: ...W 14 0 14 0 14 0 4 1 16 0 BTU h 47800 47800 47800 14000 54600 CURRENT A 0 89 0 86 0 83 5 50 5 20 5 05 INPUT POWER W 110 110 110 3 400k 3 400k 3 400k TOTAL W 3 510k 3 510k 3 510k 900 5 210k COP COP CLASS TOTAL W W 5 A G 3 99 3 99 A 3 99 4 56 3 07 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 94 94 94 NOISE INDOOR H M L dB A 46 40 36 Power Level dB 64 58 54 NOISE OUTD...

Страница 63: ... 16 0 16 0 16 0 4 1 18 0 BTU h 54600 54600 54600 14000 61400 CURRENT A 0 94 0 91 0 88 6 85 6 50 6 25 INPUT POWER W 120 120 120 4 240k 4 240k 4 240k TOTAL W 4 360k 4 360k 4 360k 900 5 930k COP COP CLASS TOTAL W W 5 A G 3 67 3 67 A 3 67 4 56 3 04 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 94 94 94 NOISE INDOOR H M L dB A 47 41 37 Power Level dB 65 59 55 NOISE OUTDO...

Страница 64: ...PACITY kW 8 0 8 0 8 0 2 0 9 0 BTU h 27300 27300 27300 6800 30700 CURRENT A 0 20 2 0 19 2 0 19 2 9 85 9 50 9 20 INPUT POWER W 16 2 17 2 17 2 2 095k 2 095k 2 095k TOTAL W 2 130k 2 130k 2 130k 400 2 900k COP COP CLASS TOTAL W W 5 A G 3 76 3 76 A 3 76 5 00 3 10 Erp 6 Pdsign kW 7 1 Tbivalen C 8 SCOP W W 3 9 Annual consumption kWh 2548 Class A POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 35 31 27 Power...

Страница 65: ...PACITY kW 11 2 11 2 11 2 4 1 14 0 BTU h 38200 38200 38200 14000 47800 CURRENT A 0 20 3 0 19 3 0 19 3 13 1 12 5 12 0 INPUT POWER W 16 3 17 3 17 3 2 705k 2 705k 2 700k TOTAL W 2 755k 2 760k 2 755k 900 4 400k COP COP CLASS TOTAL W W 5 A G 4 07 4 06 A 4 07 4 56 3 18 Erp 6 Pdsign kW 10 0 Tbivalen C 10 SCOP W W 4 0 Annual consumption kWh 3500 Class A POWER FACTOR 94 94 94 NOISE INDOOR H M L dB A 35 31 2...

Страница 66: ...CAPACITY kW 14 0 14 0 14 0 4 1 16 0 BTU h 47800 47800 47800 14000 54600 CURRENT A 0 20 4 0 19 4 0 19 4 17 3 16 7 16 2 INPUT POWER W 16 4 17 4 17 4 3 705k 3 705k 3 705k TOTAL W 3 770k 3 775k 3 775k 900 5 200k COP COP CLASS TOTAL W W 5 A G 3 71 3 71 A 3 71 4 56 3 08 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 35 31 27 Power Level dB ...

Страница 67: ... kW 14 0 14 0 14 0 4 1 16 0 BTU h 47800 47800 47800 14000 54600 CURRENT A 0 22 3 0 21 3 0 20 3 17 3 16 7 16 2 INPUT POWER W 20 3 20 3 20 3 3 705k 3 705k 3 705k TOTAL W 3 765k 3 765k 3 765k 900 5 200k COP COP CLASS TOTAL W W 5 A G 3 72 3 72 A 3 72 4 56 3 08 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 38 34 30 Power Level dB 55 49 44...

Страница 68: ... G CAPACITY kW 5 6 5 6 5 6 1 5 6 5 BTU h 19100 19100 19100 5100 22200 CURRENT A 0 27 0 27 0 27 6 95 6 75 6 50 INPUT POWER W 26 27 28 1 470k 1 470k 1 470k TOTAL W 1 500k 1 500k 1 500k 220 2 450k COP COP CLASS TOTAL W W 5 A G 3 73 3 73 A 3 73 6 82 2 65 Erp 6 Pdsign kW 4 0 Tbivalen C 10 SCOP W W 3 9 Annual consumption kWh 1436 Class A POWER FACTOR 96 95 94 NOISE INDOOR H M L dB A 40 36 32 Power Level...

Страница 69: ...ITY kW 11 2 11 2 11 2 4 1 14 0 BTU h 38200 38200 38200 14000 47800 CURRENT A 0 27 2 0 27 2 0 27 2 13 1 12 5 12 0 INPUT POWER W 26 2 27 2 28 2 2 705k 2 705k 2 705k TOTAL W 2 760k 2 760k 2 760k 900 4 400k COP COP CLASS TOTAL W W 5 A G 4 06 4 06 A 4 06 4 56 3 18 Erp 6 Pdsign kW 10 0 Tbivalen C 10 SCOP W W 4 0 Annual consumption kWh 3500 Class A POWER FACTOR 94 94 94 NOISE INDOOR H M L dB A 40 36 32 P...

Страница 70: ...Y kW 16 0 16 0 16 0 4 1 18 0 BTU h 54600 54600 54600 14000 61400 CURRENT A 0 27 3 0 27 3 0 27 3 21 9 21 2 20 5 INPUT POWER W 26 3 27 3 28 3 4 685k 4 685k 4 685k TOTAL W 4 765k 4 770k 4 770k 900 5 900k COP COP CLASS TOTAL W W 5 A G 3 36 3 35 C 3 35 4 56 3 05 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 40 36 32 Power Level dB 57 51 4...

Страница 71: ... kW 7 0 7 0 7 0 2 0 8 0 BTU h 23900 23900 23900 6800 27300 CURRENT A 0 59 0 58 0 52 8 45 8 15 7 90 INPUT POWER W 57 57 57 1 760k 1 760k 1 760k TOTAL W 1 820k 1 820k 1 820k 400 2 480k COP COP CLASS TOTAL W W 5 A G 3 85 3 85 A 3 85 5 00 3 23 Erp 6 Pdsign kW 6 0 Tbivalen C 10 SCOP W W 3 9 Annual consumption kWh 2154 Class A POWER FACTOR 95 94 93 NOISE INDOOR H M L dB A 47 44 40 Power Level dB 64 59 5...

Страница 72: ...14 0 14 0 14 0 4 1 16 0 BTU h 47800 47800 47800 14000 54600 CURRENT A 0 59 2 0 58 2 0 52 2 17 3 16 7 16 2 INPUT POWER W 57 2 57 2 57 2 3 705k 3 705k 3 705k TOTAL W 3 820k 3 820k 3 820k 900 5 200k COP COP CLASS TOTAL W W 5 A G 3 66 3 66 A 3 66 4 56 3 08 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 47 44 40 Power Level dB 64 59 54 NOI...

Страница 73: ...Y kW 8 0 8 0 8 0 2 0 9 0 BTU h 27300 27300 27300 6800 30700 CURRENT A 0 59 0 58 0 52 9 85 9 50 9 20 INPUT POWER W 57 57 57 2 070k 2 070k 2 070k TOTAL W 2 130k 2 130k 2 130k 400 2 900k COP COP CLASS TOTAL W W 5 A G 3 76 3 76 A 3 76 5 00 3 10 Erp 6 Pdsign kW 7 1 Tbivalen C 9 SCOP W W 3 9 Annual consumption kWh 2548 Class A POWER FACTOR 96 95 94 NOISE INDOOR H M L dB A 47 44 40 Power Level dB 64 59 5...

Страница 74: ... 16 0 16 0 16 0 4 1 18 0 BTU h 54600 54600 54600 14000 61400 CURRENT A 0 59 2 0 58 2 0 52 2 21 9 21 2 20 5 INPUT POWER W 57 2 57 2 57 2 4 685k 4 685k 4 685k TOTAL W 4 800k 4 800k 4 800k 900 5 900k COP COP CLASS TOTAL W W 5 A G 3 33 3 33 C 3 33 4 56 3 05 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 47 44 40 Power Level dB 64 59 54 NO...

Страница 75: ...885 HEAT m3 min ft3 min 95 3355 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 300 11 1 32 1416 55 3 4 WIDTH W mm inch 1065 41 23 64 940 37 1 32 DEPTH D mm inch 230 9 1 32 340 13 13 32 P A C D I M HEIGHT H mm 310 1556 WIDTH W mm 1140 1055 DEPTH D mm 380 485 MASS NET kg lb 14 5 32 98 216 GROSS kg lb 18 40 108 238 LAYERS LIMIT actually 15 16 1 2 Operation Condition Cool ...

Страница 76: ...APACITY kW 8 0 8 0 8 0 2 8 9 0 BTU h 27300 27300 27300 9600 30700 CURRENT A 0 20 2 0 19 2 0 19 2 3 35 3 25 3 15 INPUT POWER W 16 2 17 2 17 2 2 095k 2 095k 2 095k TOTAL W 2 130k 2 130k 2 130k 500 2 900k COP COP CLASS TOTAL W W 5 A G 3 76 3 76 A 3 76 5 60 3 10 Erp 6 Pdsign kW 7 1 Tbivalen C 8 SCOP W W 3 8 Annual consumption kWh 2616 Class A POWER FACTOR 95 93 93 NOISE INDOOR H M L dB A 35 31 27 Powe...

Страница 77: ...ACITY kW 11 2 11 2 11 2 4 1 14 0 BTU h 38200 38200 38200 14000 47800 CURRENT A 0 20 3 0 19 3 0 19 3 4 35 4 14 3 98 INPUT POWER W 16 3 17 3 17 3 2 705k 2 705k 2 700k TOTAL W 2 755k 2 760k 2 755k 900 4 400k COP COP CLASS TOTAL W W 5 A G 4 07 4 06 A 4 07 4 56 3 18 Erp 6 Pdsign kW 10 0 Tbivalen C 10 SCOP W W 4 0 Annual consumption kWh 3500 Class A POWER FACTOR 94 94 94 NOISE INDOOR H M L dB A 35 31 27...

Страница 78: ...ACITY kW 14 0 14 0 14 0 4 1 16 0 BTU h 47800 47800 47800 14000 54600 CURRENT A 0 20 4 0 19 4 0 19 4 5 78 5 55 5 40 INPUT POWER W 16 4 17 4 17 4 3 705k 3 705k 3 705k TOTAL W 3 770k 3 775k 3 775k 900 5 200k COP COP CLASS TOTAL W W 5 A G 3 71 3 71 A 3 71 4 56 3 08 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 35 31 27 Power Level dB 52 ...

Страница 79: ... kW 14 0 14 0 14 0 4 1 16 0 BTU h 47800 47800 47800 14000 54600 CURRENT A 0 22 3 0 21 3 0 20 3 5 78 5 55 5 40 INPUT POWER W 20 3 20 3 20 3 3 705k 3 705k 3 705k TOTAL W 3 765k 3 765k 3 765k 900 5 200k COP COP CLASS TOTAL W W 5 A G 3 72 3 72 A 3 72 4 56 3 08 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 38 34 30 Power Level dB 55 49 44...

Страница 80: ...CITY kW 11 2 11 2 11 2 4 1 14 0 BTU h 38200 38200 38200 14000 47800 CURRENT A 0 27 2 0 27 2 0 27 2 4 35 4 14 3 98 INPUT POWER W 26 2 27 2 28 2 2 705k 2 705k 2 700k TOTAL W 2 760k 2 760k 2 760k 900 4 400k COP COP CLASS TOTAL W W 5 A G 4 06 4 06 A 4 06 4 56 3 18 Erp 6 Pdsign kW 10 0 Tbivalen C 10 SCOP W W 4 0 Annual consumption kWh 3500 Class A POWER FACTOR 94 94 94 NOISE INDOOR H M L dB A 40 36 32 ...

Страница 81: ...Y kW 16 0 16 0 16 0 4 1 18 0 BTU h 54600 54600 54600 14000 61400 CURRENT A 0 27 3 0 27 3 0 27 3 7 31 6 94 6 76 INPUT POWER W 26 3 27 3 28 3 4 685k 4 685k 4 685k TOTAL W 4 765k 4 770k 4 770k 900 5 900k COP COP CLASS TOTAL W W 5 A G 3 36 3 35 C 3 35 4 56 3 05 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 97 96 NOISE INDOOR H M L dB A 40 36 32 Power Level dB 57 51 4...

Страница 82: ...14 0 14 0 14 0 4 1 16 0 BTU h 47800 47800 47800 14000 54600 CURRENT A 0 59 2 0 58 2 0 52 2 5 78 5 55 5 40 INPUT POWER W 57 2 57 2 57 2 3 705k 3 705k 3 705k TOTAL W 3 820k 3 820k 3 820k 900 5 200k COP COP CLASS TOTAL W W 5 A G 3 66 3 66 A 3 66 4 56 3 08 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 47 44 40 Power Level dB 64 59 54 NOI...

Страница 83: ...ITY kW 8 0 8 0 8 0 2 8 9 0 BTU h 27300 27300 27300 9600 30700 CURRENT A 0 59 0 58 0 52 3 30 3 20 3 10 INPUT POWER W 57 57 57 2 070k 2 070k 2 070k TOTAL W 2 130k 2 130k 2 130k 500 2 900k COP COP CLASS TOTAL W W 5 A G 3 76 3 76 A 3 76 5 60 3 10 Erp 6 Pdsign kW 7 1 Tbivalen C 9 SCOP W W 3 8 Annual consumption kWh 2616 Class A POWER FACTOR 95 93 93 NOISE INDOOR H M L dB A 47 44 40 Power Level dB 64 59...

Страница 84: ... 16 0 16 0 16 0 4 1 18 0 BTU h 54600 54600 54600 14000 61400 CURRENT A 0 59 2 0 58 2 0 52 2 7 31 6 94 6 76 INPUT POWER W 57 2 57 2 57 2 4 685k 4 685k 4 685k TOTAL W 4 800k 4 800k 4 800k 900 5 900k COP COP CLASS TOTAL W W 5 A G 3 33 3 33 C 3 33 4 56 3 05 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 97 96 95 NOISE INDOOR H M L dB A 47 44 40 Power Level dB 64 59 54 NO...

Страница 85: ...Y kW 9 5 9 5 9 5 4 1 11 5 BTU h 32400 32400 32400 14000 39200 CURRENT A 0 62 0 60 0 56 3 85 3 70 3 60 INPUT POWER W 65 65 65 2 405k 2 405k 2 405k TOTAL W 2 470k 2 470k 2 470k 900 3 350k COP COP CLASS TOTAL W W 5 A G 3 85 3 85 A 3 85 4 56 3 43 Erp 6 Pdsign kW 9 5 Tbivalen C 10 SCOP W W 3 8 Annual consumption kWh 3500 Class A POWER FACTOR 95 94 93 NOISE INDOOR H M L dB A 49 45 41 Power Level dB 65 6...

Страница 86: ...W COOL m3 min ft3 min 14 13 10 494 459 353 2 HEAT m3 min ft3 min 14 13 10 494 459 353 2 O D AIR FLOW COOL m3 min ft3 min 60 2119 HEAT m3 min ft3 min 60 2119 REFRIGERANT TYPE AMOUNT g oz R410A 2 35k 82 9 P R O D I M HEIGHT H mm inch 290 11 13 32 996 39 7 32 WIDTH W mm inch 800 31 1 2 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1136 WIDTH W mm 1014 1055 DEPTH D m...

Страница 87: ...AIR FLOW COOL m3 min ft3 min 14 13 10 494 459 353 3 HEAT m3 min ft3 min 14 13 10 494 459 353 3 O D AIR FLOW COOL m3 min ft3 min 110 3885 HEAT m3 min ft3 min 95 3355 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 290 11 13 32 1416 55 3 4 WIDTH W mm inch 800 31 1 2 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1556 WIDTH W mm 1014 1055 ...

Страница 88: ...min ft3 min 14 13 10 494 459 353 4 HEAT m3 min ft3 min 14 13 10 494 459 353 4 O D AIR FLOW COOL m3 min ft3 min 130 4591 HEAT m3 min ft3 min 110 3885 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 290 11 13 32 1416 55 3 4 WIDTH W mm inch 800 31 1 2 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1556 WIDTH W mm 1014 1055 DEPTH D mm 850 4...

Страница 89: ...ft3 min 14 13 10 494 459 353 3 HEAT m3 min ft3 min 14 13 10 494 459 353 3 O D AIR FLOW COOL m3 min ft3 min 130 4591 HEAT m3 min ft3 min 110 3885 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 290 11 13 32 1416 55 3 4 WIDTH W mm inch 800 31 1 2 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1556 WIDTH W mm 1014 1055 DEPTH D mm 850 485 M...

Страница 90: ...min 16 15 12 565 530 424 16 15 12 565 530 424 HEAT m3 min ft3 min O D AIR FLOW COOL m3 min ft3 min 30 1067 HEAT m3 min ft3 min 35 1225 REFRIGERANT TYPE AMOUNT g oz R410A 1 65k 58 2 P R O D I M HEIGHT H mm inch WIDTH W mm inch DEPTH D mm inch 290 11 13 32 800 31 1 2 700 27 9 16 569 22 13 32 790 31 7 64 285 11 7 32 P A C D I M HEIGHT H mm WIDTH W mm DEPTH D mm 355 1014 850 645 921 386 MASS NET kg lb...

Страница 91: ...I D AIR FLOW COOL m3 min ft3 min 16 15 12 565 530 424 2 HEAT m3 min ft3 min 16 15 12 565 530 424 2 O D AIR FLOW COOL m3 min ft3 min 110 3885 HEAT m3 min ft3 min 95 3355 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 290 11 13 32 1416 55 3 4 WIDTH W mm inch 800 31 1 2 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1556 WIDTH W mm 1014 1...

Страница 92: ...min ft3 min 16 15 12 565 530 424 3 HEAT m3 min ft3 min 16 15 12 565 530 424 3 O D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 290 11 13 32 1416 55 3 4 WIDTH W mm inch 800 31 1 2 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1556 WIDTH W mm 1014 1055 DEPTH D mm 850 4...

Страница 93: ...7 00 7 00 2 0 8 0 BTU h 23900 23900 23900 6800 27300 CURRENT A 0 91 0 89 0 87 8 70 8 40 8 10 INPUT POWER W 120 120 120 1 690k 1 690k 1 690k TOTAL W 1 810k 1 810k 1 810k 480 2 480k COP COP CLASS TOTAL W W 5 A G 3 87 A 3 87 A 3 87 A 4 17 3 23 Erp 6 Pdsign kW 6 0 Tbivalen C 10 SCOP W W 3 9 Annual consumption kWh 2154 Class A POWER FACTOR 95 94 93 NOISE INDOOR H M L dB A 35 32 26 Power Level dB 57 54 ...

Страница 94: ...in ft3 min 21 19 15 742 671 530 2 HEAT m3 min ft3 min 21 19 15 742 671 530 2 O D AIR FLOW COOL m3 min ft3 min 130 4591 HEAT m3 min ft3 min 110 3885 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 290 11 13 32 1416 55 3 4 WIDTH W mm inch 1000 39 3 8 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1556 WIDTH W mm 1214 1055 DEPTH D mm 850 4...

Страница 95: ... 21 19 15 742 671 530 HEAT m3 min ft3 min 21 19 15 742 671 530 O D AIR FLOW COOL m3 min ft3 min 60 2119 HEAT m3 min ft3 min 60 2119 REFRIGERANT TYPE AMOUNT g oz R410A 2 35k 82 9 P R O D I M HEIGHT H mm inch 290 11 13 32 996 39 7 32 WIDTH W mm inch 1000 39 3 8 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1136 WIDTH W mm 1214 1055 DEPTH D mm 850 485 MASS NET kg lb...

Страница 96: ...n ft3 min 21 19 15 742 671 530 2 HEAT m3 min ft3 min 21 19 15 742 671 530 2 O D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 290 11 13 32 1416 55 3 4 WIDTH W mm inch 1000 39 3 8 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1556 WIDTH W mm 1214 1055 DEPTH D mm 850 48...

Страница 97: ...2 26 21 1130 918 742 HEAT m3 min ft3 min 32 26 21 1130 918 742 O D AIR FLOW COOL m3 min ft3 min 110 3885 HEAT m3 min ft3 min 95 3355 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 290 11 13 32 1416 55 3 4 WIDTH W mm inch 1400 55 1 8 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1556 WIDTH W mm 1614 1055 DEPTH D mm 850 485 MASS NET kg ...

Страница 98: ...EAT m3 min ft3 min 34 29 23 1201 1024 812 O D AIR FLOW COOL m3 min ft3 min 130 4591 HEAT m3 min ft3 min 110 3885 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 290 11 13 32 1416 55 3 4 WIDTH W mm inch 1400 55 1 8 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1556 WIDTH W mm 1614 1055 DEPTH D mm 850 485 MASS NET kg lb 45 99 98 216 GROS...

Страница 99: ...EAT m3 min ft3 min 36 32 25 1271 1130 883 O D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 290 11 13 32 1416 55 3 4 WIDTH W mm inch 1400 55 1 8 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1556 WIDTH W mm 1614 1055 DEPTH D mm 850 485 MASS NET kg lb 45 99 98 216 GROS...

Страница 100: ... COOL m3 min ft3 min 14 13 10 494 459 353 2 HEAT m3 min ft3 min 14 13 10 494 459 353 2 O D AIR FLOW COOL m3 min ft3 min 60 2119 HEAT m3 min ft3 min 60 2119 REFRIGERANT TYPE AMOUNT g oz R410A 2 35k 82 9 P R O D I M HEIGHT H mm inch 290 11 13 32 996 39 7 32 WIDTH W mm inch 800 31 1 2 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1136 WIDTH W mm 1014 1055 DEPTH D mm...

Страница 101: ...IR FLOW COOL m3 min ft3 min 14 13 10 494 459 353 3 HEAT m3 min ft3 min 14 13 10 494 459 353 3 O D AIR FLOW COOL m3 min ft3 min 110 3885 HEAT m3 min ft3 min 95 3355 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 290 11 13 32 1416 55 3 4 WIDTH W mm inch 800 31 1 2 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1556 WIDTH W mm 1014 1055 D...

Страница 102: ...min ft3 min 14 13 10 494 459 353 4 HEAT m3 min ft3 min 14 13 10 494 459 353 4 O D AIR FLOW COOL m3 min ft3 min 130 4591 HEAT m3 min ft3 min 110 3885 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 290 11 13 32 1416 55 3 4 WIDTH W mm inch 800 31 1 2 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1556 WIDTH W mm 1014 1055 DEPTH D mm 850 4...

Страница 103: ...ft3 min 14 13 10 494 459 353 3 HEAT m3 min ft3 min 14 13 10 494 459 353 3 O D AIR FLOW COOL m3 min ft3 min 130 4591 HEAT m3 min ft3 min 110 3885 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 290 11 13 32 1416 55 3 4 WIDTH W mm inch 800 31 1 2 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1556 WIDTH W mm 1014 1055 DEPTH D mm 850 485 M...

Страница 104: ...D AIR FLOW COOL m3 min ft3 min 16 15 12 565 530 424 2 HEAT m3 min ft3 min 16 15 12 565 530 424 2 O D AIR FLOW COOL m3 min ft3 min 110 3885 HEAT m3 min ft3 min 95 3355 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 290 11 13 32 1416 55 3 4 WIDTH W mm inch 800 31 1 2 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1556 WIDTH W mm 1014 105...

Страница 105: ...min ft3 min 16 15 12 565 530 424 3 HEAT m3 min ft3 min 16 15 12 565 530 424 3 O D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 290 11 13 32 1416 55 3 4 WIDTH W mm inch 800 31 1 2 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1556 WIDTH W mm 1014 1055 DEPTH D mm 850 4...

Страница 106: ...in ft3 min 21 19 15 742 671 530 2 HEAT m3 min ft3 min 21 19 15 742 671 530 2 O D AIR FLOW COOL m3 min ft3 min 130 4591 HEAT m3 min ft3 min 110 3885 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 290 11 13 32 1416 55 3 4 WIDTH W mm inch 1000 39 3 8 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1556 WIDTH W mm 1214 1055 DEPTH D mm 850 4...

Страница 107: ...19 15 742 671 530 HEAT m3 min ft3 min 21 19 15 742 671 530 O D AIR FLOW COOL m3 min ft3 min 60 2119 HEAT m3 min ft3 min 60 2119 REFRIGERANT TYPE AMOUNT g oz R410A 2 35k 82 9 P R O D I M HEIGHT H mm inch 290 11 13 32 996 39 7 32 WIDTH W mm inch 1000 39 3 8 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1136 WIDTH W mm 1214 1055 DEPTH D mm 850 485 MASS NET kg lb 33 ...

Страница 108: ...n ft3 min 21 19 15 742 671 530 2 HEAT m3 min ft3 min 21 19 15 742 671 530 2 O D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 290 11 13 32 1416 55 3 4 WIDTH W mm inch 1000 39 3 8 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1556 WIDTH W mm 1214 1055 DEPTH D mm 850 48...

Страница 109: ... ft3 min 32 26 21 1130 918 742 HEAT m3 min ft3 min 32 26 21 1130 918 742 O D AIR FLOW COOL m3 min ft3 min 110 3885 HEAT m3 min ft3 min 95 3355 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 290 11 13 32 1416 55 3 4 WIDTH W mm inch 1400 55 1 8 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1556 WIDTH W mm 1614 1055 DEPTH D mm 850 485 MA...

Страница 110: ...1 1024 812 HEAT m3 min ft3 min 34 29 23 1201 1024 812 O D AIR FLOW COOL m3 min ft3 min 130 4591 HEAT m3 min ft3 min 110 3885 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 290 11 13 32 1416 55 3 4 WIDTH W mm inch 1400 55 1 8 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1556 WIDTH W mm 1614 1055 DEPTH D mm 850 485 MASS NET kg lb 45 99...

Страница 111: ...1 1130 883 HEAT m3 min ft3 min 36 32 25 1271 1130 883 O D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 290 11 13 32 1416 55 3 4 WIDTH W mm inch 1400 55 1 8 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1556 WIDTH W mm 1614 1055 DEPTH D mm 850 485 MASS NET kg lb 45 99...

Страница 112: ... min 14 12 10 494 424 353 2 HEAT m3 min ft3 min 14 12 10 494 424 353 2 O D AIR FLOW COOL m3 min ft3 min 60 2119 HEAT m3 min ft3 min 60 2119 REFRIGERANT TYPE AMOUNT g oz R410A 2 35k 82 9 P R O D I M HEIGHT H mm inch 250 9 27 32 996 39 7 32 WIDTH W mm inch 780 100 30 23 32 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 345 1136 WIDTH W mm 1007 1055 DEPTH D mm 7...

Страница 113: ...m3 min ft3 min 14 12 10 494 424 353 3 HEAT m3 min ft3 min 14 12 10 494 424 353 3 O D AIR FLOW COOL m3 min ft3 min 110 3885 HEAT m3 min ft3 min 95 3355 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 250 9 27 32 1416 55 3 4 WIDTH W mm inch 780 100 30 23 32 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 345 1556 WIDTH W mm 1007 1055 ...

Страница 114: ...4 12 10 494 424 353 4 HEAT m3 min ft3 min 14 12 10 494 424 353 4 O D AIR FLOW COOL m3 min ft3 min 130 4591 HEAT m3 min ft3 min 110 3885 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 250 9 27 32 1416 55 3 4 WIDTH W mm inch 780 100 30 23 32 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 345 1556 WIDTH W mm 1007 1055 DEPTH D mm 777 ...

Страница 115: ... 13 11 565 459 388 3 HEAT m3 min ft3 min 16 13 11 565 459 388 3 O D AIR FLOW COOL m3 min ft3 min 130 4591 HEAT m3 min ft3 min 110 3885 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 250 9 27 32 1416 55 3 4 WIDTH W mm inch 780 100 30 23 32 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 345 1556 WIDTH W mm 1007 1055 DEPTH D mm 777 4...

Страница 116: ...6 5 6 1 5 6 3 BTU h 19100 19100 19100 5100 21500 CURRENT A 0 54 0 55 0 56 8 00 7 70 7 40 INPUT POWER W 115 120 125 1 620k 1 620k 1 620k TOTAL W 1 735k 1 740k 1 745k 220 2 520k COP COP CLASS TOTAL W W 5 A G 3 23 3 22 C 3 21 6 82 2 50 Erp 6 Pdsign kW 3 8 Tbivalen C 10 SCOP W W 3 8 Annual consumption kWh 1400 Class A POWER FACTOR 92 91 91 NOISE INDOOR H M L dB A 41 39 35 Power Level dB 58 56 52 NOISE...

Страница 117: ...L m3 min ft3 min 16 13 11 565 459 388 2 HEAT m3 min ft3 min 16 13 11 565 459 388 2 O D AIR FLOW COOL m3 min ft3 min 110 3885 HEAT m3 min ft3 min 95 3355 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 250 9 27 32 1416 55 3 4 WIDTH W mm inch 780 100 30 23 32 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 345 1556 WIDTH W mm 1007 105...

Страница 118: ...13 11 565 459 388 3 HEAT m3 min ft3 min 16 13 11 565 459 388 3 O D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 250 9 27 32 1416 55 3 4 WIDTH W mm inch 780 100 30 23 32 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 345 1556 WIDTH W mm 1007 1055 DEPTH D mm 777 48...

Страница 119: ... m3 min ft3 min 22 20 16 777 706 565 O D AIR FLOW COOL m3 min ft3 min 60 2119 HEAT m3 min ft3 min 60 2119 REFRIGERANT TYPE AMOUNT g oz R410A 2 00k 70 5 P R O D I M HEIGHT H mm inch 250 9 27 32 996 39 7 32 WIDTH W mm inch 1000 100 39 5 16 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 338 1136 WIDTH W mm 1211 1055 DEPTH D mm 761 485 MASS NET kg lb 32 71 68 150...

Страница 120: ...20 16 777 706 565 2 HEAT m3 min ft3 min 22 20 16 777 706 565 2 O D AIR FLOW COOL m3 min ft3 min 130 4591 HEAT m3 min ft3 min 110 3885 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 250 9 27 32 1416 55 3 4 WIDTH W mm inch 1000 100 39 5 16 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 338 1556 WIDTH W mm 1211 1055 DEPTH D mm 761 48...

Страница 121: ...T m3 min ft3 min 22 20 16 777 706 565 O D AIR FLOW COOL m3 min ft3 min 60 2119 HEAT m3 min ft3 min 60 2119 REFRIGERANT TYPE AMOUNT g oz R410A 2 35k 82 9 P R O D I M HEIGHT H mm inch 250 9 27 32 996 39 7 32 WIDTH W mm inch 1000 100 39 5 16 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 338 1136 WIDTH W mm 1211 1055 DEPTH D mm 761 485 MASS NET kg lb 32 71 69 15...

Страница 122: ...20 16 777 706 565 2 HEAT m3 min ft3 min 22 20 16 777 706 565 2 O D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 250 9 27 32 1416 55 3 4 WIDTH W mm inch 1000 100 39 5 16 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 338 1556 WIDTH W mm 1211 1055 DEPTH D mm 761 48...

Страница 123: ...5 918 HEAT m3 min ft3 min 36 33 26 1271 1165 918 O D AIR FLOW COOL m3 min ft3 min 110 3885 HEAT m3 min ft3 min 95 3355 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 250 9 27 32 1416 55 3 4 WIDTH W mm inch 1200 100 47 1 4 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 338 1556 WIDTH W mm 1402 1055 DEPTH D mm 761 485 MASS NET kg lb...

Страница 124: ...3 min 38 35 28 1342 1236 989 O D AIR FLOW COOL m3 min ft3 min 130 4591 HEAT m3 min ft3 min 110 3885 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 250 9 27 32 1416 55 3 4 WIDTH W mm inch 1200 100 47 1 4 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 338 1556 WIDTH W mm 1402 1055 DEPTH D mm 761 485 MASS NET kg lb 41 91 98 216 GROSS...

Страница 125: ... min 40 37 30 1413 1307 1059 O D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 250 9 27 32 1416 55 3 4 WIDTH W mm inch 1200 100 47 1 4 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 338 1556 WIDTH W mm 1402 1055 DEPTH D mm 761 485 MASS NET kg lb 41 91 98 216 GROSS...

Страница 126: ... min 14 12 10 494 424 353 2 HEAT m3 min ft3 min 14 12 10 494 424 353 2 O D AIR FLOW COOL m3 min ft3 min 60 2119 HEAT m3 min ft3 min 60 2119 REFRIGERANT TYPE AMOUNT g oz R410A 2 35k 82 9 P R O D I M HEIGHT H mm inch 250 9 27 32 996 39 7 32 WIDTH W mm inch 780 100 30 23 32 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 345 1136 WIDTH W mm 1007 1055 DEPTH D mm 7...

Страница 127: ...min ft3 min 14 12 10 494 424 353 3 HEAT m3 min ft3 min 14 12 10 494 424 353 3 O D AIR FLOW COOL m3 min ft3 min 110 3885 HEAT m3 min ft3 min 95 3355 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 250 9 27 32 1416 55 3 4 WIDTH W mm inch 780 100 30 23 32 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 345 1556 WIDTH W mm 1007 1055 DEP...

Страница 128: ...4 12 10 494 424 353 4 HEAT m3 min ft3 min 14 12 10 494 424 353 4 O D AIR FLOW COOL m3 min ft3 min 130 4591 HEAT m3 min ft3 min 110 3885 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 250 9 27 32 1416 55 3 4 WIDTH W mm inch 780 100 30 23 32 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 345 1556 WIDTH W mm 1007 1055 DEPTH D mm 777 ...

Страница 129: ... 13 11 565 459 388 3 HEAT m3 min ft3 min 16 13 11 565 459 388 3 O D AIR FLOW COOL m3 min ft3 min 130 4591 HEAT m3 min ft3 min 110 3885 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 250 9 27 32 1416 55 3 4 WIDTH W mm inch 780 100 30 23 32 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 345 1556 WIDTH W mm 1007 1055 DEPTH D mm 777 4...

Страница 130: ...m3 min ft3 min 16 13 11 565 459 388 2 HEAT m3 min ft3 min 16 13 11 565 459 388 2 O D AIR FLOW COOL m3 min ft3 min 110 3885 HEAT m3 min ft3 min 95 3355 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 250 9 27 32 1416 55 3 4 WIDTH W mm inch 780 100 30 23 32 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 345 1556 WIDTH W mm 1007 1055 ...

Страница 131: ...13 11 565 459 388 3 HEAT m3 min ft3 min 16 13 11 565 459 388 3 O D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 250 9 27 32 1416 55 3 4 WIDTH W mm inch 780 100 30 23 32 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 345 1556 WIDTH W mm 1007 1055 DEPTH D mm 777 48...

Страница 132: ...20 16 777 706 565 2 HEAT m3 min ft3 min 22 20 16 777 706 565 2 O D AIR FLOW COOL m3 min ft3 min 130 4591 HEAT m3 min ft3 min 110 3885 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 250 9 27 32 1416 55 3 4 WIDTH W mm inch 1000 100 39 5 16 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 338 1556 WIDTH W mm 1211 1055 DEPTH D mm 761 48...

Страница 133: ... m3 min ft3 min 22 20 16 777 706 565 O D AIR FLOW COOL m3 min ft3 min 60 2119 HEAT m3 min ft3 min 60 2119 REFRIGERANT TYPE AMOUNT g oz R410A 2 35k 82 9 P R O D I M HEIGHT H mm inch 250 9 27 32 996 39 7 32 WIDTH W mm inch 1000 100 39 5 16 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 338 1136 WIDTH W mm 1211 1055 DEPTH D mm 761 485 MASS NET kg lb 32 71 71 157...

Страница 134: ...20 16 777 706 565 2 HEAT m3 min ft3 min 22 20 16 777 706 565 2 O D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 250 9 27 32 1416 55 3 4 WIDTH W mm inch 1000 100 39 5 16 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 338 1556 WIDTH W mm 1211 1055 DEPTH D mm 761 48...

Страница 135: ... 918 HEAT m3 min ft3 min 36 33 26 1271 1165 918 O D AIR FLOW COOL m3 min ft3 min 110 3885 HEAT m3 min ft3 min 95 3355 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 250 9 27 32 1416 55 3 4 WIDTH W mm inch 1200 100 47 1 4 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 338 1556 WIDTH W mm 1402 1055 DEPTH D mm 761 485 MASS NET kg lb ...

Страница 136: ...3 min 38 35 28 1342 1236 989 O D AIR FLOW COOL m3 min ft3 min 130 4591 HEAT m3 min ft3 min 110 3885 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 250 9 27 32 1416 55 3 4 WIDTH W mm inch 1200 100 47 1 4 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 338 1556 WIDTH W mm 1402 1055 DEPTH D mm 761 485 MASS NET kg lb 41 91 98 216 GROSS...

Страница 137: ...3 min 40 37 30 1413 1307 1059 O D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 250 9 27 32 1416 55 3 4 WIDTH W mm inch 1200 100 47 1 4 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 338 1556 WIDTH W mm 1402 1055 DEPTH D mm 761 485 MASS NET kg lb 41 91 98 216 GROS...

Страница 138: ...2119 REFRIGERANT TYPE AMOUNT g oz R410A 2 35k 82 9 P R O D I M HEIGHT H mm inch 260 265 23 10 1 4 996 39 7 32 WIDTH W mm inch 575 583 22 21 32 940 37 1 32 DEPTH D mm inch 575 583 22 21 32 340 13 13 32 Panel H W D mm 3A 31 700 700 3B 31 625 625 P A C D I M HEIGHT H mm 345 13 19 32 1136 WIDTH W mm 691 27 7 32 1055 DEPTH D mm 691 27 7 32 485 MASS NET kg lb 18 40 69 152 GROSS kg lb 23 51 77 170 Panel ...

Страница 139: ...5 3355 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 260 265 23 10 1 4 1416 55 3 4 WIDTH W mm inch 575 583 22 21 32 940 37 1 32 DEPTH D mm inch 575 583 22 21 32 340 13 13 32 Panel H W D mm 3A 31 700 700 3B 31 625 625 P A C D I M HEIGHT H mm 345 13 19 32 1556 WIDTH W mm 691 27 7 32 1055 DEPTH D mm 691 27 7 32 485 MASS NET kg lb 18 40 98 216 GROSS kg lb 23 51 108 238 Pa...

Страница 140: ...ERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 260 265 23 10 1 4 1416 55 3 4 WIDTH W mm inch 575 583 22 21 32 940 37 1 32 DEPTH D mm inch 575 583 22 21 32 340 13 13 32 Panel H W D mm 3A 31 700 700 3B 31 625 625 P A C D I M HEIGHT H mm 345 13 19 32 1556 WIDTH W mm 691 27 7 32 1055 DEPTH D mm 691 27 7 32 485 MASS NET kg lb 18 40 98 216 GROSS kg lb 23 51 108 238 Panel NET kg lb...

Страница 141: ...RANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 260 265 23 10 1 4 1416 55 3 4 WIDTH W mm inch 575 583 22 21 32 940 37 1 32 DEPTH D mm inch 575 583 22 21 32 340 13 13 32 Panel H W D mm 3A 31 700 700 3B 31 625 625 P A C D I M HEIGHT H mm 345 13 19 32 1556 WIDTH W mm 691 27 7 32 1055 DEPTH D mm 691 27 7 32 485 MASS NET kg lb 18 40 98 216 GROSS kg lb 23 51 108 238 Panel NET kg lb ...

Страница 142: ...n ft3 min 30 1059 HEAT m3 min ft3 min 35 1236 REFRIGERANT TYPE AMOUNT g oz R410A 1 65k 58 2 P R O D I M HEIGHT H mm inch 260 265 23 10 1 4 569 22 13 32 WIDTH W mm inch 575 583 22 21 32 790 31 7 64 DEPTH D mm inch 575 583 22 21 32 285 11 7 32 Panel H W D mm 3A 31 700 700 3B 31 625 625 P A C D I M HEIGHT H mm 345 13 19 32 645 WIDTH W mm 691 27 7 32 921 DEPTH D mm 691 27 7 32 386 MASS NET kg lb 18 40...

Страница 143: ...2 346 2 307 2 O D AIR FLOW COOL m3 min ft3 min 110 3885 HEAT m3 min ft3 min 95 3355 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 260 265 23 10 1 4 1416 55 3 4 WIDTH W mm inch 575 583 22 21 32 940 37 1 32 DEPTH D mm inch 575 583 22 21 32 340 13 13 32 Panel H W D mm 3A 31 700 700 3B 31 625 625 P A C D I M HEIGHT H mm 345 13 19 32 1556 WIDTH W mm 691 27 7 32 1055 DEPTH ...

Страница 144: ...D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 260 265 23 10 1 4 1416 55 3 4 WIDTH W mm inch 575 583 22 21 32 940 37 1 32 DEPTH D mm inch 575 583 22 21 32 340 13 13 32 Panel H W D mm 3A 31 700 700 3B 31 625 625 P A C D I M HEIGHT H mm 345 13 19 32 1556 WIDTH W mm 691 27 7 32 1055 DEPTH D mm 691 27 7 3...

Страница 145: ...EFRIGERANT TYPE AMOUNT g oz R410A 2 35k 82 9 P R O D I M HEIGHT H mm inch 260 265 23 10 1 4 996 39 7 32 WIDTH W mm inch 575 583 22 21 32 940 37 1 32 DEPTH D mm inch 575 583 22 21 32 340 13 13 32 Panel H W D mm 3A 31 700 700 3B 31 625 625 P A C D I M HEIGHT H mm 345 13 19 32 1136 WIDTH W mm 691 27 7 32 1055 DEPTH D mm 691 27 7 32 485 MASS NET kg lb 18 40 71 157 GROSS kg lb 23 51 79 174 Panel NET kg...

Страница 146: ... 3355 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 260 265 23 10 1 4 1416 55 3 4 WIDTH W mm inch 575 583 22 21 32 940 37 1 32 DEPTH D mm inch 575 583 22 21 32 340 13 13 32 Panel H W D mm 3A 31 700 700 3B 31 625 625 P A C D I M HEIGHT H mm 345 13 19 32 1556 WIDTH W mm 691 27 7 32 1055 DEPTH D mm 691 27 7 32 485 MASS NET kg lb 18 40 98 216 GROSS kg lb 23 51 108 238 Pan...

Страница 147: ...ERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 260 265 23 10 1 4 1416 55 3 4 WIDTH W mm inch 575 583 22 21 32 940 37 1 32 DEPTH D mm inch 575 583 22 21 32 340 13 13 32 Panel H W D mm 3A 31 700 700 3B 31 625 625 P A C D I M HEIGHT H mm 345 13 19 32 1556 WIDTH W mm 691 27 7 32 1055 DEPTH D mm 691 27 7 32 485 MASS NET kg lb 18 40 98 216 GROSS kg lb 23 51 108 238 Panel NET kg lb...

Страница 148: ...RANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 260 265 23 10 1 4 1416 55 3 4 WIDTH W mm inch 575 583 22 21 32 940 37 1 32 DEPTH D mm inch 575 583 22 21 32 340 13 13 32 Panel H W D mm 3A 31 700 700 3B 31 625 625 P A C D I M HEIGHT H mm 345 13 19 32 1556 WIDTH W mm 691 27 7 32 1055 DEPTH D mm 691 27 7 32 485 MASS NET kg lb 18 40 98 216 GROSS kg lb 23 51 108 238 Panel NET kg lb ...

Страница 149: ...346 2 307 2 O D AIR FLOW COOL m3 min ft3 min 110 3885 HEAT m3 min ft3 min 95 3355 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 260 265 23 10 1 4 1416 55 3 4 WIDTH W mm inch 575 583 22 21 32 940 37 1 32 DEPTH D mm inch 575 583 22 21 32 340 13 13 32 Panel H W D mm 3A 31 700 700 3B 31 625 625 P A C D I M HEIGHT H mm 345 13 19 32 1556 WIDTH W mm 691 27 7 32 1055 DEPTH D ...

Страница 150: ...D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 260 265 23 10 1 4 1416 55 3 4 WIDTH W mm inch 575 583 22 21 32 940 37 1 32 DEPTH D mm inch 575 583 22 21 32 340 13 13 32 Panel H W D mm 3A 31 700 700 3B 31 625 625 P A C D I M HEIGHT H mm 345 13 19 32 1556 WIDTH W mm 691 27 7 32 1055 DEPTH D mm 691 27 7 3...

Страница 151: ...er Level dB 50 70 H E A T I N G CAPACITY kW BTU h CURRENT A INPUT POWER W 7 1 24200 0 17 2 20 2 7 1 24200 0 17 2 20 2 7 1 24200 0 16 2 20 2 TOTAL W COP COP CLASS 1 8 6100 275 6 55 8 1 27600 2 510k 3 23 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 9 10 1 840k 1 880k 3 78 92 8 70 1 840k 1 880k 3 78 A 6 0 6 4 0 2100 A 92 8 30 1 840k 1 880k 3 78 92 NOISE INDOOR dB A H ...

Страница 152: ...LOW COOL m3 min ft3 min 16 13 5 12 565 477 424 2 HEAT m3 min ft3 min 16 13 5 12 565 477 424 2 O D AIR FLOW COOL m3 min ft3 min 76 2684 HEAT m3 min ft3 min 67 2366 REFRIGERANT TYPE AMOUNT g oz R410A 2 60k 91 7 P R O D I M HEIGHT H mm inch 256 10 3 32 996 39 7 32 WIDTH W mm inch 840 33 3 32 940 37 1 32 DEPTH D mm inch 840 33 3 32 340 13 13 32 P A C D I M HEIGHT H mm 298 1136 WIDTH W mm 929 1055 DEPT...

Страница 153: ...Power Level dB 46 65 H E A T I N G CAPACITY kW BTU h CURRENT A INPUT POWER W 6 0 20500 0 30 35 6 0 20500 0 30 35 6 0 20500 0 29 35 TOTAL W COP COP CLASS 1 8 6100 275 6 55 7 0 23900 2 155k 3 25 Erp Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 7 20 1 445k 1 480k 4 05 91 6 90 1 445k 1 480k 4 05 A 6 0 6 4 0 2100 A 91 6 60 1 445k 1 480k 4 05 91 NOISE INDOOR dB A H M L Power L...

Страница 154: ...3 min 21 17 14 742 600 494 2 HEAT m3 min ft3 min 21 17 14 742 600 494 2 O D AIR FLOW COOL m3 min ft3 min 80 2825 HEAT m3 min ft3 min 73 2578 REFRIGERANT TYPE AMOUNT g oz R410A 3 20k 112 9 P R O D I M HEIGHT H mm inch 256 10 3 32 996 39 7 32 WIDTH W mm inch 840 33 3 32 940 37 1 32 DEPTH D mm inch 840 33 3 32 340 13 13 32 P A C D I M HEIGHT H mm 298 1136 WIDTH W mm 929 1055 DEPTH D mm 929 485 MASS N...

Страница 155: ... L Power Level dB 50 70 H E A T I N G CAPACITY kW BTU h CURRENT A INPUT POWER W 7 1 24200 0 35 40 7 1 24200 0 32 40 7 1 24200 0 31 40 TOTAL W COP COP CLASS 1 8 6100 275 6 55 8 1 27600 2 510k 3 23 Erp Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 9 10 1 840k 1 880k 3 78 92 8 70 1 840k 1 880k 3 78 A 6 0 6 4 0 2100 A 92 8 30 1 840k 1 880k 3 78 92 NOISE INDOOR dB A H M L Powe...

Страница 156: ... 1165 953 742 HEAT m3 min ft3 min 33 27 21 1165 953 742 O D AIR FLOW COOL m3 min ft3 min 76 2684 HEAT m3 min ft3 min 67 2366 REFRIGERANT TYPE AMOUNT g oz R410A 2 60k 91 7 P R O D I M HEIGHT H mm inch 319 12 9 16 996 39 7 32 WIDTH W mm inch 840 33 3 32 940 37 1 32 DEPTH D mm inch 840 33 3 32 340 13 13 32 P A C D I M HEIGHT H mm 361 1136 WIDTH W mm 929 1055 DEPTH D mm 929 485 MASS NET kg lb 27 60 73...

Страница 157: ...AT m3 min ft3 min 35 28 22 1236 989 777 O D AIR FLOW COOL m3 min ft3 min 80 2825 HEAT m3 min ft3 min 73 2578 REFRIGERANT TYPE AMOUNT g oz R410A 3 20k 112 9 P R O D I M HEIGHT H mm inch 319 12 9 16 996 39 7 32 WIDTH W mm inch 840 33 3 32 940 37 1 32 DEPTH D mm inch 840 33 3 32 340 13 13 32 P A C D I M HEIGHT H mm 361 1136 WIDTH W mm 929 1055 DEPTH D mm 929 485 MASS NET kg lb 27 60 85 187 GROSS kg l...

Страница 158: ...OW COOL m3 min ft3 min 16 13 5 12 565 477 424 2 HEAT m3 min ft3 min 16 13 5 12 565 477 424 2 O D AIR FLOW COOL m3 min ft3 min 76 2684 HEAT m3 min ft3 min 67 2366 REFRIGERANT TYPE AMOUNT g oz R410A 2 60k 91 7 P R O D I M HEIGHT H mm inch 256 10 3 32 996 39 7 32 WIDTH W mm inch 840 33 3 32 940 37 1 32 DEPTH D mm inch 840 33 3 32 340 13 13 32 P A C D I M HEIGHT H mm 298 1136 WIDTH W mm 929 1055 DEPTH...

Страница 159: ...3 min 21 17 14 742 600 494 2 HEAT m3 min ft3 min 21 17 14 742 600 494 2 O D AIR FLOW COOL m3 min ft3 min 80 2825 HEAT m3 min ft3 min 73 2578 REFRIGERANT TYPE AMOUNT g oz R410A 3 20k 112 9 P R O D I M HEIGHT H mm inch 256 10 3 32 996 39 7 32 WIDTH W mm inch 840 33 3 32 940 37 1 32 DEPTH D mm inch 840 33 3 32 340 13 13 32 P A C D I M HEIGHT H mm 298 1136 WIDTH W mm 929 1055 DEPTH D mm 929 485 MASS N...

Страница 160: ...min 22 17 14 777 600 494 2 HEAT m3 min ft3 min 22 17 14 777 600 494 2 O D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 256 10 3 32 1416 55 3 4 WIDTH W mm inch 840 33 3 32 940 37 1 32 DEPTH D mm inch 840 33 3 32 340 13 13 32 P A C D I M HEIGHT H mm 298 1556 WIDTH W mm 929 1055 DEPTH D mm 929 485 MASS N...

Страница 161: ...165 953 742 HEAT m3 min ft3 min 33 27 21 1165 953 742 O D AIR FLOW COOL m3 min ft3 min 76 2684 HEAT m3 min ft3 min 67 2366 REFRIGERANT TYPE AMOUNT g oz R410A 2 60k 91 7 P R O D I M HEIGHT H mm inch 319 12 9 16 996 39 7 32 WIDTH W mm inch 840 33 3 32 940 37 1 32 DEPTH D mm inch 840 33 3 32 340 13 13 32 P A C D I M HEIGHT H mm 361 1136 WIDTH W mm 929 1055 DEPTH D mm 929 485 MASS NET kg lb 27 60 73 1...

Страница 162: ...AT m3 min ft3 min 35 28 22 1236 989 777 O D AIR FLOW COOL m3 min ft3 min 80 2825 HEAT m3 min ft3 min 73 2578 REFRIGERANT TYPE AMOUNT g oz R410A 3 20k 112 9 P R O D I M HEIGHT H mm inch 319 12 9 16 996 39 7 32 WIDTH W mm inch 840 33 3 32 940 37 1 32 DEPTH D mm inch 840 33 3 32 340 13 13 32 P A C D I M HEIGHT H mm 361 1136 WIDTH W mm 929 1055 DEPTH D mm 929 485 MASS NET kg lb 27 60 85 187 GROSS kg l...

Страница 163: ...AT m3 min ft3 min 36 29 23 1271 1024 812 O D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 319 12 9 16 1416 55 3 4 WIDTH W mm inch 840 33 3 32 940 37 1 32 DEPTH D mm inch 840 33 3 32 340 13 13 32 P A C D I M HEIGHT H mm 361 1556 WIDTH W mm 929 1055 DEPTH D mm 929 485 MASS NET kg lb 27 60 98 216 GROSS k...

Страница 164: ...ft3 min 14 12 10 5 494 424 371 2 HEAT m3 min ft3 min 14 12 10 5 494 424 371 2 O D AIR FLOW COOL m3 min ft3 min 39 1377 HEAT m3 min ft3 min 39 1377 REFRIGERANT TYPE AMOUNT g oz R410A 1 70k 60 0 P R O D I M HEIGHT H mm inch 235 9 1 4 569 22 13 32 WIDTH W mm inch 960 37 25 32 790 31 7 64 DEPTH D mm inch 690 27 5 32 285 11 7 32 P A C D I M HEIGHT H mm 360 645 WIDTH W mm 1025 921 DEPTH D mm 820 386 MAS...

Страница 165: ...in ft3 min 15 12 5 10 5 530 441 371 2 HEAT m3 min ft3 min 15 12 5 10 5 530 441 371 2 O D AIR FLOW COOL m3 min ft3 min 76 2684 HEAT m3 min ft3 min 67 2366 REFRIGERANT TYPE AMOUNT g oz R410A 2 60k 91 7 P R O D I M HEIGHT H mm inch 235 9 1 4 996 39 7 32 WIDTH W mm inch 960 37 25 32 940 37 1 32 DEPTH D mm inch 690 27 5 32 340 13 13 32 P A C D I M HEIGHT H mm 360 1136 WIDTH W mm 1025 1055 DEPTH D mm 82...

Страница 166: ...t h 3 4 7 1 External static pressure Pa I D AIR FLOW COOL m3 min ft3 min 20 17 14 5 706 600 512 HEAT m3 min ft3 min 20 17 14 5 706 600 512 O D AIR FLOW COOL m3 min ft3 min 30 1059 HEAT m3 min ft3 min 35 1236 REFRIGERANT TYPE AMOUNT g oz R410A 1 70k 60 0 P R O D I M HEIGHT H mm inch 235 9 1 4 569 22 13 32 WIDTH W mm inch 1275 50 3 16 790 31 7 64 DEPTH D mm inch 690 27 5 32 285 11 7 32 P A C D I M H...

Страница 167: ...4 5 706 600 512 2 HEAT m3 min ft3 min 20 17 14 5 706 600 512 2 O D AIR FLOW COOL m3 min ft3 min 80 2825 HEAT m3 min ft3 min 73 2578 REFRIGERANT TYPE AMOUNT g oz R410A 3 20k 112 9 P R O D I M HEIGHT H mm inch 235 9 1 4 996 39 7 32 WIDTH W mm inch 1275 50 3 16 940 37 1 32 DEPTH D mm inch 690 27 5 32 340 13 13 32 P A C D I M HEIGHT H mm 360 1136 WIDTH W mm 1340 1055 DEPTH D mm 820 485 MASS NET kg lb ...

Страница 168: ...Pt h 4 2 8 8 External static pressure Pa I D AIR FLOW COOL m3 min ft3 min 21 18 15 5 742 636 547 HEAT m3 min ft3 min 21 18 15 5 742 636 547 O D AIR FLOW COOL m3 min ft3 min 39 1377 HEAT m3 min ft3 min 39 1377 REFRIGERANT TYPE AMOUNT g oz R410A 1 70k 60 0 P R O D I M HEIGHT H mm inch 235 9 1 4 569 22 13 32 WIDTH W mm inch 1275 50 3 16 790 31 7 64 DEPTH D mm inch 690 27 5 32 285 11 7 32 P A C D I M ...

Страница 169: ... L h Pt h 6 0 12 6 External static pressure Pa I D AIR FLOW COOL m3 min ft3 min 30 25 23 1059 883 812 HEAT m3 min ft3 min 30 25 23 1059 883 812 O D AIR FLOW COOL m3 min ft3 min 76 2684 HEAT m3 min ft3 min 67 2366 REFRIGERANT TYPE AMOUNT g oz R410A 2 60k 91 7 P R O D I M HEIGHT H mm inch 235 9 1 4 996 39 7 32 WIDTH W mm inch 1590 62 19 32 940 37 1 32 DEPTH D mm inch 690 27 5 32 340 13 13 32 P A C D...

Страница 170: ...6 6 External static pressure Pa I D AIR FLOW COOL m3 min ft3 min 34 28 24 1201 989 848 HEAT m3 min ft3 min 34 28 24 1201 989 848 O D AIR FLOW COOL m3 min ft3 min 80 2825 HEAT m3 min ft3 min 73 2578 REFRIGERANT TYPE AMOUNT g oz R410A 3 20k 112 9 P R O D I M HEIGHT H mm inch 235 9 1 4 996 39 7 32 WIDTH W mm inch 1590 62 19 32 940 37 1 32 DEPTH D mm inch 690 27 5 32 340 13 13 32 P A C D I M HEIGHT H ...

Страница 171: ...n ft3 min 15 12 5 10 5 530 441 371 2 HEAT m3 min ft3 min 15 12 5 10 5 530 441 371 2 O D AIR FLOW COOL m3 min ft3 min 76 2684 HEAT m3 min ft3 min 67 2366 REFRIGERANT TYPE AMOUNT g oz R410A 2 60k 91 7 P R O D I M HEIGHT H mm inch 235 9 1 4 996 39 7 32 WIDTH W mm inch 960 37 25 32 940 37 1 32 DEPTH D mm inch 690 27 5 32 340 13 13 32 P A C D I M HEIGHT H mm 360 1136 WIDTH W mm 1025 1055 DEPTH D mm 820...

Страница 172: ...4 5 706 600 512 2 HEAT m3 min ft3 min 20 17 14 5 706 600 512 2 O D AIR FLOW COOL m3 min ft3 min 80 2825 HEAT m3 min ft3 min 73 2578 REFRIGERANT TYPE AMOUNT g oz R410A 3 20k 112 9 P R O D I M HEIGHT H mm inch 235 9 1 4 996 39 7 32 WIDTH W mm inch 1275 50 3 16 940 37 1 32 DEPTH D mm inch 690 27 5 32 340 13 13 32 P A C D I M HEIGHT H mm 360 1136 WIDTH W mm 1340 1055 DEPTH D mm 820 485 MASS NET kg lb ...

Страница 173: ... 5 742 636 547 2 HEAT m3 min ft3 min 21 18 15 5 742 636 547 2 O D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 235 9 1 4 1416 55 3 4 WIDTH W mm inch 1275 50 3 16 940 37 1 32 DEPTH D mm inch 690 27 5 32 340 13 13 32 P A C D I M HEIGHT H mm 360 1556 WIDTH W mm 1340 1055 DEPTH D mm 820 485 MASS NET kg lb...

Страница 174: ...L h Pt h 6 0 12 6 External static pressure Pa I D AIR FLOW COOL m3 min ft3 min 30 25 23 1059 883 812 HEAT m3 min ft3 min 30 25 23 1059 883 812 O D AIR FLOW COOL m3 min ft3 min 76 2684 HEAT m3 min ft3 min 67 2366 REFRIGERANT TYPE AMOUNT g oz R410A 2 60k 91 7 P R O D I M HEIGHT H mm inch 235 9 1 4 996 39 7 32 WIDTH W mm inch 1590 62 19 32 940 37 1 32 DEPTH D mm inch 690 27 5 32 340 13 13 32 P A C D ...

Страница 175: ...6 6 External static pressure Pa I D AIR FLOW COOL m3 min ft3 min 34 28 24 1201 989 848 HEAT m3 min ft3 min 34 28 24 1201 989 848 O D AIR FLOW COOL m3 min ft3 min 80 2825 HEAT m3 min ft3 min 73 2578 REFRIGERANT TYPE AMOUNT g oz R410A 3 20k 112 9 P R O D I M HEIGHT H mm inch 235 9 1 4 996 39 7 32 WIDTH W mm inch 1590 62 19 32 940 37 1 32 DEPTH D mm inch 690 27 5 32 340 13 13 32 P A C D I M HEIGHT H ...

Страница 176: ...9 External static pressure Pa I D AIR FLOW COOL m3 min ft3 min 35 29 25 1236 1024 883 HEAT m3 min ft3 min 35 29 25 1236 1024 883 O D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 235 9 1 4 1416 55 3 4 WIDTH W mm inch 1590 62 19 32 940 37 1 32 DEPTH D mm inch 690 27 5 32 340 13 13 32 P A C D I M HEIGHT ...

Страница 177: ...ft3 min 11 9 5 7 5 388 335 265 2 HEAT m3 min ft3 min 11 9 5 7 5 388 335 265 2 O D AIR FLOW COOL m3 min ft3 min 39 1377 HEAT m3 min ft3 min 39 1377 REFRIGERANT TYPE AMOUNT g oz R410A 1 70k 60 0 P R O D I M HEIGHT H mm inch 300 11 1 32 569 22 13 32 WIDTH W mm inch 1065 41 15 16 790 31 7 64 DEPTH D mm inch 230 9 1 32 285 11 7 32 P A C D I M HEIGHT H mm 310 648 WIDTH W mm 1140 921 DEPTH D mm 380 386 M...

Страница 178: ...L m3 min ft3 min 14 12 10 5 494 424 371 2 HEAT m3 min ft3 min 14 12 10 5 494 424 371 2 O D AIR FLOW COOL m3 min ft3 min 76 2684 HEAT m3 min ft3 min 67 2366 REFRIGERANT TYPE AMOUNT g oz R410A 2 60k 91 7 P R O D I M HEIGHT H mm inch 300 11 1 32 996 39 7 32 WIDTH W mm inch 1065 41 23 64 940 37 1 32 DEPTH D mm inch 230 9 1 32 340 13 13 32 P A C D I M HEIGHT H mm 310 1136 WIDTH W mm 1140 1055 DEPTH D m...

Страница 179: ...dB 46 65 H E A T I N G CAPACITY kW BTU h CURRENT A INPUT POWER W 6 0 20500 0 59 57 6 0 20500 0 58 57 6 0 20500 0 52 57 TOTAL W COP COP CLASS 1 8 6100 275 6 55 7 0 23900 2 200k 3 18 Erp Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 7 05 1 440k 1 500k 4 00 93 6 80 1 440k 1 500k 4 00 A 6 0 6 3 9 2154 A 92 6 60 1 440k 1 500k 4 00 91 NOISE INDOOR dB A H M L Power Level dB NOIS...

Страница 180: ...5 11 5 636 512 406 2 HEAT m3 min ft3 min 18 14 5 11 5 636 512 406 2 O D AIR FLOW COOL m3 min ft3 min 80 2825 HEAT m3 min ft3 min 73 2578 REFRIGERANT TYPE AMOUNT g oz R410A 3 20k 112 9 P R O D I M HEIGHT H mm inch 300 11 1 32 996 39 7 32 WIDTH W mm inch 1065 41 23 64 940 37 1 32 DEPTH D mm inch 230 9 1 32 340 13 13 32 P A C D I M HEIGHT H mm 310 1136 WIDTH W mm 1140 1055 DEPTH D mm 380 485 MASS NET...

Страница 181: ...6 HEAT m3 min ft3 min 18 14 5 11 5 636 512 406 O D AIR FLOW COOL m3 min ft3 min 39 1377 HEAT m3 min ft3 min 39 1377 REFRIGERANT TYPE AMOUNT g oz R410A 1 70k 60 0 P R O D I M HEIGHT H mm inch 300 11 1 32 569 22 13 32 WIDTH W mm inch 1065 41 15 16 790 31 7 64 DEPTH D mm inch 230 9 1 32 285 11 7 32 P A C D I M HEIGHT H mm 310 648 WIDTH W mm 1140 921 DEPTH D mm 380 386 MASS NET kg lb 14 5 32 42 93 GRO...

Страница 182: ...EAT m3 min ft3 min 19 16 5 13 671 583 459 O D AIR FLOW COOL m3 min ft3 min 76 2684 HEAT m3 min ft3 min 67 2366 REFRIGERANT TYPE AMOUNT g oz R410A 2 60k 91 7 P R O D I M HEIGHT H mm inch 300 11 1 32 996 39 7 32 WIDTH W mm inch 1065 41 23 64 940 37 1 32 DEPTH D mm inch 230 9 1 32 340 13 13 32 P A C D I M HEIGHT H mm 310 1136 WIDTH W mm 1140 1055 DEPTH D mm 380 485 MASS NET kg lb 14 5 32 73 161 GROSS...

Страница 183: ...m3 min ft3 min 14 12 10 5 494 424 371 2 HEAT m3 min ft3 min 14 12 10 5 494 424 371 2 O D AIR FLOW COOL m3 min ft3 min 76 2684 HEAT m3 min ft3 min 67 2366 REFRIGERANT TYPE AMOUNT g oz R410A 2 60k 91 7 P R O D I M HEIGHT H mm inch 300 11 1 32 996 39 7 32 WIDTH W mm inch 1065 41 23 64 940 37 1 32 DEPTH D mm inch 230 9 1 32 340 13 13 32 P A C D I M HEIGHT H mm 310 1136 WIDTH W mm 1140 1055 DEPTH D mm ...

Страница 184: ...5 11 5 636 512 406 2 HEAT m3 min ft3 min 18 14 5 11 5 636 512 406 2 O D AIR FLOW COOL m3 min ft3 min 80 2825 HEAT m3 min ft3 min 73 2578 REFRIGERANT TYPE AMOUNT g oz R410A 3 20k 112 9 P R O D I M HEIGHT H mm inch 300 11 1 32 996 39 7 32 WIDTH W mm inch 1065 41 23 64 940 37 1 32 DEPTH D mm inch 230 9 1 32 340 13 13 32 P A C D I M HEIGHT H mm 310 1136 WIDTH W mm 1140 1055 DEPTH D mm 380 485 MASS NET...

Страница 185: ...11 5 636 512 406 2 HEAT m3 min ft3 min 18 14 5 11 5 636 512 406 2 O D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 300 11 1 32 1416 55 3 4 WIDTH W mm inch 1065 41 23 64 940 37 1 32 DEPTH D mm inch 230 9 1 32 340 13 13 32 P A C D I M HEIGHT H mm 310 1556 WIDTH W mm 1140 1055 DEPTH D mm 380 485 MASS NET...

Страница 186: ...HEAT m3 min ft3 min 19 16 5 13 671 583 459 O D AIR FLOW COOL m3 min ft3 min 76 2684 HEAT m3 min ft3 min 67 2366 REFRIGERANT TYPE AMOUNT g oz R410A 2 60k 91 7 P R O D I M HEIGHT H mm inch 300 11 1 32 996 39 7 32 WIDTH W mm inch 1065 41 23 64 940 37 1 32 DEPTH D mm inch 230 9 1 32 340 13 13 32 P A C D I M HEIGHT H mm 310 1136 WIDTH W mm 1140 1055 DEPTH D mm 380 485 MASS NET kg lb 14 5 32 73 161 GROS...

Страница 187: ... A T I N G CAPACITY kW BTU h CURRENT A INPUT POWER W 7 1 24200 0 6 2 70 2 7 1 24200 0 57 2 70 2 7 1 24200 0 56 2 70 2 TOTAL W COP COP CLASS 1 8 6100 275 6 55 8 1 27600 2 400k 3 38 Erp Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 8 30 1 680k 1 820k 3 90 5 50 92 7 90 1 680k 1 820k 3 90 A 5 50 7 00 3 80 2026 A 92 7 60 1 680k 1 820k 3 90 5 50 92 NOISE INDOOR dB A H M L Power...

Страница 188: ... 120 2 90 MOISTURE REMOVAL VOLUME L h Pt h 6 0 3 0 2 12 6 External static pressure Pa 70 MIN10 MAX150 I D AIR FLOW COOL m3 min ft3 min 16 15 12 565 530 424 2 HEAT m3 min ft3 min 16 15 12 565 530 424 2 O D AIR FLOW COOL m3 min ft3 min 76 2684 HEAT m3 min ft3 min 67 2366 REFRIGERANT TYPE AMOUNT g oz R410A 2 60k 91 7 P R O D I M HEIGHT H mm inch 290 11 13 32 996 39 7 32 WIDTH W mm inch 800 31 1 2 940...

Страница 189: ... 46 65 H E A T I N G CAPACITY kW BTU h CURRENT A INPUT POWER W 6 0 20500 0 91 120 6 0 20500 0 89 120 6 0 20500 0 87 120 TOTAL W COP COP CLASS 1 8 6100 275 6 55 7 0 23900 2 055k 3 41 Erp Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 6 40 1 290k 1 410k 4 25 A 92 6 10 1 290k 1 410k 4 25 A 5 0 9 3 8 1842 A 92 5 90 1 290k 1 410k 4 25 A 91 NOISE INDOOR dB A H M L Power Level dB...

Страница 190: ...MOVAL VOLUME L h Pt h 7 9 3 95 2 16 6 External static pressure Pa 70 MIN10 MAX150 I D AIR FLOW COOL m3 min ft3 min 21 19 15 742 671 530 2 HEAT m3 min ft3 min 21 19 15 742 671 530 2 O D AIR FLOW COOL m3 min ft3 min 80 2825 HEAT m3 min ft3 min 73 2578 REFRIGERANT TYPE AMOUNT g oz R410A 3 20k 112 9 P R O D I M HEIGHT H mm inch 290 11 13 32 996 39 7 32 WIDTH W mm inch 1000 39 3 8 940 37 1 32 DEPTH D m...

Страница 191: ...er Level dB 50 70 H E A T I N G CAPACITY kW BTU h CURRENT A INPUT POWER W 7 1 24200 0 91 120 7 1 24200 0 89 120 7 1 24200 0 87 120 TOTAL W COP COP CLASS 1 8 6100 275 6 55 8 1 27600 2 380k 3 40 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 8 30 1 680k 1 800k 3 94 92 7 90 1 680k 1 800k 3 94 A 5 5 7 3 8 2026 A 92 7 60 1 680k 1 800k 3 94 92 NOISE INDOOR dB A H M L Power...

Страница 192: ...LUME L h Pt h 6 0 12 6 External static pressure Pa 100 MIN10 MAX150 I D AIR FLOW COOL m3 min ft3 min 32 26 21 1130 918 742 HEAT m3 min ft3 min 32 26 21 1130 918 742 O D AIR FLOW COOL m3 min ft3 min 76 2684 HEAT m3 min ft3 min 67 2366 REFRIGERANT TYPE AMOUNT g oz R410A 2 60k 91 7 P R O D I M HEIGHT H mm inch 290 11 13 32 996 39 7 32 WIDTH W mm inch 1400 55 1 8 940 37 1 32 DEPTH D mm inch 700 27 9 1...

Страница 193: ... 6 External static pressure Pa 100 MIN10 MAX150 I D AIR FLOW COOL m3 min ft3 min 34 29 23 1201 1024 812 HEAT m3 min ft3 min 34 29 23 1201 1024 812 O D AIR FLOW COOL m3 min ft3 min 80 2825 HEAT m3 min ft3 min 73 2578 REFRIGERANT TYPE AMOUNT g oz R410A 3 20k 112 9 P R O D I M HEIGHT H mm inch 290 11 13 32 996 39 7 32 WIDTH W mm inch 1400 55 1 8 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P ...

Страница 194: ...120 2 90 MOISTURE REMOVAL VOLUME L h Pt h 6 0 3 0 2 12 6 External static pressure Pa 70 MIN10 MAX150 I D AIR FLOW COOL m3 min ft3 min 16 15 12 565 530 424 2 HEAT m3 min ft3 min 16 15 12 565 530 424 2 O D AIR FLOW COOL m3 min ft3 min 76 2684 HEAT m3 min ft3 min 67 2366 REFRIGERANT TYPE AMOUNT g oz R410A 2 60k 91 7 P R O D I M HEIGHT H mm inch 290 11 13 32 996 39 7 32 WIDTH W mm inch 800 31 1 2 940 ...

Страница 195: ...MOVAL VOLUME L h Pt h 7 9 3 95 2 16 6 External static pressure Pa 70 MIN10 MAX150 I D AIR FLOW COOL m3 min ft3 min 21 19 15 742 671 530 2 HEAT m3 min ft3 min 21 19 15 742 671 530 2 O D AIR FLOW COOL m3 min ft3 min 80 2825 HEAT m3 min ft3 min 73 2578 REFRIGERANT TYPE AMOUNT g oz R410A 3 20k 112 9 P R O D I M HEIGHT H mm inch 290 11 13 32 996 39 7 32 WIDTH W mm inch 1000 39 3 8 940 37 1 32 DEPTH D m...

Страница 196: ...m3 min ft3 min 21 19 15 742 671 530 2 HEAT m3 min ft3 min 21 19 15 742 671 530 2 O D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 290 11 13 32 1416 55 3 4 WIDTH W mm inch 1000 39 3 8 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1556 WIDTH W mm 1214 1055 DEPTH D mm 8...

Страница 197: ...UME L h Pt h 6 0 12 6 External static pressure Pa 100 MIN10 MAX150 I D AIR FLOW COOL m3 min ft3 min 32 26 21 1130 918 742 HEAT m3 min ft3 min 32 26 21 1130 918 742 O D AIR FLOW COOL m3 min ft3 min 76 2684 HEAT m3 min ft3 min 67 2366 REFRIGERANT TYPE AMOUNT g oz R410A 2 60k 91 7 P R O D I M HEIGHT H mm inch 290 11 13 32 996 39 7 32 WIDTH W mm inch 1400 55 1 8 940 37 1 32 DEPTH D mm inch 700 27 9 16...

Страница 198: ... 6 External static pressure Pa 100 MIN10 MAX150 I D AIR FLOW COOL m3 min ft3 min 34 29 23 1201 1024 812 HEAT m3 min ft3 min 34 29 23 1201 1024 812 O D AIR FLOW COOL m3 min ft3 min 80 2825 HEAT m3 min ft3 min 73 2578 REFRIGERANT TYPE AMOUNT g oz R410A 3 20k 112 9 P R O D I M HEIGHT H mm inch 290 11 13 32 996 39 7 32 WIDTH W mm inch 1400 55 1 8 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P ...

Страница 199: ... 883 HEAT m3 min ft3 min 36 32 25 1271 1130 883 O D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 290 11 13 32 1416 55 3 4 WIDTH W mm inch 1400 55 1 8 940 37 1 32 DEPTH D mm inch 700 27 9 16 340 13 13 32 P A C D I M HEIGHT H mm 355 1556 WIDTH W mm 1614 1055 DEPTH D mm 850 485 MASS NET kg lb 45 99 98 21...

Страница 200: ...n ft3 min 14 12 10 494 424 353 2 HEAT m3 min ft3 min 14 12 10 494 424 353 2 O D AIR FLOW COOL m3 min ft3 min 39 1377 HEAT m3 min ft3 min 39 1377 REFRIGERANT TYPE AMOUNT g oz R410A 1 70k 60 0 P R O D I M HEIGHT H mm inch 250 9 27 32 569 22 13 32 WIDTH W mm inch 780 100 30 23 32 3 15 16 790 31 7 64 DEPTH D mm inch 650 25 19 32 285 11 7 32 P A C D I M HEIGHT H mm 345 645 WIDTH W mm 1007 921 DEPTH D m...

Страница 201: ...W COOL m3 min ft3 min 16 13 11 565 459 388 2 HEAT m3 min ft3 min 16 13 11 565 459 388 2 O D AIR FLOW COOL m3 min ft3 min 76 2684 HEAT m3 min ft3 min 67 2366 REFRIGERANT TYPE AMOUNT g oz R410A 2 60k 91 7 P R O D I M HEIGHT H mm inch 250 9 27 32 996 39 7 32 WIDTH W mm inch 780 100 30 23 32 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 345 1136 WIDTH W mm 1007 ...

Страница 202: ...G CAPACITY kW BTU h CURRENT A INPUT POWER W 6 0 20500 1 12 140 6 0 20500 1 08 140 6 0 20500 1 04 140 TOTAL W COP COP CLASS 1 8 6100 275 6 55 7 0 23900 2 420k 2 89 Erp 6 Pdsign kW Tbivalen C SCOP W W Annual consumption kWh Class POWER FACTOR 7 50 1 520k 1 660k 3 61 92 7 20 1 520k 1 660k 3 61 A 4 8 10 3 8 1757 A 92 6 90 1 520k 1 660k 3 61 92 NOISE INDOOR dB A H M L Power Level dB NOISE OUTDOOR dB A ...

Страница 203: ...in 22 20 16 777 706 565 2 HEAT m3 min ft3 min 22 20 16 777 706 565 2 O D AIR FLOW COOL m3 min ft3 min 80 2825 HEAT m3 min ft3 min 73 2578 REFRIGERANT TYPE AMOUNT g oz R410A 3 20k 112 9 P R O D I M HEIGHT H mm inch 250 9 27 32 996 39 7 32 WIDTH W mm inch 1000 100 39 5 16 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 338 1136 WIDTH W mm 1211 1055 DEPTH D mm 76...

Страница 204: ...6 565 HEAT m3 min ft3 min 22 20 16 777 706 565 O D AIR FLOW COOL m3 min ft3 min 39 1377 HEAT m3 min ft3 min 39 1377 REFRIGERANT TYPE AMOUNT g oz R410A 1 70k 60 0 P R O D I M HEIGHT H mm inch 250 9 27 32 569 22 13 32 WIDTH W mm inch 1000 100 39 5 16 3 15 16 790 31 7 64 DEPTH D mm inch 650 25 19 32 285 11 7 32 P A C D I M HEIGHT H mm 338 645 WIDTH W mm 1211 921 DEPTH D mm 761 386 MASS NET kg lb 32 7...

Страница 205: ...71 1165 918 HEAT m3 min ft3 min 36 33 26 1271 1165 918 O D AIR FLOW COOL m3 min ft3 min 76 2684 HEAT m3 min ft3 min 67 2366 REFRIGERANT TYPE AMOUNT g oz R410A 2 60k 91 7 P R O D I M HEIGHT H mm inch 250 9 27 32 996 39 7 32 WIDTH W mm inch 1200 100 47 1 4 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 338 1136 WIDTH W mm 1402 1055 DEPTH D mm 761 485 MASS NET k...

Страница 206: ...min ft3 min 38 35 28 1342 1236 989 O D AIR FLOW COOL m3 min ft3 min 80 2825 HEAT m3 min ft3 min 73 2578 REFRIGERANT TYPE AMOUNT g oz R410A 3 20k 112 9 P R O D I M HEIGHT H mm inch 250 9 27 32 996 39 7 32 WIDTH W mm inch 1200 100 47 1 4 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 338 1136 WIDTH W mm 1402 1055 DEPTH D mm 761 485 MASS NET kg lb 41 91 85 187 G...

Страница 207: ... COOL m3 min ft3 min 16 13 11 565 459 388 2 HEAT m3 min ft3 min 16 13 11 565 459 388 2 O D AIR FLOW COOL m3 min ft3 min 76 2684 HEAT m3 min ft3 min 67 2366 REFRIGERANT TYPE AMOUNT g oz R410A 2 60k 91 7 P R O D I M HEIGHT H mm inch 250 9 27 32 996 39 7 32 WIDTH W mm inch 780 100 30 23 32 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 345 1136 WIDTH W mm 1007 1...

Страница 208: ...in 22 20 16 777 706 565 2 HEAT m3 min ft3 min 22 20 16 777 706 565 2 O D AIR FLOW COOL m3 min ft3 min 80 2825 HEAT m3 min ft3 min 73 2578 REFRIGERANT TYPE AMOUNT g oz R410A 3 20k 112 9 P R O D I M HEIGHT H mm inch 250 9 27 32 996 39 7 32 WIDTH W mm inch 1000 100 39 5 16 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 338 1136 WIDTH W mm 1211 1055 DEPTH D mm 76...

Страница 209: ... 22 20 16 777 706 565 2 HEAT m3 min ft3 min 22 20 16 777 706 565 2 O D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 250 9 27 32 1416 55 3 4 WIDTH W mm inch 1000 100 39 5 16 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 338 1556 WIDTH W mm 1211 1055 DEPTH D mm 76...

Страница 210: ... 1165 918 HEAT m3 min ft3 min 36 33 26 1271 1165 918 O D AIR FLOW COOL m3 min ft3 min 76 2684 HEAT m3 min ft3 min 67 2366 REFRIGERANT TYPE AMOUNT g oz R410A 2 60k 91 7 P R O D I M HEIGHT H mm inch 250 9 27 32 996 39 7 32 WIDTH W mm inch 1200 100 47 1 4 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 338 1136 WIDTH W mm 1402 1055 DEPTH D mm 761 485 MASS NET kg ...

Страница 211: ...min ft3 min 38 35 28 1342 1236 989 O D AIR FLOW COOL m3 min ft3 min 80 2825 HEAT m3 min ft3 min 73 2578 REFRIGERANT TYPE AMOUNT g oz R410A 3 20k 112 9 P R O D I M HEIGHT H mm inch 250 9 27 32 996 39 7 32 WIDTH W mm inch 1200 100 47 1 4 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 338 1136 WIDTH W mm 1402 1055 DEPTH D mm 761 485 MASS NET kg lb 41 91 85 187 G...

Страница 212: ...in ft3 min 40 37 30 1413 1307 1059 O D AIR FLOW COOL m3 min ft3 min 135 4767 HEAT m3 min ft3 min 120 4238 REFRIGERANT TYPE AMOUNT g oz R410A 3 40k 119 9 P R O D I M HEIGHT H mm inch 250 9 27 32 1416 55 3 4 WIDTH W mm inch 1200 100 47 1 4 3 15 16 940 37 1 32 DEPTH D mm inch 650 25 19 32 340 13 13 32 P A C D I M HEIGHT H mm 338 1556 WIDTH W mm 1402 1055 DEPTH D mm 761 485 MASS NET kg lb 41 91 98 216...

Страница 213: ...REFRIGERANT TYPE AMOUNT g oz R410A 1 70k 60 0 P R O D I M HEIGHT H mm inch 260 265 23 10 1 4 569 22 13 32 WIDTH W mm inch 575 583 22 21 32 790 31 7 64 DEPTH D mm inch 575 583 22 21 32 285 11 7 32 Panel H W D mm 3A 31 700 700 3B 31 625 625 P A C D I M HEIGHT H mm 345 13 19 32 645 WIDTH W mm 691 27 7 32 921 DEPTH D mm 691 27 7 32 386 MASS NET kg lb 18 40 42 93 GROSS kg lb 23 51 46 101 Panel NET kg l...

Страница 214: ... 346 2 307 2 O D AIR FLOW COOL m3 min ft3 min 76 2684 HEAT m3 min ft3 min 67 2366 REFRIGERANT TYPE AMOUNT g oz R410A 2 60k 91 7 P R O D I M HEIGHT H mm inch 260 265 23 10 1 4 996 39 7 32 WIDTH W mm inch 575 583 22 21 32 940 37 1 32 DEPTH D mm inch 575 583 22 21 32 340 13 13 32 Panel H W D mm 3A 31 700 700 3B 31 625 625 P A C D I M HEIGHT H mm 345 13 19 32 1136 WIDTH W mm 691 27 7 32 1055 DEPTH D m...

Страница 215: ...346 2 307 2 O D AIR FLOW COOL m3 min ft3 min 76 2684 HEAT m3 min ft3 min 67 2366 REFRIGERANT TYPE AMOUNT g oz R410A 2 60k 91 7 P R O D I M HEIGHT H mm inch 260 265 23 10 1 4 996 39 7 32 WIDTH W mm inch 575 583 22 21 32 940 37 1 32 DEPTH D mm inch 575 583 22 21 32 340 13 13 32 Panel H W D mm 3A 31 700 700 3B 31 625 625 P A C D I M HEIGHT H mm 345 13 19 32 1136 WIDTH W mm 691 27 7 32 1055 DEPTH D mm...

Страница 216: ...840 50 271 145 160 160 82 unit mm 130 480 130 167 480 2 840 167 124 514 950 515 950 95 124 95 180 30 18 118 256 115 115 80 80 Necessary to provide optional air intake kit Filter dimension 520 x 520 x 16 The length of the suspension bolts should be selected so that there is a gap of 30 mm or more below the lower surface of the ceiling 18 mm or more below the lower surface of the main unit as shown ...

Страница 217: ... Detailed view Y 4 ø3 burring hole 4 ø3 burring hole ø162 ø113 The length of the suspension bolts should be selected so that there is a gap of 30 mm or more below the lower surface of the ceiling 18 mm or more below the lower surface of the main unit as shown in the figure at right If the suspension bolt is too long it will contact the ceiling panel and the unit cannot be installed 7 8 130 480 130...

Страница 218: ...vice space Over 250 90 Over 250 Approx 2 Air discharge Minimum 50cm 4 15 4 13 3 2 216 5 14 10 11 12 6 131 196 235 185 105 196 176 96 123 86 70 97 90 90 120 1 Drain port VP20 inside diameter ø26mm drain hose supplied 2 Left drain position 3 Refrigerant liquid tubing ø6 35mm flare connection ø100 cutout ø113 4 ø3 1 4 Refrigerant gas tubing ø12 7mm flare connection 5 Cover of rear tubing hole 6 Tubin...

Страница 219: ...iew from front Filter size 579 x 250 x 16 x 2 pcs Distance of each exposed bolt must be of equal length within 50mm unit mm Detailed view of intaking outside air duct connection port 1 Drain port VP20 inside diameter ø26mm drain hose supplied 2 Left drain position 3 Refrigerant liquid tubing ø9 52mm flare connection 4 Refrigerant gas tubing ø15 88mm flare connection 5 Cover of rear tubing hole 6 T...

Страница 220: ...bolt must be of equal length within 50mm unit mm Detailed view of intaking outside air duct connection port 1 Drain port VP20 inside diameter ø26mm drain hose supplied 2 Left drain position 3 Refrigerant liquid tubing ø9 52mm flare connection 4 Refrigerant gas tubing ø15 88mm flare connection 5 Cover of rear tubing hole 6 Tubing hole on wall surface ø100mm 7 Upper side tubing port 8 Right side dra...

Страница 221: ...n hose VP13 outer dia ø18 4 Rear panel PL BACK Refrigerant tubing gas tube 5 Rear panel fixing holes ø5 holes or 5X13 elongated holes 6 Piping coiring holes ø80 unit mm 1065 300 230 3 70 8 60 95 95 231 m c 5 m c 5 7 5 cm 450 384 200 140 67 300 415 415 448 440 497 568 ø 8 0 ø 8 0 158 132 48 48 37 18 4 6 3 2 1 Z Z view Nessesary minimum space for a installation Front view 5 SM830231 02 Single 欧州 ind...

Страница 222: ...0 Pitch 150 7 71 1 192 20 Unit mm Air intake port side Air outlet duct side F ø3 holes E Flange O D A Suspension bolt pitch a Refrigerant tubing joint liquid tube b Refrigerant tubing joint gas tube c Upper drain port VP25 O D 32 mm 200 flexible hose supplied d Bottom drain port VP25 O D 32 mm e Suspension lug 4 12 30 mm f Power supply outlet g Fresh air intake port ø150 mm h Flange for flexible a...

Страница 223: ...Outside Dimensions MODEL NO UNIT mm No 1 2 3 4 5 6 NAME Q TY NOTE Air Flow Pipe connection liquid 1 1 2 2 4 1 Pipe connection gas Drain pipe connection Hanger Duct connection Control box O D Ø12 7 Flared 24 Ø4 5 22 Ø4 5 O D Ø6 35 Flared Female screw PT1 S 45PN1E5A S 36PN1E5A S 50PN1E5A 58 48 31 65 161 48 30 650 30 31 32 187 55 55 100 670 585 P65 x 9 650 P65 x 10 65 64 250 80 65 740 780 523 134 45 ...

Страница 224: ...0 890 65 64 250 80 65 960 1000 523 57 5 20 58 48 31 65 161 48 30 650 30 31 32 187 134 134 1060 5 4 4 3 2 1 6 NO 1 2 3 4 5 6 NAME NOTE Pipe connection liquid Q TY 1 1 2 2 4 1 Pipe connection gas Drain pipe connection Hanger Duct connection Control box O D Ø15 88 Flared O D Ø9 52 Flared Female screw PT1 Outside Dimensions MODEL NO UNIT mm S 100PN1E5A S 140PN1E5A S 125PN1E5A 100 1260 1090 250 64 46 Ø...

Страница 225: ... surface becomes 45mm or more as shown in the figure at right If the suspension bolts is too long it will contact the ceiling panel and the unit cannot be installed 25 583 575 44 170 123 31 146 179 283 288 31 23 260 ceiling opening dimension suspension bolt pitch A 600 ceiling opening dimension 530 600 530 suspension bolt pitch 301 316 320 VIEW A 212 148 112 583 575 200 a a 700 625 CZ KPY3A CZ KPY...

Страница 226: ...E5 U 60PEY1E5 U 71PEY1E5 Air intake Air intake Drain port Drain port Air discharge Anchor bolt hole Anchor bolt M8 Refrigerant tubing joint gas tube Flare connection ø12 7 mm 50 ø15 88 mm 60 71 Refrigerant tubing joint liquid tube Flare connection ø6 35 mm 50 ø9 52 mm 60 71 Unit mm SM830231 02 Single 欧州 indb 216 SM830231 02 Single 欧州 indb 216 2014 09 19 13 21 32 2014 09 19 13 21 32 ...

Страница 227: ... Refrigerant piping gas pipe flared connection ø15 88 Refrigerant piping liquid pipe flared connection ø9 52 Mounting hole anchor bolt M10 Electrical wiring port ø35 View B Refrigerant piping end connection Anchor hole Air discharge Air intake Bottom 380 5 996 170 620 150 340 340 120 81 48 39 8 7 6 5 2 3 4 4 6 7 8 5 18 A 39 48 81 120 26 35 86 84 5 109 5 35 60 60 41 41 13 940 173 47 35 51 16 120 90...

Страница 228: ...0 or more 200 or more 300 57 5 61 76 31 5 522 490 unit mm Electrical wiring port ø27 Electrical wiring port ø22 Electrical wiring port ø13 Refrigerant piping hole Refrigerant piping gas pipe flared connection ø15 88 Refrigerant piping liquid pipe flared connection ø9 52 Mounting hole anchor bolt M10 Electrical wiring port ø35 1 3 6 5 4 7 2 8 Enlarged view A View B Refrigerant piping end connection...

Страница 229: ...er Distributor Flare connection Flare connection M High pressure switch HP ø12 7 ø6 35 EC P M Outdoor Unit U 50PE1E5 Indoor Unit Compressor High pressure switch Muffler Heat exchanger Accumulator Gas line service valve Muffler 4 way valve Electronic ref control valve Liquid line service valve Cooling cycle Heating cycle Strainer Heat exchanger Strainer Distributor Flare connection Flare connection...

Страница 230: ...on Temp Thermistor 4 way valve High pressure switch Thermistor Accumulator Muffler Strainer Strainer Heat exchanger Strainer Distributor Distributor ø15 88 ø9 52 Compressor Heat EC P Defrost Temp Expantion valve Cooling cycle Heating cycle exchanger Heat exchanger Temp Thermistor Temp Thermistor Outdoor air Discharge Temp Thermistor Suction Temp Thermistor 4 way valve High pressure switch Thermist...

Страница 231: ...mp Thermistor Heat exchanger Temp Thermistor Defrost Temp Thermistor Suction Temp Thermistor Heat exchanger Distributor Indoor Unit t i n U r o o d t u O Strainer Compressor Expansion valve Heat exchanger Temp Thermistor Strainer Strainer EC P Heat exchanger Defrost Temp Thermistor Suction Temp Thermistor 4 way valve Accumulator Outdoor air Temp Thermistor High pressure switch Distributor Heating ...

Страница 232: ...B WB 16 C DB WB 46 C DB 15 C DB 24 C DB 18 C WB 20 C DB 20 C WB Type PEY1 Temperature Indoor air intake temp Outdoor air intake temp Cooling Maximum Minimum Heating Maximum Minimum 32 C DB 25 C WB 18 C DB 14 C WB 30 C DB WB 16 C DB WB 43 C DB 10 C DB 24 C DB 18 C WB 15 C DB 15 C WB SM830231 02 Single 欧州 indb 222 SM830231 02 Single 欧州 indb 222 2014 09 19 13 21 38 2014 09 19 13 21 38 ...

Страница 233: ...ting Input coefficient PE1 Indoor air intake temp C WB 1 5 Capacity Correction Graph According to Temperature Condition 40 50 60 70 80 90 100 110 120 130 140 150 160 60 70 80 90 100 110 120 130 140 30 20 10 0 10 20 30 Indoor air intake temp C DB Indoor air intake temp C DB 22 CWB 19 CWB 16 CWB 22 CWB 19 CWB 16 CWB 16 CDB 20 CDB 24 CDB 16 CDB 20 CDB 24 CDB Indoor air intake temp C WB 0 20 40 60 80 ...

Страница 234: ...pproximately 85 Outdoor intake air temperature C WB 20 15 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 Correction coefficient 1 0 1 0 0 97 0 96 0 96 0 95 0 94 0 91 0 89 0 88 0 87 0 87 0 87 0 88 0 89 0 91 0 92 0 95 1 0 To calculate the heating capacity with consideration for frosting defrosting operation multiply the heating capacity found from the capacity graph by the correction coefficient from the table ...

Страница 235: ...6 0 96 0 95 0 94 0 91 0 89 0 88 0 87 0 87 0 87 0 88 0 89 0 91 0 92 0 95 1 0 To calculate the heating capacity with consideration for frosting defrosting operation multiply the heating capacity found from the capacity graph by the correction coefficient from the table above U 71PE1E5A For 50 Hz U 71PE1E8A For 50 Hz U 71PE1E5A For 50 Hz 1 5 Capacity Correction Graph According to Temperature Conditio...

Страница 236: ...ting defrosting To calculate the heating capacity with consideration for frosting defrosting operation multiply the heating capacity found from the capacity graph by the correction coefficient from the table above RH approximately 85 20 10 0 10 20 30 40 50 Indoor air intake temp C WB Indoor air intake temp C WB 22 CWB 19 CWB 16 CWB 0 0 2 0 4 0 6 0 8 0 10 0 12 0 14 0 16 0 PE1 16 CDB 20 CDB 24 CDB I...

Страница 237: ...r intake temp C DB 16 CDB 20 CDB 24 CDB 16 CDB 20 CDB 24 CDB Indoor air intake temp C DB 0 0 2 0 4 0 6 0 8 0 10 0 12 0 14 0 16 0 18 0 20 0 Cooling Heating Outdoor unit heating capacity correction cofficient during of frosting defrosting To calculate the heating capacity with consideration for frosting defrosting operation multiply the heating capacity found from the capacity graph by the correctio...

Страница 238: ... 100 120 140 180 160 140 180 160 20 0 40 60 80 100 120 140 140 22 CWB 19 CWB 16 CWB 22 CWB 19 CWB 16 CWB 16 CDB 20 CDB 24 CDB 16 CDB 20 CDB 24 CDB Indoor air intake temp C WB Indoor air intake temp C DB Outdoor unit heating capacity correction cofficient during of frosting defrosting To calculate the heating capacity with consideration for frosting defrosting operation multiply the heating capacit...

Страница 239: ...fficient 50 60 70 80 90 100 110 120 130 22 CWB 19 CWB 16 CWB Indoor air intake temp C WB 50 60 70 80 90 100 110 120 20 10 0 10 20 30 40 50 22 CWB 19 CWB 16 CWB Indoor air intake temp C WB 40 50 60 70 80 90 100 110 120 130 140 150 160 16 CDB 20 CDB 24 CDB Indoor air intake temp C DB 60 70 80 90 100 110 120 130 140 20 15 10 5 0 5 10 15 20 25 30 16 CDB 20 CDB 24 CDB Indoor air intake temp C DB 0 20 4...

Страница 240: ...ature Condition 50 60 70 80 90 100 110 120 130 22 CWB 19 CWB 16 CWB 50 60 70 80 90 100 110 120 20 10 0 10 20 30 40 50 22 CWB 19 CWB 16 CWB 40 50 60 70 80 90 100 110 120 130 140 150 160 16 CDB 20 CDB 24 CDB Indoor air intake temp C DB 60 70 80 90 100 110 120 130 140 20 15 10 5 0 5 10 15 20 25 30 16 CDB 20 CDB 24 CDB Indoor air intake temp C WB Indoor air intake temp C WB Indoor air intake temp C DB...

Страница 241: ...oximately 85 Correction coefficient Outdoor intake air temperature C WB 0 86 0 86 0 86 0 86 0 86 0 86 0 86 0 86 0 86 0 86 0 86 0 84 0 84 0 82 0 8 0 8 0 82 0 84 0 86 20 15 10 9 0 10 8 9 8 7 6 5 4 3 2 1 1 2 3 4 5 6 7 0 88 0 88 1 1 Cooling capacity ratio maximum capacity 20 0 40 60 80 100 140 120 20 0 40 60 80 100 120 140 20 10 0 10 20 30 40 50 22 CWB 19 CWB 16 CWB 22 CWB 19 CWB 16 CWB 20 0 40 60 80 ...

Страница 242: ...osting defrosting operation multiply the heating capacity found from the capacity graph by the correction coefficient from the table above RH approximately 85 Correction coefficient Outdoor intake air temperature C WB 0 86 0 86 0 86 0 86 0 86 0 86 0 86 0 86 0 86 0 86 0 86 0 84 0 84 0 82 0 8 0 8 0 82 0 84 0 86 20 15 10 9 0 10 8 9 8 7 6 5 4 3 2 1 1 2 3 4 5 6 7 0 88 0 88 1 1 20 0 40 60 80 100 140 120...

Страница 243: ...ng operation multiply the heating capacity found from the capacity graph by the correction coefficient from the table above RH approximately 85 Correction coefficient Outdoor intake air temperature C WB 0 86 0 86 0 86 0 86 0 86 0 86 0 86 0 86 0 86 0 86 0 86 0 84 0 84 0 82 0 8 0 8 0 82 0 84 0 86 0 88 0 88 1 1 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 15 20 Indoor air intake temp C DB PEY1 Outdoor...

Страница 244: ...C 40 NC 60 NC 50 NC 30 NC 20 10 20 30 40 50 60 63 125 250 500 1000 2000 4000 8000 NC 40 NC 50 NC 30 NC 20 NC 60 10 20 30 40 50 60 63 125 250 500 1000 2000 4000 8000 NC 40 NC 60 NC 50 NC 30 NC 20 MODEL SOUND LEVEL CONDITION SOURCE S 50PU1E5A High Low 32 dB A 27 dB A Under the unit 1 5m 220 230 240V 1 phase 50Hz MODEL SOUND LEVEL CONDITION SOURCE S 45PU1E5A High Low 31 dB A 27 dB A Under the unit 1 ...

Страница 245: ...NC 50 NC 30 NC 20 MODEL SOUND LEVEL CONDITION SOURCE S 125PU1E5A High Low 45 dB A 33 dB A Under the unit 1 5m 220 230 240V 1 phase 50Hz MODEL SOUND LEVEL CONDITION SOURCE S 140PU1E5A High Low 46 dB A 34 dB A Under the unit 1 5m 220 230 240V 1 phase 50Hz MODEL SOUND LEVEL CONDITION SOURCE S 71PU1E5A High Low 37 dB A 28 dB A Under the unit 1 5m 220 230 240V 1 phase 50Hz Octave Band Level dB 0dB 0 00...

Страница 246: ... minimum audible limit for continuous noise Frequency at center of sound pressure band Hz Frequency at center of sound pressure band Hz Frequency at center of sound pressure band Hz Frequency at center of sound pressure band Hz 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Overall Overall Overall Overall ...

Страница 247: ...m audible limit for continuous noise Frequency at center of sound pressure band Hz Frequency at center of sound pressure band Hz Frequency at center of sound pressure band Hz 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Overall Overall Overall Sound pressure level dB 0dB 0 0002 bar 10 20 30 40 50 60 70 80 90 70 80 90 NC 60 NC 50 NC 40 NC ...

Страница 248: ...r continuous noise 250 125 2000 1000 63 500 Overall Frequency at center of sound pressure band Hz STRONG Sound pressure level dB 0dB 0 0002 bar MODEL S 60PK1E5A S 71PK1E5A SOUND LEVEL 47 dB A Low High 40 dB A 44 dB A CONDITION 1m in front of air discharge and then 1m below 60 50 40 30 10 20 Approximate minimum audible limit for continuous noise Overall Frequency at center of sound pressure band Hz...

Страница 249: ...PF1E5A High Low 34 dB A 26 dB A Under the unit 1 5m 220 230 240V 1 phase 50Hz MODEL SOUND LEVEL CONDITION SOURCE S 45PF1E5A High Low 33 dB A 25 dB A Under the unit 1 5m 220 230 240V 1 phase 50Hz MODEL SOUND LEVEL CONDITION SOURCE S 60PF1E5A High Low 35 dB A 26 dB A Under the unit 1 5m 220 230 240V 1 phase 50Hz Low Silhouette Ducted Type Approximate minimum audible limit for continuous noise Approx...

Страница 250: ...50 NC 40 NC 30 NC 20 63 125 250 500 1000 2000 4000 8000 NC 40 NC 50 NC 30 NC 20 10 20 30 40 50 63 125 250 500 1000 2000 4000 8000 NC 40 NC 50 NC 30 NC 20 MODEL SOUND LEVEL CONDITION SOURCE S 140PF1E5A High Low 40 dB A 33 dB A Under the unit 1 5m 220 230 240V 1 phase 50Hz MODEL SOUND LEVEL CONDITION SOURCE S 125PF1E5A High Low 39 dB A 32 dB A Under the unit 1 5m 220 230 240V 1 phase 50Hz Low Silhou...

Страница 251: ... 2000 4000 8000 Sound pressure level dB 0dB 0 0002 μbar 10 20 30 40 50 60 Frequency at center of sound pressure band Hz 63 125 250 500 1000 2000 4000 8000 NC 40 NC 50 NC 30 NC 20 NC 60 Approximate minimum audible limit for continuous noise Sound pressure level dB 0dB 0 0002 μbar Frequency at center of sound pressure band Hz 10 20 30 40 50 60 63 125 250 500 1000 2000 4000 8000 NC 40 NC 50 NC 30 NC ...

Страница 252: ...5A High Low 40 dB A 33 dB A Under the unit 1 5m 220 230 240V 1 phase 50Hz MODEL SOUND LEVEL CONDITION SOURCE S 45PY2E5A High Low 38 dB A 28 dB A Under the unit 1 5m 220 230 240V 1 phase 50Hz 4 Way Cassette 60 60 Type 10 20 30 40 50 60 Octave Band Level dB 0dB 0 0002 μbar 10 20 30 40 50 60 Octave Band Level dB 0dB 0 0002 μbar 10 20 30 40 50 60 NC 60 NC 50 NC 40 NC 30 NC 20 NC 60 NC 50 NC 40 NC 30 N...

Страница 253: ... Hz Cooling Overall Approximate minimum audible limit for continuous noise 4000 8000 2000 1000 500 63 125 250 10 20 30 40 50 60 70 NC 70 NC 60 NC 50 NC 40 NC 30 NC 20 MODEL SOUND LEVEL CONDITION SOURCE U 50PE1E5 Heating 50 dB A 1 m in front at height of 1 5 m 220 230 240V 1 phase 50Hz Octave Band Level dB 0dB 0 0002 μbar Frequency at center of sound pressure band Hz Heating Overall Approximate min...

Страница 254: ...0 NC 30 NC 20 10 20 30 40 50 60 NC 40 NC 60 NC 50 NC 30 NC 20 Approximate minimum audible limit for continuous noise Approximate minimum audible limit for continuous noise MODEL SOUND LEVEL CONDITION SOURCE U 71PE1E5A U 71PE1E8A Heating 50 dB A 1 m in front at height of 1 5 m 1 phase model Heating MODEL SOUND LEVEL CONDITION SOURCE U 71PE1E5A U 71PE1E8A Cooling 48 dB A 1 m in front at height of 1 ...

Страница 255: ... 53 dB A 1 m in front at height of 1 5 m MODEL SOUND LEVEL CONDITION U 125PE1E5A U 125PE1E8A Cooling 53 dB A 1 m in front at height of 1 5 m 10 20 30 40 50 60 NC 40 NC 50 NC 30 NC 20 NC 60 10 20 30 40 50 60 NC 40 NC 60 NC 50 NC 30 NC 20 Approximate minimum audible limit for continuous noise Approximate minimum audible limit for continuous noise Approximate minimum audible limit for continuous nois...

Страница 256: ...C 40 NC 60 NC 50 NC 30 NC 20 Approximate minimum audible limit for continuous noise Approximate minimum audible limit for continuous noise Frequency at center of sound pressure band Hz Frequency at center of sound pressure band Hz 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Heating Cooling SOURCE 1 phase model SOURCE 220 230 240V 1 phase 50Hz 1 phase model 380 400 415V 3 ...

Страница 257: ...0 20 30 40 50 60 70 Approximate minimum audible limit for continuous noise MODEL SOUND LEVEL CONDITION SOURCE U 60PEY1E5 Heating 50 dB A 1 m in front at height of 1 5 m 220 230 240V 1 phase 50Hz 4000 8000 2000 1000 500 63 125 250 Frequency at center of sound pressure band Hz Overall Octave Band Level dB 0dB 0 0002 μbar Heating NC 70 NC 60 NC 50 NC 40 NC 30 NC 20 10 20 30 40 50 60 70 Approximate mi...

Страница 258: ...re band Hz Frequency at center of sound pressure band Hz 8000 4000 2000 1000 500 250 125 63 8000 4000 2000 1000 500 250 125 63 MODEL SOUND LEVEL CONDITION U 100PEY1E5 U 100PEY1E8 Heating 54 dB A 1 m in front at height of 1 5 m MODEL SOUND LEVEL CONDITION U 100PEY1E5 U 100PEY1E8 Cooling 54 dB A 1 m in front at height of 1 5 m Octave Band Level dB 0dB 0 0002 μbar Octave Band Level dB 0dB 0 0002 μbar...

Страница 259: ...Y1E8 Heating 53 dB A 1 m in front at height of 1 5 m SOURCE 380 400 415V 3 phase 50Hz Octave Band Level dB 0dB 0 0002 μbar 10 20 30 40 50 60 NC 60 NC 50 NC 40 NC 30 NC 20 Approximate minimum audible limit for continuous noise 8000 4000 2000 1000 500 250 125 63 8000 4000 2000 1000 500 250 125 63 Cooling MODEL SOUND LEVEL CONDITION U 140PEY1E8 Cooling 54 dB A 1 m in front at height of 1 5 m SOURCE 3...

Страница 260: ...o elevate air volume S 45PN1E5A S 50PN1E5A P Q CURVE 0 10 20 30 40 50 60 70 80 20 10 Air volume m3 min Air volume m3 min Air volume m3 min External static pressure Pa External static pressure Pa External static pressure Pa S 36PN1E5A P Q CURVE 0 10 20 30 40 50 60 70 80 18 8 Air volume m3 min External static pressure Pa 0 50 100 16 26 ձ 3 ձ 2 ձ ճ յ 䐭 䐬 䐫 䐪 䐩 䐦 䐤 S 60PN1E5A S 71PN1E5A Limit line 0 5...

Страница 261: ... s 1 0m s 0 5m s 0 3m s 33 27 24 30 Horizontal air flow distance m Cooling Distribution of wind velocity Cooling Distribution of temperature 0 1 2 3 0 1 2 3 Horizontal air flow distance m 0 1 2 3 0 1 2 3 Strong wind Discharge angle approx 30 Room temperature approx 27 1 5m s 1 0m s 0 5m s 0 3m s 20 24 26 22 Strong wind Discharge angle approx 30 Room temperature approx 27 Vertical air flow distance...

Страница 262: ...ce m Heating Distribution of temperature Cooling Distribution of wind velocity Cooling Distribution of temperature Vertical air flow distance m Vertical air flow distance m Vertical air flow distance m Strong wind Discharge angle approx 65 Room temperature approx 20 Strong wind Discharge angle approx 30 Room temperature approx 27 Strong wind Discharge angle approx 30 Room temperature approx 27 Hor...

Страница 263: ...y Cassette Type U1 S 100PU1E5A 125PU1E5A 140PU1E5A Horizontal air flow distance m Horizontal air flow distance m Horizontal air flow distance m Horizontal air flow distance m Strong wind Discharge angle approx 65 Room temperature approx 20 C 5 5 3 2 3 2 1 1 0 4 4 33 C 27 C 24 C 30 C Strong wind Discharge angle approx 65 Room temperature approx 20 C Strong wind Discharge angle approx 30 Room temper...

Страница 264: ...rizontal air flow distance m Horizontal air flow distance m 1 5m s 1 0m s 0 5m s 0 3m s 1 5m s 1 0m s 0 5m s 0 3m s S 36PT2E5A 45PT2E5A 50PT2E5A Heating Distribution of wind velocity Heating Distribution of temperature Cooling Distribution of wind velocity Cooling Distribution of temperature Vertical air flow distance m Vertical air flow distance m Vertical air flow distance m Vertical air flow di...

Страница 265: ... Distribution of wind velocity Heating Distribution of temperature Cooling Distribution of wind velocity Cooling Distribution of temperature Horizontal air flow distance m 0 1 2 3 4 5 6 7 8 9 10 26 C 24 C 22 C 20 C 0 1 2 3 4 5 6 7 8 9 10 Horizontal air flow distance m Horizontal air flow distance m 0 1 2 3 4 5 6 7 8 9 10 Strong wind Discharge angle approx 54 Room temperature approx 20 C 4 0 1 2 3 ...

Страница 266: ...izontal air flow distance m 0 1 2 3 4 5 6 7 8 9 10 26 C 24 C 22 C 20 C Strong wind Discharge angle approx 7 Room temperature approx 27 C 0 1 2 3 4 5 6 7 8 9 10 Horizontal air flow distance m Strong wind Discharge angle approx 7 Room temperature approx 27 C Horizontal air flow distance m 0 1 2 3 4 5 6 7 8 9 10 Strong wind Discharge angle approx 54 Room temperature approx 20 C 24 C 27 C 30 C 33 C 0 ...

Страница 267: ...tance m 0 1 2 3 0 1 2 3 0 1 2 3 0 1 2 3 0 5 4 3 2 1 Strong Outlet Angle 30 Strong Outlet Angle 30 Strong Outlet Angle 60 Strong Outlet Angle 60 Cooling Air Flow Heating Air Flow Cooling Temperature Heating Temperature 1 5m s 1 2m s 0 9m s 0 3m s 0 6m s 0 3m s 0 6m s 20 22 24 26 26 1 5m s 1 2m s 0 9m s 0 3m s 0 6m s 0 3m s 33 30 27 24 0 5 4 3 2 1 0 5 4 3 2 1 0 5 4 3 2 1 SM830231 02 Single 欧州 indb 2...

Страница 268: ...tal air flow distance m S 50PK1E5A Strong wind Discharge angle app 60 Rm temp app 20 C Strong wind Discharge angle app 60 Rm temp app 20 C Strong wind Discharge angle app 30 Rm temp app 27 C Strong wind Discharge angle app 30 Rm temp app 27 C 1 0 2 3 1 0 2 3 1 5m s 1 2m s 0 9m s 0 3m s 0 6m s 0 3m s 33 C 27 C 24 C 30 C 1 0 2 3 1 0 2 3 1 5m s 1 2m s 0 9m s 0 3m s 0 6m s 0 6m s 0 3m s 20 C 24 C 26 C...

Страница 269: ...3 1 0 2 3 1 5m s 1 2m s 0 9m s 0 3m s 0 6m s 0 3m s 33 C 27 C 24 C 30 C 1 0 2 3 1 0 2 3 1 5m s 1 2m s 0 9m s 0 9m s 0 3m s 0 6m s 0 6m s 0 3m s 20 C 24 C C 26 C 26 C 22 C Heating Distribution of wind velocity Heating Distribution of temperature Vertical air flow distance m Vertical air flow distance m Vertical air flow distance m Vertical air flow distance m Strong wind Discharge angle app 60 Rm t...

Страница 270: ...pprox 60 Room temperature approx 20 C Strong wind Discharge angle approx 30 Room temperature approx 27 C Strong wind Discharge angle approx 30 Room temperature approx 27 C 1 5m s 1 0m s 0 5m s 0 3m s 33 27 24 30 Horizontal air flow distance m Cooling Distribution of wind velocity Cooling Distribution of temperature 0 1 2 0 1 2 Horizontal air flow distance m 0 5 5 2 1 3 2 4 3 4 0 1 5 5 2 1 3 2 4 3 ...

Страница 271: ...f temperature 0 1 2 3 0 1 2 3 Horizontal air flow distance m 0 1 2 3 0 1 2 3 1 5m s 1 0m s 0 5m s 0 3m s 20 24 26 22 S 45PY2E5A 50PY2E5A 4 Way Cassette 60 x 60 Type Y2 Strong wind Discharge angle approx 60 Room temperature approx 20 C Strong wind Discharge angle approx 60 Room temperature approx 20 C Strong wind Discharge angle approx 30 Room temperature approx 27 C Strong wind Discharge angle app...

Страница 272: ... is fed in 3 When used in combination with humidifiers External air must always be processed when the external air temperature reaches freezing point to prevent the risk of the humidifier freezing 4 Arranging Ducts and Filters in the Field External air intake ducting must be arranged in the field External air filters must also be installed without fail in order to prevent the intake of dust and gr...

Страница 273: ... as shown in the diagram for operation noise characteristics and the operation noise of the unit as stipulated in the catalogue 2 The amount of external air that is possible to feed when external air intake chamber is in use CZ FCU2 CZ ATU2 The operation noise for models that use small units is lower so use values that are within the range shown in the above table Using values that exceed these wi...

Страница 274: ...els that use small units is lower so use values that are within the range shown in the above table Using values that exceed these will result in noise when only external air is fed being louder than the noise emitted from the unit Permissible air intake volume m3 h The operation noise conforms to JIS standards and constitute measurements taken in an anechoic chamber 1 5m directly below the indoor ...

Страница 275: ...sible to feed when it is fed directly into the unit The operation noise for models that use small units is lower so use values that are within the range shown in the above table Using values that exceed these will result in noise when only external air is fed being louder than the noise emitted from the unit Permissible air intake volume m3 h 170 170 160 The operation noise conforms to JIS standar...

Страница 276: ...sible to feed when it is fed directly into the unit The operation noise for models that use small units is lower so use values that are within the range shown in the above table Using values that exceed these will result in noise when only external air is fed being louder than the noise emitted from the unit Permissible air intake volume m3 h Type 126 126 150 180 180 36 45 50 60 71 240 240 240 100...

Страница 277: ... on wire diameters differ from locality to locality For field wiring rules please refer to your LOCAL ELECTRICAL CODES before beginning You must ensure that installation complies with all relevant rules and regulations To prevent malfunction of the air conditioner caused by electrical noise care must be taken when wiring as follows If the power supply cord of this appliance is damaged it must be r...

Страница 278: ...e U1 U1 U2 N L R1 R2 U1 U2 N L 1 R R2 L N U1 U2 5P terminal board Power supply Type K1 Inter unit control wiring L N U1 U2 R1 R2 6P terminal board Type T2 F1 Power supply Remote control wiring Inter unit control wiring Power supply Remote control wiring Inter unit control wiring Type N1 6P terminal board L2 L1 U2 U1 L3 N A L1 L2 L3 N U2 R2 U1 R1 R2 R1 L N U2 U1 2 1 D C B L N L N 2 1 B E C L N Powe...

Страница 279: ...ved polychloroprene sheathed 5 or 3 1 5 mm2 flexible cord Type designation 60245 IEC 57 H05RN F GP85PCP etc or heavier cord Use the standard power supply cables for Europe such as H05RN F or H07RN F which conform to CENELEC HAR rating specifications or use the cables based on IEC standard 60245 IEC57 60245 IEC66 Connect wiring as shown in Section Wiring System Loose wiring may cause the terminal t...

Страница 280: ...e ends Fig 1 1 Using a Phillips head screwdriver remove the terminal screw s on the terminal plate Using a ring connector fastener or pliers securely clamp each stripped wire end with a ring pressure terminal Place the ring pressure terminal and replace and tighten the removed terminal screw using a screwdriver Fig 1 2 Examples of shield wires 1 2 3 4 Remove cable coat not to scratch braided shiel...

Страница 281: ...tty to seal off the opening to prevent dust 2 Wiring connection ports How to carry out wiring Insert the power wiring into the indoor unit through the rubber at the side of the electrical component box For wiring connection to the outdoor unit and remote control wiring open the elongated hole of the piping cover and pass the wires through the hole NOTE Type T2 Protective ground screw Functional gr...

Страница 282: ...Schedule Timer Protective ground screw External Solenoid Valve Kit for 3WAY Use this screw when connecting the shield for the inter unit control wiring to ground Inter unit control wiring Remote control wiring SM830231 02 Single 欧州 indb 272 SM830231 02 Single 欧州 indb 272 2014 09 19 13 21 44 2014 09 19 13 21 44 ...

Страница 283: ...ation is to be used when the outdoor air temperature is 5 C or below install a duct on the outdoor unit Exhaust fan Heat source Outdoor unit Hot air Installation space for outdoor unit single phase Install the outdoor unit with a sufficient space around the outdoor unit for operation and maintenance 1 Obstructions on the left side right side and rear side Front side and above the unit are opened A...

Страница 284: ...g a sidewalk and discharged hot air annoys passers by Air discharge Installing the Unit in Heavy Snow Areas In locations with strong wind snow proof ducting should likewise be fitted and direct exposure to the wind should be avoided as much as possible Countermeasures against snow and wind In regions with snow and strong wind the following problems may occur when the outdoor unit is not provided w...

Страница 285: ...m and the unit must be secured with anchor bolts In case of installation on a roof subject to strong wind countermeasures must be taken to prevent the unit from being blown over Dimensions of Snow Wind proof Ducting and Refrigerant Tubing Space for Installation 250 249 Min 100 Min 100 Unit mm Duct Air Intake Platform foundation Higher than the maximum snow depth 50 cm About 1 2 of the unit height ...

Страница 286: ...stant indoor unit L L 1 L 2 40 50 40 Maximum distribution tubing length Maximum length following the first branch point No 1 distribution 1 2 15 Maximum branch tubing length Difference between the maximum length and minimum length in tubing following the first branch point 1 2 1 2 10 Maximum difference between lengths of No 1 distribution tubing double twin Maximum difference between lengths of No...

Страница 287: ...erant for main tubing g Additional refrigerant for distribution tubing g Outdoor unit charge less refrigerant amount g 40 a 20 b 400 1 Type 60 71 1 Type 50 of outdoor unit is 600 g 1 In case of twin connection Type 71 of outdoor unit is 400 g Use with the current refrigerant charge a Actual length m of main tubing ø9 52 Refrigerant charge per 1 m of actual length 40 g m Type 60 71 b Total length o...

Страница 288: ...the leak detector Total refrigerant charged amount kg Min indoor volume where indoor unit is installed m3 Limit density 0 3 kg m3 The limit density of refrigerant which is used in this unit is 0 3 kg m3 ISO 5149 The shipped outdoor unit comes charged with the amount of refrigerant fixed for each type so add it to the amount that is charged at the field Refer to the unit s nameplate for the amount ...

Страница 289: ...18 Drain port 2 ø19 Drain port Drainage Work Follow the procedure below to ensure adequate draining for the outdoor unit For the drain port dimensions Ensure a base height of 15 cm or more at the feet on both sides of the unit When using a drain pipe install the drain socket optional part STK DS13U onto the drain port Seal the other drain port with the rubber cap supplied with the drain socket Rou...

Страница 290: ... Remove the flare nut from the unit and be sure to mount it on the copper tube 4 Make a flare at the end of the copper tube with a flare tool 2 Remove burrs at each end of the copper tubing with a tube reamer or file This process is important and should be done carefully to make a good flare Be sure to keep any contaminants moisture dirt metal filings etc from entering the tubing Flaring Procedure...

Страница 291: ...ant system valves to become damaged Therefore allow the tubing to cool when brazing Use a reducing valve for the nitrogen cylinder Do not use agents intended to prevent the formation of oxide film These agents adversely affect the refrigerant and refrigerant oil and may cause damage or malfunctions Adjust the shape of the liquid tube using a tube bender at the installation site and connect it to t...

Страница 292: ...emoved refrigerant will leak from the valve Therefore do not leave the valve stem cap removed Use a torque wrench to securely tighten the valve stem cap Tightening torque Because the pressure is approximately 1 6 times higher than conventional refrigerant pressure the use of ordinary flare nuts Type 1 or thin walled tubes may result in tube rupture injury or asphyxiation caused by refrigerant leak...

Страница 293: ...ulation characteristics be easy to use be age resistant and must not easily absorb moisture For gas tubing the insulation material must be heat resistant to 120 C or above For other tubing it must be heat resistant to 80 C or above Two tubes arranged together Inter unit control wiring Gas tube Liquid tube Armoring tape Insulation CAUTION After a tube has been insulated never try to bend it into a ...

Страница 294: ...ap the armoring tape from the bottom of the outdoor unit to the top of the tubing where it enters the wall As you wrap the tubing overlap half of each previous tape turn 3 Clamp the tubing bundle to the wall using 1 clamp approx each meter Inter unit control wiring Insulation Gas tube Liquid tube Armoring tape NOTE Do not wind the armoring tape too tightly since this will decrease the heat insulat...

Страница 295: ...properly connected and all wiring for the test run has been completed Remove the valve caps from both the gas and liquid service valves on the outdoor unit Note that both liquid and gas tube service valves on the outdoor unit are kept closed at this stage The refrigerant charge at the time of shipment is only guaranteed sufficient for a tubing length of up to 30 m The tubing may exceed this length...

Страница 296: ... of the tubing both indoor and outdoor and both gas and liquid service valves Bubbles indicate a leak Wipe off the soap with a clean cloth after a leak test 5 After the system is found to be free of leaks relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder When the system pressure is reduced to normal disconnect the hose from the cylinder CAUTION Use a man...

Страница 297: ...list the refrigerant tubing length and amount of additional refrigerant charge on the product label inside the panel CAUTION To avoid gas from leaking when removing the charge hose make sure the stem of the gas tube is turned all the way out BACK SEAT position Charging additional refrigerant calculated from the liquid tube length as shown in Amount of additional refrigerant charge using the liquid...

Страница 298: ...hen wiring as follows 2 Provide a power outlet to be used exclusively for each unit and a circuit breaker for overcurrent protection should be provided in the exclusive line General Precautions on Wiring Recommended Wire Length and Wire Diameter for Power Supply System NOTE 1 With ring type wire terminal 2 When D and E are used together with maximum length of 500 m for group control and if the rem...

Страница 299: ...rd so the terminal boards in your equipment may differ from the diagram 3 Refrigerant Circuit R C address should be set before turning the power on 4 Regarding R C address setting refer to the installation instructions supplied with the remote controller unit Optional Auto address setting can be executed by remote controller automatically Refer to the Installation Instructions supplied with the re...

Страница 300: ... CENELEC HAR rating specifications or use the cables based on IEC standard 60245 IEC57 60245 IEC66 Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 5 or 3 1 5 mm2 flexible cord Type designation 60245 IEC 57 H05RN F GP85PCP etc or heavier cord 3 Do not install the inter unit control wiring in a way that forms a loop If branching the inter unit control...

Страница 301: ...d terminal screw through the ring pressure terminal and then replace and tighten the terminal screw using a screwdriver Air Purging with a Vacuum Pump for Test Run Preparation Assembling parts for outdoor unit cover Stranded wire Strip 10 mm Ring pressure terminal Ring pressure terminal Special washer Screw Terminal board Ring pressure terminal Wire Wire Screw and Special washer Terminal board Ear...

Страница 302: ... heater around the feet of the compressor should be hot to the touch 6 Both the gas and liquid tube service valves are open If not open them now 7 Request that the customer be present for the test run Explain the contents of the Installation Instructions and then have the customer actually operate the system 8 Be sure to give the Installation Instructions and warranty certificate to the customer 9...

Страница 303: ...unit is connected to 1 outdoor unit and remote controller Is group control with multiple outdoor units used Turn ON the indoor and outdoor power Indicate mark the combination number Automatic address setting Set the remote controller to test run See section Test Run Using the Remote Controller See section Indicating marking the indoor and outdoor unit combination number Can operation be started Re...

Страница 304: ...e customer be present when the test run is performed At this time explain the Operating Instructions and have the customer perform the actual steps Be sure to pass the manuals and warranty certificate to the customer Check that the 220 240 V AC power is not connected to the inter unit control wiring connector terminal Temperature control is not possible when test run mode is engaged This mode plac...

Страница 305: ...ndoor and outdoor units are appropriate E16 displayed Indoor unit capacity is too high E20 displayed No serial signal is being received at all from the indoor units Check that the indoor unit power is ON and that the inter unit control wiring is connected correctly P05 displayed Operation lamp and Standby lamp are blinking alternately Reversed phase in the outdoor unit single phase or open phase i...

Страница 306: ...mote power switch Refer to section Setting the outdoor unit system addresses Set using the system address rotary switch on the outdoor unit control PCB Be careful to avoid miswiring when connecting the wires Miswiring will damage the units 1 2 1 2 1 2 U2 U1 L N N U1 U2 1 2 L L N WHT BLK Inter unit control wiring Outdoor unit Ground Ground Ground Leakage breaker Leakage breaker Indoor unit Indoor u...

Страница 307: ... of the indoor unit power wires Use a pull box to divide the wiring Be sure to use the indoor unit temperature sensor body sensor when using this control Status at shipment ON 1 2 Outdoor unit control PCB DIP switch System address System address rotary switch Set to 0 at time of shipment System address rotary switch 10s 20s ON OFF LED1 LED2 PUMP DOWN CN042 EEPROM IC006 AUTO ADD CN041 System addres...

Страница 308: ...ress the Each time the button is pressed the address changes as follows 1 1 1 2 2 1 2 2 The indoor unit fan operates only at the selected indoor unit Confirm that correct fan is operating and indicate the address on the indoor unit button and select the indoor address button and button for 4 seconds or longer simple settings mode Press the remote controller timer time To select each refrigerant sy...

Страница 309: ...low the steps below U1 U2 1 2 1 2 1 2 1 2 Optional Indoor unit Ground Ground Outdoor unit Optional Remote control wiring Terminal board for remote control wiring U1 U2 U1 U2 1 2 1 2 1 2 1 2 1 2 Remote controller main Optional Indoor unit 1 Indoor unit 2 Ground Ground Ground Outdoor unit Optional Remote control communication wiring Terminal board for remote control wiring Inter unit control wiring ...

Страница 310: ...nit Are multiple outdoor units used Turn ON the indoor and outdoor power Set the indoor unit control switch to TEST See section Test Run for Type K1 See section Test Run for Type K1 See section Table of Self Diagnostic Functions and Corrections Type K1 Can operation be started Slide the indoor unit control switch back to ON Turn ON the indoor and outdoor power Automatic Address Setting Automatic A...

Страница 311: ...oller cover and press the SENSOR button once body sensor appears on the LCD display of the wireless remote controller then the indoor unit body NOTE Switching the temperature sensor Face the remote controller toward the receiver on the main unit The signal can be received up to a distance of approximately 8 m Use this distance as a guide This distance may vary somewhat depending on the battery cap...

Страница 312: ...hange the switch once to ON or OFF then switch it back to the TEST position NOTE Using the control unit Indicator lamps OPERATION STANDBY TIMER Indoor control unit switch ON OFF TEST If 220 240 V AC is accidentally applied the indoor or outdoor unit control PCB fuse 0 5 A for both indoor and outdoor units will blow in order to protect the PCB Correct the wiring connections then disconnect the 2P c...

Страница 313: ...ring Perform automatic address setting again E15 displayed E16 displayed L02 displayed Both the Operation lamp and Standby lamp are blinking together Indoor unit capacity is too low Indoor unit capacity is too high Indoor outdoor unit type mismatch Same at left Same at left Check that the total capacities of the indoor and outdoor units are appropriate Reverse 2 phases of the outdoor unit 3 phase ...

Страница 314: ...apacity of the indoor units It is not possible to connect individual remote controllers for independent operation Be careful to avoid miswiring when connecting the wires Miswiring will damage the units 2 1 L N 2 1 L N L N 1 2 Remote control communication wiring Dia 0 5 to 2 mm2 Total length of wiring 200 m or less System address S2 Setting at shipment 0 Leakage breaker Leakage breaker Outdoor unit...

Страница 315: ...stem address rotary switch Change the setting to 2 Leakage breaker Leakage breaker Outdoor unit Outdoor unit Ground Indoor power crossover wiring up to 16 units no heater units only Inter unit control wiring Connection to lead wires Black White Remote control communication wiring for group control field supply wiring Up to 8 units can be set for group control Thickness 0 5 2 0 mm 2 total length 20...

Страница 316: ... is No 21 20s digit ON ON 1 2 ON OFF 1 setting 30 If outdoor unit is No 30 10s digit and 20s digit ON ON OFF ON 1 2 0 setting If the power can be turned ON separately for the indoor and outdoor units in each system The indoor unit addresses can be set without running the compressor Be sure to use a jig for short circuiting Approximately 4 5 minutes are required 1 When there are multiple outdoor un...

Страница 317: ...d If ALL is set operation is possible regardless of the indoor unit address Point the remote controller toward the receiver indoor unit that you wish to operate and send the operation signal Remote controller address setting Press and hold the address button for 4 seconds or longer to display the address on the remote controller display The current address starts blinking The address changes each ...

Страница 318: ...is work If link wiring is used set the outdoor unit system address to allow the combination of indoor and outdoor units to be identified At the same time indicate the indoor outdoor unit combination number in a location where it can be checked easily near the indoor unit nameplates This number will be required for subsequent maintenance This unit may be used in a single type refrigerant system whe...

Страница 319: ... and outdoor power Automatic Address Setting Refer to Table of Self Diagnostic Functions to check the system In addition refer to section Automatic Address Setting for Type U1 T2 F1 N1 and Y2 for Link Wiring and correct any items that need to be corrected Note Check the indoor side drainage Indicate mark the combination number See section Checking indoor unit addresses and Indicating marking the i...

Страница 320: ...rrectly Indoor unit power is not ON Turn ON the indoor unit power Check the remote controller and inter unit control wiring Perform automatic address setting See section Automatic Address Setting for Type U1 T2 F1 N1 and Y2 for Link Wiring E02 displayed Remote controller is not connected with indoor unit correctly Connect the remote controller correctly E14 displayed Connect the wiring correctly E...

Страница 321: ... in each system The indoor unit addresses can be set without running the compressor Be sure to use a jig for short circuiting NOTE A terminal plug black is attached to each of the outdoor unit control PCBs At only one outdoor unit leave the terminal plug shortcircuit socket on the Yes side At all the other outdoor units change the socket from Yes to No A maximum of 8 indoor units can be connected ...

Страница 322: ...old for 4 seconds or longer If the power cannot be turned ON separately for the indoor and outdoor units in each system The compressors must be run in order to automatically set the indoor unit addresses Therefore perform this step after completing the refrigerant tubing work Case 3 Automatic address setting using the remote controller If the power can be turned ON separately for the indoor and ou...

Страница 323: ...2 Outdoor unit control PCB DIP switch System address rotary switch System address rotary switch Set to 0 at time of shipment 10s 20s ON OFF LED1 LED2 PUMP DOWN CN042 EEPROM IC006 AUTO ADD CN041 System address Rotary switch S002 TERMINAL CN003 JP007 System address DIP switch S003 Bottom side Up side HIC Temperature sensor SILENT MODE CN028 WHT RC P CN034 RED FAN CN030 WHT ROM CN012 WHT OC CN013 BLU...

Страница 324: ...ddress changes as follows 1 1 1 2 button and select the indoor address button and button for 4 seconds or longer So that the combination of each indoor unit can be easily checked when multiple units are installed ensure that the indoor and outdoor unit numbers correspond to the system address number on the outdoor unit control PCB and use a magic marker or similar means which cannot be easily remo...

Страница 325: ...the indoor or outdoor unit control PCB fuse 0 5 A for both indoor and outdoor units will blow in order to protect the PCB Correct the wiring connections then disconnect the 2P connectors indoor blue OC outdoor blue serial 1 that are connected to the PCB and replace them with 2P connectors indoor brown EMG outdoor brown serial 2 If operation is still not possible after changing the brown connectors...

Страница 326: ... Automatic Address Setting for Type K1 for Link Wiring and correct any items that need to be corrected Note Check the indoor side drainage Set the automatic address setting from outside unit Indicate mark the combination number See section Setting the outdoor unit system addresses for Type K1 for Link Wiring How to Set the Outdoor Unit System Address See section Basic wiring diagram and Setting th...

Страница 327: ...eck the remote control communication wiring Perform automatic address setting again E15 displayed E16 displayed P09 displayed Timer lamp and Standby lamp are blinking alternately Indoor unit capacity is too low Indoor unit capacity is too high Check that the total capacities of the indoor and outdoor units are appropriate P05 displayed Timer lamp and Standby lamp are blinking alternately Reversed ...

Страница 328: ...o 3 Change setting to 2 System address 2 Change setting to 3 System address 3 Change the terminal plug black short circuit socket Change the terminal plug black short circuit socket If wall mounted type units are used for a simultaneous operation multi system group control refer to section System Control for Type K1 System Control basic wiring diagrams and wiring procedures when wiring ON 1 2 Outd...

Страница 329: ...setting 1 setting 2 setting 1 setting 1 setting 0 setting 1 Turn on the indoor and outdoor unit power for refrigerant system 1 Short circuit the AUTO ADD CN041 pin The compressor operates when the power is turned ON at a different outdoor unit 2 Next turn ON the power only at the indoor and outdoor units in a different system Short circuit the AUTO ADD CN041 pin 3 Operation using the remote contro...

Страница 330: ...r units in each system The compressors must be run in order to automatically set the indoor unit addresses Therefore perform this step after completing the refrigerant tubing work Use the remote controller to check the addresses of the indoor units Be sure to use a jig for short circuiting When setting addresses in heating mode Indicating marking the indoor and outdoor unit combination number Indi...

Страница 331: ...even when the power is turned off Make sure to set Normal for RCU CK Finally press TIMER buttons buttons To set the remote controller main sub setting or change the sensor follow the steps below CODE ITEM ITEM DATA RCU Main Sub Clock display RCU CK Room temperature sensor Sub 24 hours RCU CK Main unit Main 12 hours AM PM Normal RCU SM830231 02 Single 欧州 indb 321 SM830231 02 Single 欧州 indb 321 2014...

Страница 332: ...ly strong wind blow to the area directly in front of the discharge of the outdoor unit there is the risk of damage due to the fan s high speed reverse rotation If the direction of the prevailing wind is known when operating the unit place the unit at an appropriate angle to the wind s direction so that the discharge faces towards a building or a wall 3 4 5 6 7 8 9 If installing at locations prone ...

Страница 333: ...les at the intake If the upper part is open If there are obstacles above the unit 1 For separate installation location Only if there are obstacles at the intake unit mm unit mm If there are obstacles on both sides M o r e t h a n 1 0 0 M ore than 200 M ore than 500 M ore than 100 If there are obstacles on both sides M ore than 200 More than 10 More than 1000 M o r e t h a n 2 0 0 1 2 2 M o r e t h...

Страница 334: ...than 200 The dimensions for H A and L are shown in the following table Cover the bottom part of the pedestal or mount so that air does not bypass it A limit of only 2 units can be installed If the upper part is open If the upper part is open If there are obstacles above the unit If there are obstacles above the unit 1 For separate installation location 1 For separate installation location 1 For se...

Страница 335: ...f the first tier outdoor unit Close A section the space between the upper and lower level outdoor units so the outtake air does not bypass it E For multiple row installation on the roof etc The dimensions for H A and L are shown in the following table A L H 200 H L Installation not possible Pattern 2 If there is an obstacle that is higher than the unit on the discharge side There is no limit to the...

Страница 336: ... with the presence of fluorine dust which will adversely affect the refrigerant piping system due to deterioration of the refrigerant oil etc This unit is specifically for R410A Ensure to adhere to the following items and install accordingly Only for storing or for open pipes Use pipe cutters and flaring tools which are specially designed for use with R410A When connecting with flaring tools coat ...

Страница 337: ...d of the valve shaft Once adjustments to the valve are completed ensure to tighten the valve cap according to the prescribed torque Precautions for handling the valve cap Valve size Tightening torque ø9 52 ø15 88 20 6N m 28 4N m 2 1kgf m 2 8kgf m 48 0N m 59 8N m 4 8kgf m 6 0kgf m Use a push rod with a charge hose Once adjustments to the valve are completed ensure to tighten the valve cap according...

Страница 338: ...hen refilling If gas refrigerant is filled the refrigerant composition will not be balanced and will cause abnormal operation Cylinder with a siphon tube Liquid refrigerant Siphon tube Cylinder Cylinder Gas refrigerant Possible For refilling due to a leak Not possible VACUUM PURGING Use nitrogen gas for the leak tightness test Using flammable gas can cause an explosion Pressure meter Nitrogen Refr...

Страница 339: ...driver and short circuit the pin If the pump down pin PUMPDOWN on the control PCB of the outdoor unit is short circuit refrigerant recovery control is started in the cooling operation When 2 or 3 minutes have passed after the start of outdoor unit operation fully close the liquid narrow tube side valve of the outdoor unit When the pressure gauge installed at the service port reaches the desired pr...

Страница 340: ...tive bushing occurs seal it accordingly Tie the cables with the provided binding strap so that they do not touch the compressor and the pipes When setting up the cables inside of unit install properly so that the front panel will not lift up Make sure that front panel mount correctly ELECTRICAL WIRING SG Use a round type terminal with an insulation sleeve for connecting to the terminal block Use t...

Страница 341: ...g regulations If capacity of power supply circuit and enforcement are not enough it can causes the electric shock and a fire This equipment complies with EN IEC 31000 3 12 provided that the short circuit power Ssc is greater than or equals to 2 kVA at the interface point between the user s supply and the public system It is the responsibility of 2 kVA Ssc SG Short circuit power Shows the earth for...

Страница 342: ...ination combination U 71 S 36 S 36 U 100 S 50 S 50 U 125 S 60 S 60 Type 100 Type 125 Type 140 U 100 S 50 S 50 U 125 S 60 S 60 U 140 S 71 S 71 U 140 S 71 S 71 TRIPLE ______ ______ ______ U 100 S 36 S 36 S 36 U 125 S 45 S 45 S 45 U 140 S 50 S 50 S 50 DOUBLE TWIN U 125 S 36 S 36 S 36 S 36 ______ This unit cannot make triple or double twin connections Two indoor units can be operated simultaneously wi...

Страница 343: ...YMBOLS SPEC TWIN L La Lb La or Lb Maximum branch pipe length difference Total pipe length Maximum branch pipe length Height difference between indoor units La Lb La Lb Height difference Outdoor located higher installation Outdoor located lower installation H2 H1 H1 Less than 50m Less than 15m Less than 10m Less than 0 5m Less than 30m Less than 15m For Type PE1 The following table shows the equiva...

Страница 344: ...ipe Main pipe Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Use the main pipe to gain any rise or fall required for the pipes The number of bends should be 8 or less in a single system and 15 or less overall Branch pipes should be positioned horizontally SM830231 02 Single 欧州 indb 334 SM830231 02 Single 欧州 indb 334 2014 09 19 13 21 53 2014 09 19 13 21 53 ...

Страница 345: ...h Earth Earth Wired remote controller Indoor unit Indoor unit TRIPLE type DOUBLE TWIN type Controll cable Controll cable Controll cable Controll cable Switch Circuit breaker Switch Circuit breaker Switch Circuit breaker Switch Circuit breaker Switch Circuit breaker Switch Indoor unit Indoor unit For the twin connection the amount of refrigerant required for pipe length 30m has been included in thi...

Страница 346: ...ore than 1 MΩ Use the 500 V mega testers to measure the insulation Do not use the mega tester for any other circuit except for voltage of 220V to 240V or 380 415V Are the wire connections for the indoor outdoor units connected as described in the instructions Are there any looped wires Was the N phase surely connected when connecting the power supply wire on the three phase model If N phase is not...

Страница 347: ...d Is the earth wire securely connected Is the front panel and the indoor unit air conditioner firmly fixed and was the installation completed without any leakage from the refrigerant Are the indoor and outdoor units secured firmly installed with bolts at secured locations REGARDING DELIVERY TO THE CUSTOMER Request the customer to review the instruction manual and explain the operating method for t...

Страница 348: ...rigerant allowable pipe lengths and allowable elevation difference refer to the Installation Instructions provided with the outdoor unit The diameter of the piping for the indoor and outdoor units differs depending on the model of the unit Refer to respective diameter of the piping for the indoor and the outdoor units and install accordingly Use pipe cutters to cut the appropriate connecting secti...

Страница 349: ... pipe insulation Note Use insulating material that can tolerate 120 C on the gas side 2 1 Installation Instructions Refrigerant pipe Output 1 Refrigerant pipe Gas side Liquid side branch pipe To the outdoor unit or next branch pipe Input Output 2 To next branch pipe or indoor unit Installation on a vertical plane is also possible 2 2 Installation precaution 2 3 Precautions at connecting points Pos...

Страница 350: ...hermal insulation for liquid distribution joints Thermal insulation for gas distribution joints Gas tube side tube connector 100 35 80 80 295 ø9 52 ø9 52 ø9 52 1 2 1 2 3 4 5 6 BCUP 3 100 80 80 300 100 ø12 7 ø25 4 ø15 88 ø15 88 ø15 88 1 1 ø9 52 ø12 7 ø9 52 ø6 35 3 1 ø12 7 ø15 88 ø19 05 ø25 4 3 1 1 1 1 ø15 88 ø19 05 ø25 4 ø28 58 2 SM830231 02 Single 欧州 indb 340 SM830231 02 Single 欧州 indb 340 2014 09...

Страница 351: ...t to the ground The collective tubes are vertical with respect to the ground The collective tube and distribution joint are horizontal with respect to the ground Collective tube Distribution joint Gas tube side Only the distribution joints are horizontal with respect to the ground The collective tubes are vertical with respect to the ground The collective tube and distribution joint are horizontal...

Страница 352: ... of the room can be uniformly cooled select a location where the ceiling is strong enough to support the weight of the unit select a location where tubing and drain pipe have the shortest run to the outdoor unit allow room for operation and maintenance as well as unrestricted air flow around the unit install the unit within the maximum elevation difference above or below the outdoor unit and withi...

Страница 353: ...ation diagram The diagram and table Fig 1 9 and Table 1 5 show the relationship between the positions of the suspension fitting unit and panel Use the nut field supply and washer supplied for upper and lower position of the suspension lug Table 1 5 Unit mm Length Type A B C D E 36 45 50 60 71 121 171 256 180 130 100 125 140 121 171 319 180 130 Hole in anchor Hole in plug Concrete Insert Suspension...

Страница 354: ...hers field supply onto each of the 4 suspension bolts as shown in Fig 1 11 Use 1 nut and 1 washer for the upper side and 2 nuts and 1 washer for the lower side so that the unit will not fall off the suspension lugs 4 Adjust so that the distance between the unit and the ceiling bottom is 12 to 17 mm Tighten the nuts on the upper side and lower side of the suspension lug 5 Remove the protective poly...

Страница 355: ...sult in water leakage Fig 1 12 2 Limitations of Drain Pipe Connection CAUTION Do not install the drain pipe with an upward slant from the drain port connection This will cause the drain water to flow backward and leak when the unit is not operating Fig 1 13 Do not install an air bleeder as this may cause water to spray from the drain pipe outlet Fig 1 13 Do not provide U trap or bell shaped trap i...

Страница 356: ... without connection of the hard PVC socket and the hard PVC joint VP25 in the local supply 6 Connect the drain hose and the hard PVC joint so that the adhesive area of both sides can be overlapped Wipe off the protrusion adhesive with a soft cloth Drain port Do not use adhesive here Drain port may possibly be damaged if PVC adhesive is used After checking the drainage wrap the supplied packing and...

Страница 357: ...eck the following items k r a m e R k c e h C m o t p m y S t n i o p k c e h C 1 Make sure whether indoor and outdoor units are correctly installed Fall vibration noise 2 Make sure whether gas leakage is tested No cooling no heating 3 Make sure whether insulation is completed Refrigerant piping and drain piping Water leakage 4 Make sure whether drain water is running smoothly Water leakage 5 Make...

Страница 358: ...he wires from the power supply inlet to the unit Be sure to lead the wires through the power supply inlet Make sure that no wire is caught between the indoor unit and ceiling panel Otherwise the unit may cause a fire 5 Connect the wires into the terminals through the power supply inlet for the electrical component box Fix the wires with a clamping clip 6 Reinstall the lid of the electrical compone...

Страница 359: ...ng panel corner with the correct positions on the unit When removing the ceiling panel push the temporary latches outward while holding the ceiling panel Fig 1 22 Fig 1 22 2 Align the panel installation holes and the unit screw holes 3 Tighten the supplied washer head screws at the 4 panel installation locations so that the panel is attached tightly to the unit Fig 1 23 Fig 1 23 4 Check that the p...

Страница 360: ...talling multiple units and change the directions according to customer s requests When attaching the air intake grille be careful that the flap lead wire does not become caught Be sure to attach the safety cord that prevents the air intake grille from dropping off to the ceiling panel unit as shown in the figure below With this ceiling panel the directions of the air intake grille lattices when in...

Страница 361: ...B Connect the jumper connector 2P yellow which was supplied with the accessory to the correct connector pin on the indoor unit control PCB according to the setting number which was confirmed in Table for DC Fan Motor Tap Settings Setting No 3 Then connect the jumper connector to the connector pin TP3 2P yellow on the indoor unit control PCB Setting No 6 Then connect the jumper connector to the con...

Страница 362: ... timer time buttons to select the desired setting data Flap position 1 2 3 4 5 Fig 1 27 Setting data refer to Fig 1 27 Setting data Flap position during operation Without separate setting Swing Move to position 1 and stay Move to position 2 and stay Move to position 3 and stay Move to position 4 and stay Move to position 5 and stay When the flap position is set to 4 or 5 and the unit is in the coo...

Страница 363: ... tube flare nuts Flare insulator 1 For liquid tube Flare insulator 1 For gas tube Drain hose 1 Hose band 1 For securing drain hose Packing 1 Drain insulator 1 Clamper 3 Operating Instructions 1 A5 size Installation Instructions 1 Included this instructions Use M10 for suspension bolts Field supply for suspension bolts and nuts SM830231 02 Single 欧州 indb 353 SM830231 02 Single 欧州 indb 353 2014 09 1...

Страница 364: ...ion where the ceiling is strong enough to support the weight of the unit select a location where tubing and drain pipe have the shortest run to the outdoor unit allow room for operation and maintenance as well as unrestricted air flow around the unit install the unit within the maximum elevation difference above or below the outdoor unit and within a total tubing length L from the outdoor unit as ...

Страница 365: ...Figure shows view from front Remote control wiring and inter unit wiring inlet port Left rear side drain hose outlet port cutout Cover of rear tubing hole Power inlet port 1 the indented portion of the side cover and make a hole inside the cover 2 Use a compass saw jigsaw or similar tool and cut along When removing the refrigerant tubing from the upper side cut along the indented portion and pass ...

Страница 366: ... Center bracket Fig 1 35 2 3 Suspending the Indoor Unit NOTE Since the diagram is made of paper it may shrink or stretch slightly because of high temperature or humidity For this reason before drilling the holes maintain the correct dimensions between the markings 1 If the full scale installation diagram is placed on the ceiling the locations of each suspension bolt can be chosen Take a pencil and...

Страница 367: ...the bracket Tighten the M8 suspension bolts and fix the indoor unit in place Fig 1 44 M4 screw for preventing bracket from taking off M8 suspension bolts M8 suspension bolt Fig 1 44 NOTE The ceiling surface is not always level Confirm that the indoor unit is evenly suspended For the installation to be correct leave a clearance of about 10 mm between the ceiling panel and the ceiling surface and fi...

Страница 368: ...the hose band with the drain insulator where the screw is located facing upward Fig 1 50 Then tighten the insulator with a vinyl tape not to cause the detachment If the tubing parts remain exposed condensation may occur Be sure to use the supplied drain hose If other commercially available hose bands are used the drain hose may become pinched or wrinkled and there is danger of water leakage Theref...

Страница 369: ...ws Safety string Fig 1 53 Ceiling Part Name Figure Q ty Remarks Special washer For temporarily suspending indoor unit from ceiling Drain insulator For drain hose joint Flare insulator For gas tube joint For liquid tube joints For positioning installation Clamper For flare insulator and wiring Full scale installation diagram Drain hose For main unit PVC pipe joints Hose band Side cover R Side cover...

Страница 370: ...ich every corner of the room can be uniformly cooled select a location where the ceiling is strong enough to support the weight of the unit select a location where tubing and drain pipe have the shortest run to the outdoor unit allow room for operation and maintenance as well as unrestricted air flow around the unit install the unit within the maximum elevation difference above or below the outdoo...

Страница 371: ...location selected Make sure the panel is horizontal using a carpenter s level or tape measure to measure down from the ceiling Wait until after cutting the hole before attaching the rear panel to the wall 2 Determine which side of the unit you should make the hole for tubing and wiring Fig 1 59 NOTE In the case of left rear tubing use the measurement points 158 mm from the marked position on the r...

Страница 372: ...all 1 Attach the rear panel to the wall with the 8 screws provided Fig 1 63 If you are not able to line up the holes in the rear panel with the beam locations marked on the wall use rawl plugs or toggle bolts to go through the holes on the panel or drill 5 mm dia holes in the panel over the stud locations and then mount the rear panel 2 Double check with a carpenter s level or tape measure that th...

Страница 373: ...aligning the top edge of the grille with the frame move the grille horizontally and insert the top and bottom into the frame 2 Press the grille firmly with your hand to ensure no gap exists between the frame and grille 3 Tighten the 6 screws And fix the removed covers in place 4 Grasp the sections near the front panel arms on both sides and hold the front panel so that it is nearly horizontal Push...

Страница 374: ... for each unit with a power supply disconnect and circuit breaker for overcurrent protection provided in the exclusive line 3 To prevent possible hazards due to insulation failure the unit must be grounded 4 Each wiring connection must be done tightly and in accordance with the wiring system diagram Wrong wiring may cause the unit to misoperate or become damaged 5 Do not allow wiring to touch the ...

Страница 375: ...igerant tubing and drain hose through the hole in the wall Adjust the indoor unit so it is securely seated on the rear panel Fig 1 78 3 Carefully bend the tubing if necessary to run along the wall in the direction of the outdoor unit and then tape as far as the fittings The drain hose should come straight down the wall to a point where water runoff won t stain the wall 4 Connect the refrigerant tu...

Страница 376: ...ket and the drain pan outlet are aligned and securely in contact then fasten them with the screw After attaching the drain hose check that it is attached securely Fig 1 84 Drain cap Use a Phillips head screwdriver to push the drain cap in firmly If it is difficult to push in wet the cap with water first 3 Install the indoor unit on the rear panel 4 Connect the tubing and wiring led inside from out...

Страница 377: ...rain hose should be slanted downward to the outdoors Fig 1 88 b Never form a trap in the course of the hose c If the drain hose will run in the room insulate the hose with insulation so that chilled condensation will not damage furniture or floors Fig 1 89 Foamed polyethylene or its equivalent is recommended WARNING Do not supply power to the unit or operate it until all tubing and wiring to the o...

Страница 378: ... Name Figure Q ty Tapping screw Truss head Phillips 4 20 mm 8 Tapping screw Truss head Phillips 4 10 mm 2 Flare insulation 1 SM830231 02 Single 欧州 indb 368 SM830231 02 Single 欧州 indb 368 2014 09 19 13 22 00 2014 09 19 13 22 00 ...

Страница 379: ...ct an appropriate position from which every corner of the room can be uniformly cooled select a location where the ceiling is strong enough to support the weight of the unit select a location where tubing and drain pipe have the shortest run to the outdoor unit allow room for operation and maintenance as well as unrestricted air flow around the unit install the unit within the maximum elevation di...

Страница 380: ...i c d b a e j Fig 1 90 Table 1 7 Unit mm Type A B C D E F 36 45 50 867 800 450 Pitch 150 3 71 592 12 60 71 1 067 1 000 750 Pitch 150 5 21 792 16 100 125 140 1 467 1 400 1 050 Pitch 150 7 71 1 192 20 Table 1 8 Unit mm Air intake port side Air outlet duct side F ø3 holes E Flange O D A Suspension bolt pitch Unit mm Fig 1 91 a Refrigerant tubing joint liquid tube b Refrigerant tubing joint gas tube c...

Страница 381: ...de the ceiling when suspending the unit If the ceiling is already constructed lay the tubing into position for connection to the unit before placing the unit inside the ceiling 2 Screw in the suspension bolts allowing them to protrude from the ceiling Fig 1 92 Cut the ceiling material if necessary 3 Thread the 3 hexagonal nuts and 2 washers field supply onto each of the 4 suspension bolts Figs 1 9...

Страница 382: ...be raised a maximum of 500 mm Do not raise it any higher than 500 mm as this could result in water leaks Fig 1 100 300 mm or less 500 mm or less Good Fig 1 100 Do not install the pipe with an upward slant from the connection port This will cause the drain water to flow backward and leak when the unit is not operating Fig 1 101 Upward slant Prohibited Fig 1 101 Do not apply force to the piping on t...

Страница 383: ...nstallation Fig 1 105 NOTE Select an air intake grille with a filter at a local shop To get clean air and to extend the service life of the air conditioner an air filter must be installed in the air intake For installation and cleaning the air filter consult your dealer or service center Pull out Bracket Packing Filter Fig 1 104 K ø4 1 hole For M5 self tapping screw 250 150 H G H 50 50 J Type G H ...

Страница 384: ...djusted to the rated airflow volume with the auto airflow control drive Flow of External Static Pressure Finish the ducting and electrical wiring and prepare it for use Note 1 External static pressure should be set during initial operations after installation before the cooling and heating test run When operating with group control connecting multiple indoor units with one wired remote controller ...

Страница 385: ... pressure setting range There are cases in which automatic variable dampers and other mounted items may trigger the P12 alarm on systems that modify the external static pressure when the auto airflow volume control operations or setting check operations are carried out if high external static pressure is lowered In this event lower the dampers etc so that the external static pressure reaches its l...

Страница 386: ...er s LCD display 2 Press the button to commence the test run Test Run will be displayed on the remote controller s LCD display 3 Select the fan mode and set it to H by pressing the button Auto airflow volume control operations and external static pressure setting check operations will not be performed unless H has been selected for the fan mode 4 The fan motor will be activated and auto airflow vo...

Страница 387: ...t line Limit line Limit line Limit line Type 60 71 Airflow Volume m3 minute 0 50 100 150 180 0 3 0 2 1 3 1 2 3 1 6 5 15 14 13 12 11 8 PQ diagram External static pressure Pa L i m i t l i n e L i m i t l i n e Lim it line Limit line Limit line Type 100 Airflow Volume m3 minute 15 14 13 12 11 8 6 5 3 0 50 100 150 180 0 4 0 3 0 2 1 3 1 2 1 PQ diagram External static pressure Pa Limit line Limit line ...

Страница 388: ...hose Packing 1 For drain hose joint hard material Packing 1 For drain hose joint soft material Drain hose 1 Operating Instructions 1 A5 size Installation Instructions 1 Included this instructions Short circuit connection 1 For high static pressure Located on the back of the electrical component box lid Use M10 for suspension bolts Suspension bolts and nuts are field supply SM830231 02 Single 欧州 in...

Страница 389: ...range 2 Attach the duct frange to the side of the unit with the supplied screws Duct frange 4 circle duct frange CZ 160DAF2 3 circle duct frange CZ 90DAF2 2 circle duct frange CZ 56DAF2 SM830231 02 Single 欧州 indb 379 SM830231 02 Single 欧州 indb 379 2014 09 19 13 22 03 2014 09 19 13 22 03 ...

Страница 390: ...7 170 170 300 100 840 45 245 240 245 244 107 107 160 160 260 260 100 244 107 107 1240 45 265 300 300 265 185 185 290 290 290 100 8 Ø6 holes 10 Ø6 holes 12 Ø6 holes Ø200 Ø200 Ø200 Ø200 Ø200 Ø200 Ø200 Ø200 Ø200 unit mm unit mm unit mm SM830231 02 Single 欧州 indb 380 SM830231 02 Single 欧州 indb 380 2014 09 19 13 22 03 2014 09 19 13 22 03 ...

Страница 391: ...position from which every corner of the room can be uniformly cooled select a location where the ceiling is strong enough to support the weight of the unit select a location where tubing and drain pipe have the shortest run to the outdoor unit allow room for operation and maintenance as well as unrestricted air flow around the unit install the unit within the maximum elevation difference above or ...

Страница 392: ...ge hole Unit mm Remove the absorber at air return hole before installation Absorber A TYPE B C D E S 36PN1E5A S 45PN1E5A S 50PN1E5A S 60PN1E5A S 71PN1E5A S 100PN1E5A S 125PN1E5A S 140PN1E5A 840 780 523 64 650 1060 1000 523 64 650 1260 1200 523 64 650 Uint mm Inspection hole Front Control box Top view Front view 600 x 600 600 600 1000 Above 250cm A B C D E Apply a joint canvas between the unit and ...

Страница 393: ... 55 100 670 585 P65 x 9 780 P65 x 12 650 P65 x 10 845 P65 x 13 65 64 250 80 65 740 780 523 134 45 20 840 3 2 1 6 5 4 4 Air Flow Outside Dimensions MODEL NO UNIT mm Air Flow Hanger Drain pipe connection Pipe connection liquid 1 2 3 4 5 NO 6 NOTE NAME Pipe connection gas 4 Q TY 2 1 1 2 1 Duct connection Control box O D Ø15 88 Flared O D Ø9 52 Flared Female screw PT1 S 71PN1E5A S 60PN1E5A 55 55 100 8...

Страница 394: ...lared Female screw PT1 Outside Dimensions MODEL NO UNIT mm S 100PN1E5A S 140PN1E5A S 125PN1E5A 100 1260 1090 250 64 46 Ø4 5 44 Ø4 5 80 1160 20 1320 523 1200 65 57 5 60 1040 P65x16 58 48 31 65 161 48 30 650 30 31 32 187 65 4 5 4 3 2 1 6 Drain pipe connection 975 P65 x 15 Air Flow SM830231 02 Single 欧州 indb 384 SM830231 02 Single 欧州 indb 384 2014 09 19 13 22 04 2014 09 19 13 22 04 ...

Страница 395: ... from the ceiling Fig 1 110 Cut the ceiling material if necessary 3 Thread the 3 hexagonal nuts and 2 washers field supply onto each of the 4 suspension bolts Figs 1 112 and 1 113 Use 1 nut and 1 washer for the upper part and 2 nuts and 1 washer for the lower part so that the unit will not fall off the suspension lugs Fig 1 112 Suspension bolt Nuts and washers use for upper and lower Double nuts S...

Страница 396: ...onnecting the drain pipe The pipe should not be allowed to hang unsupported from its connection to the unit Fasten the pipe to a wall frame or other support as close to the unit as possible Fig 1 120 Support pieces Fig 1 115 2 After connecting the drain pipe securely wrap the supplied packing and drain pipe insulator around the pipe then secure it with the vinyl clamps Fig 1 116 Fig 1 120 Drain in...

Страница 397: ...tomatically adjusted to the rated airflow volume with the auto airflow control drive Flow of External Static Pressure Finish the ducting and electrical wiring and prepare it for use Note 1 External static pressure should be set during initial operations after installation before the cooling and heating test run When operating with group control connecting multiple indoor units with one wired remot...

Страница 398: ...efer to Fig 1 123 for the external static pressure setting range There are cases in which automatic variable dampers and other mounted items may trigger the P12 alarm on systems that modify the static pressure of outdoor units when the auto airflow volume control operations or setting check operations are carried out if high static pressure in the outdoor unit is lowered In this event lower the da...

Страница 399: ...r s LCD display 2 Press and hold down the Press the button to commence the test run Test Run will be displayed on the remote controller s LCD display 3 Select the fan mode and set it to H by pressing the button Auto airflow volume control operations and external static pressure setting check operations will not be performed unless H has been selected for the fan mode 4 The fan motor will be activa...

Страница 400: ...ipment Item code Fig 1 123 P Q diagram 0 50 100 16 26 Air Volume m3 min 3 2 S 60PN1E5A S 71PN1E5A Limit line External Static Pressure Pa P Q diagram 0 50 100 6 3 6 2 Air Volume m3 min 3 2 S 125PN1E5A Limit line 40 30 External Static Pressure Pa P Q diagram 0 50 100 4 3 4 2 Air Volume m3 min 3 2 S 100PN1E5A 40 30 Limit line External Static Pressure Pa P Q diagram 0 50 100 6 3 6 2 Air Volume m3 min ...

Страница 401: ... pressure duct switch Fan Motor connector to plug in boost tap white connector to elevate air volume 0 10 20 30 40 50 60 70 80 18 8 0 10 20 30 40 50 60 70 80 20 10 P Q CURVE External Static Pressure Pa Air Volume m3 min Lo S 36PN1E5A P Q CURVE S 45PN1E5A S 50PN1E5A Me standard tap Hi boost tap SHi Lo Me standard tap Hi boost tap SHi External Static Pressure Pa Air Volume m3 min SM830231 02 Single ...

Страница 402: ... Hose band For securing drain hose Foam drain socket For drain hole another side of drain hose Drain hose Flange For inlet duct installation Screw 8 2 5 1 1 2 4 Use M10 for suspension bolts Suspension bolts and nuts are field supply SM830231 02 Single 欧州 indb 392 SM830231 02 Single 欧州 indb 392 2014 09 19 13 22 05 2014 09 19 13 22 05 ...

Страница 403: ...pipe have the shortest run to the outdoor unit allow room for operation and maintenance as well as unrestricted air flow around the unit install the unit within the maximum elevation difference above or below the outdoor unit and within a total tubing length L from the outdoor unit as detailed in the installation manual packed with the outdoor unit allow room for mounting the remote controller abo...

Страница 404: ...00 Ceiling opening 575 Unit size CAUTION Tighten the nut and bolt to prevent unit from falling WARNING The dimensions of the paper model for installation are the same as those of the ceiling opening dimensions Be sure to discuss the ceiling drilling work with the workers concerned Open the ceiling board along the outer edge of the paper model Adjust to the same height Ceiling Air conditioner body ...

Страница 405: ... Drain port Indoor unit 750 mm or less Down slope 1 50 1 100 Elbow Elbow Fig 1 131 When drain set piping install as shown in the figure below Use VP30 or more for confluence Indoor unit Down slope 1 50 1 100 Apply the head when connecting with the confluence pipe about 100 mm Fig 1 132 Drain Test The air conditioner uses a drain up motor to drain water Use the following procedure to test the drain ...

Страница 406: ... pressure the use of ordinary flare nuts type 1 or thin walled tubes may result in tube rupture injury or asphyxiation caused by refrigerant leakage In order to prevent damage to the flare caused by over tightening of the flare nuts use the table above as a guide when tightening When tightening the flare nut on the liquid tube use an adjustable wrench with a nominal handle length of 200 mm Thermal...

Страница 407: ...ditions with Mist and have been confirmed that there are no faults However if it is operated for a long time in high humid atmosphere dew point temperature more than 23 C water drops are liable to fall In this case add heat insulation material according to the following procedure Overlap with heat insulator for piping Heat insulator Accessory Heat insulator for piping Local supply Band Accessory I...

Страница 408: ... the screws 3 pcs before fitting move decorative panel as illustrated and tighten all the screws 4 pcs Check before hand the height from the ceiling to the unit The front grille fitting direction is determined by the unit direction Only use the screws with the length of 35 mm which is provided to fix the decorative panel Do not use other screw which is longer it may cause damage to the drain pan a...

Страница 409: ...ation lamp on the display blinks Example of PROPER installation Example of IMPROPER installation Air conditioner unit Ceiling Decorative panel Fit the insulator this part and be careful for cool air leakage Air Fig 1 144 Cool air leakage no good Air conditioner unit Ceiling Decorative panel Air Fig 1 145 Ground screw LM CN033 WL CN130 Fig 1 146 Be sure to hook the air inlet grille string to preven...

Страница 410: ...h a clip 1 Heat Insulator 2 Band 4 Flat washer for M10 8 Screw M5 4 Operating Instructions 1 Installation Instructions 1 Use M10 for hanging bolts Field supply for hanging bolts and nuts SM830231 02 Single 欧州 indb 400 SM830231 02 Single 欧州 indb 400 2014 09 19 13 22 07 2014 09 19 13 22 07 ...

Страница 411: ...tor for Liquid pipe E1 H Thermistor for Heat exchanger pipe middle E2 I Thermistor for Suction air TA J Inter unit wiring K Magnetic relay for operating the blower Field supplied Strainer Liquid pipe Gas pipe Min ø25 4 100 Field supply Single connection Single connection type only System piping length Charging with refrigerant At the time of shipment from the factory the outdoor unit is charged wi...

Страница 412: ...n the lowest position after distributer in heat exchanger Cover the thermistor and pipe with aluminum tape Cover the thermistor and pipe with aluminum tape Thermal insulation and wiring are fixed in two bands Cover the aluminum tape with thermal insulation Installation of Strainer Field supplied Attach the strainer to the side of the outdoor unit for Gas Liquid piping See the System Overview on pr...

Страница 413: ...ange is shown below Table 1 14 Inside volume of heat exchanger Table 1 15 Air volume of heat exchanger Table 1 16 Front area of heat exchanger Cooling Capacity 10 kW 12 5 kW 14 kW 0 51 m2 0 51 m2 0 51 m2 0 43 m2 0 43 m2 0 43 m2 Front area 1 2 3 4 X1 Minimum applicable load DC 5 V 1 mA Maximum applicable load AC 230 V 2 A SW 1 operation command field supply AC 220 240 V 0 1 A Max Min Cooling Capaci...

Страница 414: ... of steps Distance between tube sheets Number of rows 1 5 10 4 For example Number of steps 12 Distance between tube sheets 1000 mm Number of rows 3 Minimum number of passes 12 1000 3 1 5 10 4 5 4 6 passes SM830231 02 Single 欧州 indb 404 SM830231 02 Single 欧州 indb 404 2014 09 19 13 22 08 2014 09 19 13 22 08 ...

Страница 415: ...92 5 0 5 0 2 13 3 9 3 9 1 40 19 6 4 4 5 1 67 6 0 4 4 1 82 5 6 4 2 2 00 5 4 4 1 2 22 4 2 3 7 1 46 22 7 0 3 6 1 74 6 5 3 4 1 89 6 1 3 3 2 08 5 9 3 2 2 31 4 6 2 7 1 52 29 16 5 9 5 9 1 61 5 6 5 6 1 74 5 2 5 2 1 92 5 0 5 0 2 13 3 9 3 9 1 40 19 6 4 5 2 1 67 6 0 5 0 1 82 5 6 4 8 2 00 5 4 4 7 2 22 4 2 4 2 1 46 22 7 0 4 2 1 74 6 5 4 0 1 89 6 1 3 8 2 08 5 9 3 8 2 31 4 6 3 3 1 52 32 16 5 9 5 9 1 61 5 6 5 6 1...

Страница 416: ...0 3 35 14 2 8 0 3 60 13 7 7 8 3 83 12 7 7 5 3 98 9 3 6 2 3 25 29 16 12 4 12 4 3 11 12 4 12 4 3 34 11 9 11 9 3 56 11 0 11 0 3 70 8 1 8 1 3 02 19 13 2 12 2 3 25 13 2 12 2 3 49 12 7 11 8 3 71 11 8 11 7 3 86 8 6 8 6 3 15 22 14 5 9 8 3 36 14 5 9 8 3 61 13 9 9 5 3 84 12 9 9 2 3 99 9 5 7 9 3 26 32 16 12 5 12 5 3 12 12 5 12 5 3 35 12 1 12 1 3 56 11 2 11 2 3 71 8 2 8 2 3 03 19 13 4 12 3 3 25 13 4 12 3 3 50...

Страница 417: ... 3 48 12 5 9 9 3 70 11 6 9 7 3 85 8 5 8 4 3 15 22 14 2 8 0 3 35 14 2 8 0 3 60 13 7 7 7 3 83 12 7 7 4 3 98 9 3 6 1 3 25 29 16 12 4 12 4 3 11 12 4 12 4 3 34 11 9 11 9 3 56 11 0 11 0 3 70 8 1 8 1 3 02 19 13 2 11 9 3 25 13 2 11 9 3 49 12 7 11 6 3 71 11 8 11 4 3 86 8 6 8 6 3 15 22 14 5 9 6 3 36 14 5 9 6 3 61 13 9 9 4 3 84 12 9 9 1 3 99 9 5 7 7 3 26 32 16 12 5 12 5 3 12 12 5 12 5 3 35 12 1 12 1 3 56 11 ...

Страница 418: ... 98 9 9 9 9 4 89 19 16 1 13 1 5 25 16 1 13 2 5 64 15 5 12 7 6 00 14 4 12 6 6 24 10 5 10 5 5 10 22 17 7 10 1 5 43 17 7 10 1 5 83 17 0 9 8 6 21 15 8 9 5 6 46 11 5 7 8 5 28 29 16 15 3 15 3 5 05 15 3 15 3 5 42 14 7 14 7 5 77 13 7 13 7 6 00 10 0 10 0 4 90 19 16 4 15 4 5 26 16 4 15 4 5 65 15 7 14 9 6 01 14 6 14 6 6 26 10 7 10 7 5 11 22 17 9 12 3 5 44 17 9 12 4 5 85 17 2 11 9 6 22 16 0 11 7 6 47 11 7 10 ...

Страница 419: ... 22 9 0 4 8 2 55 8 7 4 7 2 71 8 3 4 5 2 86 7 8 4 3 2 75 6 8 4 0 2 36 29 16 8 1 8 1 2 36 7 9 7 9 2 53 7 6 7 6 2 72 7 2 7 2 2 70 6 3 6 3 2 31 19 8 5 7 1 2 45 8 3 7 0 2 61 8 0 6 8 2 78 7 5 6 5 2 72 6 6 6 3 2 34 22 9 0 5 6 2 55 8 7 5 5 2 71 8 3 5 2 2 86 7 8 5 2 2 75 6 8 4 7 2 36 32 16 8 1 8 1 2 36 7 9 7 9 2 53 7 6 7 6 2 72 7 2 7 2 2 70 6 3 6 3 2 31 19 8 5 7 1 2 45 8 3 7 0 2 61 8 0 6 8 2 78 7 5 6 5 2 7...

Страница 420: ... 13 1 12 5 5 63 9 5 9 4 4 60 19 15 6 10 9 4 94 15 6 10 8 5 31 15 0 10 4 5 65 14 0 10 2 5 88 10 2 8 6 4 80 22 17 1 8 6 5 11 17 1 8 7 5 49 16 4 8 4 5 85 15 3 8 0 6 08 11 2 6 5 4 97 29 16 14 8 14 6 4 75 14 8 14 6 5 10 14 3 14 1 5 43 13 3 13 1 5 65 9 7 9 6 4 62 19 15 8 12 3 4 96 15 8 12 4 5 32 15 2 12 0 5 66 14 2 11 8 5 89 10 4 10 1 4 81 22 17 3 10 2 5 13 17 3 10 3 5 51 16 7 10 0 5 86 15 5 9 5 6 09 11...

Страница 421: ... 7 3 62 12 5 9 4 3 85 11 6 9 1 4 00 8 5 7 7 3 27 22 14 2 7 6 3 49 14 2 7 6 3 74 13 7 7 5 3 98 12 7 7 1 4 14 9 3 5 8 3 39 29 16 12 4 12 4 3 24 12 4 12 4 3 48 11 9 11 9 3 70 11 0 11 0 3 85 8 1 8 1 3 15 19 13 2 11 2 3 38 13 2 11 2 3 63 12 7 11 0 3 86 11 8 10 6 4 01 8 6 8 6 3 28 22 14 5 9 2 3 49 14 5 9 2 3 75 13 9 9 0 3 99 12 9 8 6 4 15 9 5 7 2 3 39 32 16 12 5 12 5 3 25 12 5 12 5 3 49 12 1 12 1 3 71 1...

Страница 422: ... 1 13 1 5 63 9 5 9 5 4 60 19 15 6 11 9 4 94 15 6 12 0 5 31 15 0 11 6 5 65 14 0 11 4 5 88 10 2 9 7 4 80 22 17 1 9 4 5 11 17 1 9 4 5 49 16 4 9 1 5 85 15 3 8 8 6 08 11 2 7 2 4 97 29 16 14 8 14 8 4 75 14 8 14 8 5 10 14 3 14 3 5 43 13 3 13 3 5 65 9 7 9 7 4 62 19 15 8 13 8 4 96 15 8 13 9 5 32 15 2 13 4 5 66 14 2 13 3 5 89 10 4 10 4 4 81 22 17 3 11 3 5 13 17 3 11 3 5 51 16 7 10 9 5 86 15 5 10 6 6 09 11 3...

Страница 423: ...PK1E5A U 71PE1E5A U 71PE1E8A 220V 230V 240V 50Hz 1 phase 3 phase 23 16 8 1 6 0 2 25 7 9 5 9 2 41 7 6 5 7 2 59 7 2 5 5 2 57 6 3 5 1 2 20 19 8 5 4 5 2 33 8 3 4 4 2 49 8 0 4 3 2 65 7 5 4 0 2 60 6 6 3 8 2 23 22 9 0 3 2 2 44 8 7 3 1 2 58 8 3 2 9 2 73 7 8 2 7 2 62 6 8 2 4 2 25 25 16 8 1 6 8 2 25 7 9 6 7 2 41 7 6 6 5 2 59 7 2 6 3 2 57 6 3 5 9 2 20 19 8 5 5 3 2 33 8 3 5 2 2 49 8 0 5 1 2 65 7 5 4 8 2 60 6 ...

Страница 424: ... 8 3 48 12 5 9 5 3 70 11 6 9 3 3 85 8 5 7 9 3 15 22 14 2 7 7 3 35 14 2 7 7 3 60 13 7 7 4 3 83 12 7 7 2 3 98 9 3 5 9 3 25 29 16 12 4 12 4 3 11 12 4 12 4 3 34 11 9 11 9 3 56 11 0 11 0 3 70 8 1 8 1 3 02 19 13 2 11 4 3 25 13 2 11 4 3 49 12 7 11 0 3 71 11 8 10 9 3 86 8 6 8 6 3 15 22 14 5 9 4 3 36 14 5 9 4 3 61 13 9 9 0 3 84 12 9 8 7 3 99 9 5 7 4 3 26 32 16 12 5 12 5 3 12 12 5 12 5 3 35 12 1 12 1 3 56 1...

Страница 425: ... 5 5 98 9 9 9 9 4 89 19 16 1 12 5 5 25 16 1 12 6 5 64 15 5 12 2 6 00 14 4 11 9 6 24 10 5 10 2 5 10 22 17 7 9 9 5 43 17 7 9 9 5 83 17 0 9 5 6 21 15 8 9 3 6 46 11 5 7 6 5 28 29 16 15 3 15 3 5 05 15 3 15 3 5 42 14 7 14 7 5 77 13 7 13 7 6 00 10 0 10 0 4 90 19 16 4 14 6 5 26 16 4 14 7 5 65 15 7 14 1 6 01 14 6 13 9 6 26 10 7 10 7 5 11 22 17 9 11 8 5 44 17 9 11 9 5 85 17 2 11 5 6 22 16 0 11 2 6 47 11 7 9...

Страница 426: ...5 0 5 0 2 13 3 9 3 9 1 40 19 6 4 4 7 1 67 6 0 4 5 1 82 5 6 4 3 2 00 5 4 4 2 2 22 4 2 3 8 1 46 22 7 0 3 6 1 74 6 5 3 4 1 89 6 1 3 3 2 08 5 9 3 2 2 31 4 6 2 8 1 52 29 16 5 9 5 9 1 61 5 6 5 6 1 74 5 2 5 2 1 92 5 0 5 0 2 13 3 9 3 9 1 40 19 6 4 5 3 1 67 6 0 5 1 1 82 5 6 4 9 2 00 5 4 4 9 2 22 4 2 4 2 1 46 22 7 0 4 3 1 74 6 5 4 1 1 89 6 1 3 9 2 08 5 9 3 9 2 31 4 6 3 4 1 52 32 16 5 9 5 9 1 61 5 6 5 6 1 74...

Страница 427: ...35 14 2 8 1 3 60 13 7 7 8 3 83 12 7 7 6 3 98 9 3 6 2 3 25 29 16 12 4 12 4 3 11 12 4 12 4 3 34 11 9 11 9 3 56 11 0 11 0 3 70 8 1 8 1 3 02 19 13 2 12 4 3 25 13 2 12 4 3 49 12 7 12 1 3 71 11 8 11 8 3 86 8 6 8 6 3 15 22 14 5 10 0 3 36 14 5 10 0 3 61 13 9 9 7 3 84 12 9 9 4 3 99 9 5 8 1 3 26 32 16 12 5 12 5 3 12 12 5 12 5 3 35 12 1 12 1 3 56 11 2 11 2 3 71 8 2 8 2 3 03 19 13 4 12 6 3 25 13 4 12 6 3 50 1...

Страница 428: ...48 12 5 10 1 3 70 11 6 9 9 3 85 8 5 8 5 3 15 22 14 2 8 0 3 35 14 2 8 0 3 60 13 7 7 8 3 83 12 7 7 5 3 98 9 3 6 2 3 25 29 16 12 4 12 4 3 11 12 4 12 4 3 34 11 9 11 9 3 56 11 0 11 0 3 70 8 1 8 1 3 02 19 13 2 12 2 3 25 13 2 12 2 3 49 12 7 11 8 3 71 11 8 11 8 3 86 8 6 8 6 3 15 22 14 5 9 8 3 36 14 5 9 8 3 61 13 9 9 5 3 84 12 9 9 2 3 99 9 5 7 9 3 26 32 16 12 5 12 5 3 12 12 5 12 5 3 35 12 1 12 1 3 56 11 2 ...

Страница 429: ... 9 9 9 9 4 89 19 16 1 13 4 5 25 16 1 13 4 5 64 15 5 13 0 6 00 14 4 12 8 6 24 10 5 10 5 5 10 22 17 7 10 3 5 43 17 7 10 2 5 83 17 0 9 9 6 21 15 8 9 6 6 46 11 5 8 0 5 28 29 16 15 3 15 3 5 05 15 3 15 3 5 42 14 7 14 7 5 77 13 7 13 7 6 00 10 0 10 0 4 90 19 16 4 15 7 5 26 16 4 15 8 5 65 15 7 15 3 6 01 14 6 14 6 6 26 10 7 10 7 5 11 22 17 9 12 5 5 44 17 9 12 6 5 85 17 2 12 2 6 22 16 0 11 9 6 47 11 7 10 2 5...

Страница 430: ...2 2 22 5 0 5 0 2 46 3 9 3 9 1 62 19 6 4 4 6 1 93 6 0 4 4 2 10 5 6 4 2 2 31 5 4 4 1 2 56 4 2 3 7 1 68 22 7 0 3 6 2 01 6 5 3 4 2 18 6 1 3 2 2 40 5 9 3 2 2 67 4 6 2 7 1 75 29 16 5 9 5 9 1 85 5 6 5 6 2 01 5 2 5 2 2 22 5 0 5 0 2 46 3 9 3 9 1 62 19 6 4 5 1 1 93 6 0 5 0 2 10 5 6 4 8 2 31 5 4 4 7 2 56 4 2 4 2 1 68 22 7 0 4 2 2 01 6 5 4 0 2 18 6 1 3 8 2 40 5 9 3 8 2 67 4 6 3 3 1 75 32 16 5 9 5 9 1 85 5 6 5...

Страница 431: ...2 8 1 3 44 14 2 8 1 3 70 13 7 7 8 3 93 12 7 7 5 4 09 9 3 6 2 3 34 29 16 12 4 12 4 3 20 12 4 12 4 3 43 11 9 11 9 3 65 11 0 11 0 3 80 8 1 8 1 3 10 19 13 2 12 2 3 33 13 2 12 2 3 58 12 7 11 8 3 81 11 8 11 7 3 96 8 6 8 6 3 24 22 14 5 9 8 3 45 14 5 9 8 3 70 13 9 9 5 3 94 12 9 9 2 4 10 9 5 7 9 3 35 32 16 12 5 12 5 3 20 12 5 12 5 3 44 12 1 12 1 3 66 11 2 11 2 3 81 8 2 8 2 3 11 19 13 4 12 3 3 34 13 4 12 3 ...

Страница 432: ...0 2 3 57 12 5 9 9 3 80 11 6 9 7 3 95 8 5 8 4 3 23 22 14 2 7 8 3 44 14 2 7 8 3 70 13 7 7 7 3 93 12 7 7 4 4 09 9 3 6 1 3 34 29 16 12 4 12 4 3 20 12 4 12 4 3 43 11 9 11 9 3 65 11 0 11 0 3 80 8 1 8 1 3 10 19 13 2 11 9 3 33 13 2 11 9 3 58 12 7 11 7 3 81 11 8 11 5 3 96 8 6 8 6 3 24 22 14 5 9 6 3 45 14 5 9 6 3 70 13 9 9 4 3 94 12 9 9 1 4 10 9 5 7 7 3 35 32 16 12 5 12 5 3 20 12 5 12 5 3 44 12 1 12 1 3 66 ...

Страница 433: ...3 5 6 18 9 9 9 9 5 05 19 16 1 13 1 5 43 16 1 13 2 5 83 15 5 12 7 6 20 14 4 12 6 6 45 10 5 10 5 5 27 22 17 7 10 0 5 61 17 7 10 1 6 03 17 0 9 7 6 41 15 8 9 5 6 67 11 5 7 8 5 45 29 16 15 3 15 3 5 21 15 3 15 3 5 60 14 7 14 7 5 96 13 7 13 7 6 20 10 0 10 0 5 06 19 16 4 15 4 5 44 16 4 15 5 5 84 15 7 14 9 6 22 14 6 14 6 6 46 10 7 10 7 5 28 22 17 9 12 3 5 63 17 9 12 4 6 04 17 2 11 9 6 43 16 0 11 7 6 69 11 ...

Страница 434: ...5 0 4 6 2 61 3 9 3 9 1 71 19 6 4 4 2 2 05 6 0 4 0 2 23 5 6 3 8 2 45 5 4 3 8 2 72 4 2 3 3 1 79 22 7 0 3 4 2 13 6 5 3 2 2 31 6 1 3 1 2 55 5 9 3 0 2 83 4 6 2 5 1 86 29 16 5 9 5 5 1 97 5 6 5 4 2 14 5 2 5 2 2 35 5 0 5 0 2 61 3 9 3 9 1 71 19 6 4 4 7 2 05 6 0 4 5 2 23 5 6 4 3 2 45 5 4 4 3 2 72 4 2 3 7 1 79 22 7 0 3 9 2 13 6 5 3 7 2 31 6 1 3 5 2 55 5 9 3 5 2 83 4 6 3 0 1 86 32 16 5 9 5 5 1 97 5 6 5 4 2 14...

Страница 435: ... 48 12 5 9 0 3 70 11 6 8 8 3 85 8 5 7 4 3 15 22 14 2 7 4 3 35 14 2 7 4 3 60 13 7 7 2 3 83 12 7 6 8 3 98 9 3 5 5 3 25 29 16 12 4 12 4 3 11 12 4 12 4 3 34 11 9 11 9 3 56 11 0 11 0 3 70 8 1 8 1 3 02 19 13 2 10 6 3 25 13 2 10 6 3 49 12 7 10 3 3 71 11 8 10 1 3 86 8 6 8 6 3 15 22 14 5 8 8 3 36 14 5 8 8 3 61 13 9 8 5 3 84 12 9 8 1 3 99 9 5 6 9 3 26 32 16 12 5 12 5 3 12 12 5 12 5 3 35 12 1 12 1 3 56 11 2 ...

Страница 436: ...3 5 5 98 9 9 9 9 4 89 19 16 1 11 8 5 25 16 1 11 8 5 64 15 5 11 4 6 00 14 4 11 2 6 24 10 5 9 4 5 10 22 17 7 9 3 5 43 17 7 9 4 5 83 17 0 9 0 6 21 15 8 8 7 6 46 11 5 7 0 5 28 29 16 15 3 15 3 5 05 15 3 15 3 5 42 14 7 14 7 5 77 13 7 13 7 6 00 10 0 10 0 4 90 19 16 4 13 6 5 26 16 4 13 6 5 65 15 7 13 2 6 01 14 6 13 0 6 26 10 7 10 7 5 11 22 17 9 11 1 5 44 17 9 11 2 5 85 17 2 10 8 6 22 16 0 10 5 6 47 11 7 8...

Страница 437: ...6 5 4 2 60 6 5 4 7 2 29 5 9 4 3 2 08 S 71PU1E5A U 71PEY1E5 220V 230V 240V 50Hz 1 phase 23 16 7 9 6 0 2 26 7 5 5 8 2 47 7 2 5 7 2 69 6 1 5 0 2 36 5 5 4 6 2 15 19 8 5 4 6 2 35 8 1 4 4 2 58 7 7 4 2 2 80 6 5 3 7 2 46 5 9 3 4 2 24 22 9 2 3 1 2 45 8 8 3 0 2 68 8 4 2 8 2 91 7 1 2 4 2 56 6 4 2 1 2 33 25 16 7 9 7 0 2 26 7 5 6 8 2 47 7 2 6 6 2 69 6 1 5 7 2 36 5 5 5 3 2 15 19 8 5 5 6 2 35 8 1 5 3 2 58 7 7 5 ...

Страница 438: ...4 55 7 7 7 7 3 14 19 14 3 10 5 4 33 13 9 10 3 4 66 13 5 10 0 5 00 10 9 8 5 4 75 8 2 6 9 3 27 22 15 7 8 3 4 48 15 3 8 2 4 83 14 8 7 9 5 17 11 9 6 6 4 92 9 0 5 3 3 39 29 16 13 6 13 6 4 16 13 2 13 2 4 48 12 8 12 8 4 81 10 3 10 3 4 57 7 8 7 8 3 15 19 14 5 12 2 4 34 14 1 11 9 4 68 13 7 11 6 5 01 11 1 9 9 4 76 8 3 7 9 3 28 22 15 9 10 0 4 49 15 5 9 8 4 84 15 0 9 5 5 19 12 1 8 0 4 93 9 1 6 5 3 40 32 16 13...

Страница 439: ...E8 220V 230V 240V 50Hz 1phase 3phase 23 16 12 5 10 1 4 02 12 2 9 9 4 33 11 8 9 6 4 64 9 5 8 1 4 41 7 2 6 7 3 04 19 13 4 7 5 4 19 13 0 7 4 4 51 12 6 7 2 4 84 10 2 6 0 4 60 7 7 4 8 3 17 22 14 7 4 9 4 33 14 3 4 8 4 67 13 8 4 6 5 00 11 1 3 7 4 75 8 4 2 8 3 28 25 16 13 0 12 2 4 08 12 6 11 8 4 40 12 2 11 5 4 72 9 9 9 9 4 48 7 4 7 4 3 09 19 13 8 9 5 4 26 13 5 9 2 4 59 13 1 9 0 4 92 10 5 7 5 4 67 8 0 6 2 ...

Страница 440: ...84 22 13 9 7 4 3 89 13 3 7 1 4 19 12 6 6 7 4 49 10 7 5 9 4 27 7 7 4 8 2 94 29 16 12 1 11 5 3 61 11 5 10 9 3 89 10 9 10 3 4 17 9 3 8 8 3 96 6 7 6 4 2 73 19 12 9 11 0 3 77 12 3 10 5 4 06 11 7 10 1 4 35 9 9 9 1 4 13 7 1 6 7 2 85 22 14 1 8 9 3 90 13 5 8 5 4 20 12 8 8 2 4 50 10 9 7 3 4 28 7 8 6 0 2 95 32 16 12 3 11 7 3 62 11 7 11 1 3 90 11 1 10 5 4 18 9 4 8 9 3 97 6 8 6 4 2 74 19 13 1 11 2 3 78 12 5 10...

Страница 441: ... 125PEY1E8 220V 230V 240V 50Hz 1phase 3phase 23 16 12 5 9 7 4 14 12 2 9 5 4 46 11 8 9 2 4 79 9 5 7 8 4 55 7 2 6 8 3 13 19 13 4 7 4 4 32 13 0 7 2 4 66 12 6 7 0 4 99 10 2 5 8 4 74 7 7 4 8 3 27 22 14 7 5 1 4 47 14 3 4 9 4 82 13 8 4 8 5 16 11 1 3 8 4 91 8 4 2 9 3 38 25 16 13 0 11 6 4 21 12 6 11 3 4 54 12 2 11 0 4 87 9 9 9 4 4 62 7 4 7 4 3 19 19 13 8 9 1 4 40 13 5 9 0 4 74 13 1 8 8 5 08 10 5 7 3 4 82 8...

Страница 442: ... 2 31 19 8 5 6 1 2 52 8 1 5 9 2 76 7 7 5 6 3 00 6 5 4 9 2 64 5 9 4 6 2 40 22 9 2 4 8 2 62 8 8 4 6 2 87 8 4 4 4 3 12 7 1 3 9 2 74 6 4 3 6 2 50 29 16 7 9 7 9 2 42 7 5 7 5 2 65 7 2 7 2 2 88 6 1 6 1 2 53 5 5 5 5 2 31 19 8 5 6 9 2 52 8 1 6 7 2 76 7 7 6 4 3 00 6 5 5 5 2 64 5 9 5 2 2 40 22 9 2 5 6 2 62 8 8 5 4 2 87 8 4 5 2 3 12 7 1 4 5 2 74 6 4 4 2 2 50 32 16 7 9 7 9 2 42 7 5 7 5 2 65 7 2 7 2 2 88 6 1 6 ...

Страница 443: ... 6 5 2 65 19 12 5 10 8 3 65 11 9 10 3 3 94 11 3 9 8 4 22 9 6 8 9 4 01 6 9 6 6 2 76 22 13 7 8 8 3 78 13 1 8 4 4 07 12 4 8 0 4 37 10 5 7 1 4 15 7 6 5 5 2 86 S 60PK1E5A 2 U 125PEY1E5 U 125PEY1E8 220V 230V 240V 50Hz 1phase 3phase 23 16 12 2 9 4 4 02 11 9 9 3 4 33 11 5 9 0 4 64 9 3 7 6 4 41 7 0 6 2 3 04 19 13 1 7 2 4 19 12 7 7 0 4 51 12 3 6 8 4 84 9 9 5 6 4 60 7 5 4 5 3 17 22 14 3 5 0 4 33 13 9 4 8 4 6...

Страница 444: ... 5 2 96 6 5 4 8 2 61 5 9 4 4 2 38 S 71PF1E5A U 71PEY1E5 220V 230V 240V 50Hz 1phase 23 16 7 9 5 9 2 64 7 5 5 7 2 89 7 2 5 5 3 14 6 1 4 8 2 76 5 5 4 4 2 52 19 8 5 4 5 2 75 8 1 4 3 3 01 7 7 4 1 3 27 6 5 3 5 2 88 5 9 3 3 2 62 22 9 2 3 1 2 86 8 8 2 9 3 13 8 4 2 7 3 40 7 1 2 4 2 99 6 4 2 1 2 73 25 16 7 9 6 8 2 64 7 5 6 5 2 89 7 2 6 3 3 14 6 1 5 5 2 76 5 5 5 1 2 52 19 8 5 5 3 2 75 8 1 5 2 3 01 7 7 5 0 3 ...

Страница 445: ...5 7 7 7 7 3 14 19 14 3 10 6 4 33 13 9 10 3 4 66 13 5 10 2 5 00 10 9 8 6 4 75 8 2 7 0 3 27 22 15 7 8 3 4 48 15 3 8 2 4 83 14 8 7 9 5 17 11 9 6 6 4 92 9 0 5 3 3 39 29 16 13 6 13 6 4 16 13 2 13 2 4 48 12 8 12 8 4 81 10 3 10 3 4 57 7 8 7 8 3 15 19 14 5 12 2 4 34 14 1 12 0 4 68 13 7 11 7 5 01 11 1 10 0 4 76 8 3 7 9 3 28 22 15 9 10 0 4 49 15 5 9 8 4 84 15 0 9 5 5 19 12 1 8 0 4 93 9 1 6 5 3 40 32 16 13 8...

Страница 446: ...20V 230V 240V 50Hz 1phase 3phase 23 16 12 5 10 4 4 02 12 2 10 1 4 33 11 8 9 8 4 64 9 5 8 4 4 41 7 2 6 8 3 04 19 13 4 7 6 4 19 13 0 7 4 4 51 12 6 7 2 4 84 10 2 6 0 4 60 7 7 4 9 3 17 22 14 7 4 9 4 33 14 3 4 7 4 67 13 8 4 6 5 00 11 1 3 7 4 75 8 4 2 8 3 28 25 16 13 0 12 5 4 08 12 6 12 1 4 40 12 2 11 8 4 72 9 9 9 9 4 48 7 4 7 4 3 09 19 13 8 9 6 4 26 13 5 9 4 4 59 13 1 9 1 4 92 10 5 7 7 4 67 8 0 6 4 3 2...

Страница 447: ...1 7 6 5 5 3 06 6 5 4 9 2 69 5 9 4 5 2 45 S 71PN1E5A U 71PEY1E5 220V 230V 240V 50Hz 1phase 23 16 7 9 6 1 2 60 7 5 5 9 2 85 7 2 5 7 3 10 6 1 5 0 2 73 5 5 4 6 2 49 19 8 5 4 6 2 71 8 1 4 4 2 97 7 7 4 2 3 23 6 5 3 7 2 84 5 9 3 4 2 59 22 9 2 3 1 2 82 8 8 3 0 3 09 8 4 2 8 3 36 7 1 2 4 2 95 6 4 2 1 2 69 25 16 7 9 7 0 2 60 7 5 6 8 2 85 7 2 6 7 3 10 6 1 5 7 2 73 5 5 5 3 2 49 19 8 5 5 6 2 71 8 1 5 3 2 97 7 7...

Страница 448: ... 2 4 74 7 7 7 7 3 26 19 14 3 10 8 4 50 13 9 10 5 4 85 13 5 10 3 5 20 10 9 8 7 4 94 8 2 7 1 3 41 22 15 7 8 6 4 66 15 3 8 3 5 02 14 8 8 1 5 38 11 9 6 7 5 11 9 0 5 4 3 52 29 16 13 6 13 6 4 33 13 2 13 2 4 66 12 8 12 8 5 00 10 3 10 3 4 75 7 8 7 8 3 27 19 14 5 12 5 4 51 14 1 12 1 4 86 13 7 11 9 5 21 11 1 10 2 4 95 8 3 8 0 3 41 22 15 9 10 2 4 67 15 5 9 9 5 03 15 0 9 7 5 39 12 1 8 1 5 12 9 1 6 6 3 53 32 1...

Страница 449: ...EY1E8 220V 230V 240V 50Hz 1phase 3phase 23 16 12 5 10 3 4 18 12 2 10 1 4 50 11 8 9 8 4 82 9 5 8 4 4 58 7 2 6 8 3 16 19 13 4 7 5 4 36 13 0 7 4 4 69 12 6 7 2 5 03 10 2 6 0 4 78 7 7 4 8 3 29 22 14 7 4 8 4 51 14 3 4 7 4 86 13 8 4 5 5 20 11 1 3 6 4 95 8 4 2 8 3 41 25 16 13 0 12 5 4 25 12 6 12 2 4 57 12 2 11 9 4 90 9 9 9 9 4 66 7 4 7 4 3 21 19 13 8 9 6 4 43 13 5 9 4 4 77 13 1 9 2 5 12 10 5 7 7 4 86 8 0 ...

Страница 450: ...Y2E5A 2 U 100PEY1E5 U 100PEY1E8 220V 230V 240V 50Hz 1phase 3phase 23 16 10 6 7 7 3 44 10 1 7 3 3 70 9 6 7 0 3 97 8 2 6 3 3 77 5 9 4 8 2 60 19 11 4 6 0 3 59 10 8 5 7 3 86 10 3 5 5 4 14 8 7 4 7 3 93 6 3 3 6 2 71 22 12 4 4 3 3 71 11 9 4 1 4 00 11 3 3 9 4 28 9 6 3 2 4 07 6 9 2 3 2 81 25 16 11 0 9 1 3 49 10 5 8 7 3 77 10 0 8 3 4 04 8 5 7 4 3 84 6 1 5 7 2 64 19 11 8 7 3 3 65 11 2 6 9 3 93 10 6 6 6 4 21 ...

Страница 451: ...3 phase 16 8 2 2 88 8 5 2 90 9 7 2 86 9 9 2 67 9 9 2 47 20 7 8 2 96 8 1 2 98 9 0 2 90 9 0 2 72 9 0 2 49 24 7 4 3 05 7 7 3 07 8 1 2 96 8 1 2 78 8 1 2 55 S 100PU1E5A U 100PE1E5A U 100PE1E8A 220V 230V 240V 50Hz 1 phase 3 phase 16 15 1 4 97 15 1 4 77 15 1 4 16 15 1 3 66 15 1 3 10 20 14 0 5 26 14 0 5 05 14 0 4 40 14 0 3 87 14 0 3 28 24 13 1 5 34 13 1 5 13 13 1 4 47 13 1 3 94 13 1 3 33 S 125PU1E5A U 125...

Страница 452: ... 230V 240V 50Hz 1 phase 3 phase 16 16 7 5 52 17 2 5 43 17 3 4 91 17 3 4 33 17 3 3 66 20 15 5 5 84 15 9 5 74 16 0 5 20 16 0 4 58 16 0 3 87 24 14 5 5 93 14 9 5 84 15 0 5 28 15 0 4 65 15 0 3 94 S 45PU1E5A 3 U 125PE1E5A U 125PE1E8A 220V 230V 240V 50Hz 1 phase 3 phase 16 16 7 5 52 17 2 5 43 17 3 4 91 17 3 4 33 17 3 3 66 20 15 5 5 84 15 9 5 74 16 0 5 20 16 0 4 58 16 0 3 87 24 14 5 5 93 14 9 5 84 15 0 5 ...

Страница 453: ...hase 16 8 2 2 88 8 5 2 90 9 7 2 86 9 9 2 67 9 9 2 47 20 7 8 2 96 8 1 2 98 9 0 2 90 9 0 2 72 9 0 2 49 24 7 4 3 05 7 7 3 07 8 1 2 96 8 1 2 78 8 1 2 55 S 100PT2E5A U 100PE1E5A U 100PE1E8A 220V 230V 240V 50Hz 1phase 3 phase 16 15 1 4 97 15 1 4 77 15 1 4 16 15 1 3 66 15 1 3 10 20 14 0 5 26 14 0 5 05 14 0 4 40 14 0 3 87 14 0 3 28 24 13 1 5 34 13 1 5 13 13 1 4 47 13 1 3 94 13 1 3 33 S 125PT2E5A U 125PE1E...

Страница 454: ...30V 240V 50Hz 1phase 3 phase 16 16 7 5 53 17 2 5 44 17 3 4 92 17 3 4 34 17 3 3 67 20 15 5 5 85 15 9 5 75 16 0 5 21 16 0 4 59 16 0 3 88 24 14 5 5 94 14 9 5 85 15 0 5 29 15 0 4 66 15 0 3 94 S 45PT2E5A 3 U 125PE1E5A U 125PE1E8A 220V 230V 240V 50Hz 1phase 3 phase 16 16 7 5 53 17 2 5 44 17 3 4 92 17 3 4 34 17 3 3 67 20 15 5 5 85 15 9 5 75 16 0 5 21 16 0 4 59 16 0 3 88 24 14 5 5 94 14 9 5 85 15 0 5 29 1...

Страница 455: ...V 230V 240V 50Hz 1 phase 16 7 3 2 43 7 5 2 45 8 6 2 44 8 8 2 32 8 8 2 17 20 7 0 2 51 7 2 2 52 8 0 2 48 8 0 2 36 8 0 2 21 24 6 6 2 58 6 8 2 60 7 2 2 52 7 2 2 40 7 2 2 25 S 71PK1E5A U 71PE1E5A U 71PE1E8A 220V 230V 240V 50Hz 1 phase 3 phase 16 8 2 2 88 8 5 2 90 9 7 2 86 9 9 2 67 9 9 2 47 20 7 8 2 96 8 1 2 98 9 0 2 90 9 0 2 72 9 0 2 49 24 7 4 3 05 7 7 3 07 8 1 2 96 8 1 2 78 8 1 2 55 S 100PK1E5A U 100P...

Страница 456: ...230V 240V 50Hz 1 phase 3 phase 16 16 7 5 52 17 2 5 43 17 3 4 91 17 3 4 33 17 3 3 66 20 15 5 5 84 15 9 5 74 16 0 5 20 16 0 4 58 16 0 3 87 24 14 5 5 93 14 9 5 84 15 0 5 28 15 0 4 65 15 0 3 94 S 45PK1E5A 3 U 125PE1E5A U 125PE1E8A 220V 230V 240V 50Hz 1 phase 3 phase 16 16 7 5 52 17 2 5 43 17 3 4 91 17 3 4 33 17 3 3 66 20 15 5 5 84 15 9 5 74 16 0 5 20 16 0 4 58 16 0 3 87 24 14 5 5 93 14 9 5 84 15 0 5 2...

Страница 457: ...se 3 phase 16 8 2 2 88 8 5 2 90 9 7 2 86 9 9 2 67 9 9 2 47 20 7 8 2 96 8 1 2 98 9 0 2 90 9 0 2 72 9 0 2 49 24 7 4 3 05 7 7 3 07 8 1 2 96 8 1 2 78 8 1 2 55 S 100PF1E5A U 100PE1E5A U 100PE1E8A 220V 230V 240V 50Hz 1 phase 3 phase 16 15 1 4 97 15 1 4 77 15 1 4 16 15 1 3 66 15 1 3 10 20 14 0 5 26 14 0 5 05 14 0 4 40 14 0 3 87 14 0 3 28 24 13 1 5 34 13 1 5 13 13 1 4 47 13 1 3 94 13 1 3 33 S 125PF1E5A U ...

Страница 458: ...220V 230V 240V 50Hz 1 phase 3 phase 16 16 7 5 52 17 2 5 43 17 3 4 91 17 3 4 33 17 3 3 66 20 15 5 5 84 15 9 5 74 16 0 5 20 16 0 4 58 16 0 3 87 24 14 5 5 93 14 9 5 84 15 0 5 28 15 0 4 65 15 0 3 94 S 45PF1E5A 3 U 125PE1E5A U 125PE1E8A 220V 230V 240V 50Hz 1 phase 3 phase 16 16 7 5 52 17 2 5 43 17 3 4 91 17 3 4 33 17 3 3 66 20 15 5 5 84 15 9 5 74 16 0 5 20 16 0 4 58 16 0 3 87 24 14 5 5 93 14 9 5 84 15 ...

Страница 459: ...ase 16 8 2 2 90 8 5 2 92 9 7 2 88 9 9 2 69 9 9 2 48 20 7 8 2 98 8 1 3 00 9 0 2 92 9 0 2 74 9 0 2 51 24 7 4 3 07 7 7 3 09 8 1 2 98 8 1 2 79 8 1 2 57 S 100PN1E5A U 100PE1E5A U 100PE1E8A 220V 230V 240V 50Hz 1 phase 3 phase 16 15 1 5 08 15 1 4 88 15 1 4 25 15 1 3 74 15 1 3 17 20 14 0 5 38 14 0 5 17 14 0 4 50 14 0 3 96 14 0 3 35 24 13 1 5 46 13 1 5 25 13 1 4 57 13 1 4 03 13 1 3 41 S 125PN1E5A U 125PE1E...

Страница 460: ...V 240V 50Hz 1 phase 3 phase 16 16 7 5 73 17 2 5 64 17 3 5 10 17 3 4 49 17 3 3 80 20 15 5 6 06 15 9 5 96 16 0 5 40 16 0 4 75 16 0 4 02 24 14 5 6 16 14 9 6 06 15 0 5 49 15 0 4 83 15 0 4 09 S 45PN1E5A 3 U 125PE1E5A U 125PE1E8A 220V 230V 240V 50Hz 1 phase 3 phase 16 16 7 5 73 17 2 5 64 17 3 5 10 17 3 4 49 17 3 3 80 20 15 5 6 06 15 9 5 96 16 0 5 40 16 0 4 75 16 0 4 02 24 14 5 6 16 14 9 6 06 15 0 5 49 1...

Страница 461: ... C W B Model Power Source Ambient Return Air 5 C 0 C 6 C 10 C 15 C DB TC IPT TC IPT TC IPT TC IPT TC IPT S 50PY2E5A U 50PE1E5 220V 230V 240V 50Hz 1 phase 16 4 4 2 00 4 7 2 06 6 5 2 44 8 0 2 92 8 5 2 80 20 4 3 2 11 4 6 2 17 6 3 2 57 7 8 3 08 8 3 2 95 24 4 1 2 17 4 4 2 23 6 0 2 65 7 5 3 17 7 9 3 04 SM830231 02 Single 欧州 indb 451 SM830231 02 Single 欧州 indb 451 2014 09 19 13 22 24 2014 09 19 13 22 24 ...

Страница 462: ...20V 230V 240V 50Hz 1 phase 3 phase 16 15 1 4 97 15 1 4 77 15 1 4 16 15 1 3 66 15 1 3 10 20 14 0 5 26 14 0 5 05 14 0 4 40 14 0 3 87 14 0 3 28 24 13 1 5 34 13 1 5 13 13 1 4 47 13 1 3 94 13 1 3 33 S 36PY2E5A 4 U 125PE1E5 U 125PE1E8 220V 230V 240V 50Hz 1 phase 3 phase 16 16 7 5 52 17 2 5 43 17 3 4 91 17 3 4 33 17 3 3 66 20 15 5 5 84 15 9 5 74 16 0 5 20 16 0 4 58 16 0 3 87 24 14 5 5 93 14 9 5 84 15 0 5...

Страница 463: ...10 2 2 95 24 5 2 2 11 5 7 2 21 7 8 2 59 8 7 2 81 9 8 3 03 S 100PU1E5A U 100PEY1E5 U 100PEY1E8 220V 230V 240V 50Hz 1 phase 3 phase 16 13 4 4 37 13 9 3 95 14 9 3 78 13 9 2 87 15 6 3 00 20 12 4 4 63 12 9 4 19 13 8 4 00 12 9 3 03 14 5 3 18 24 11 6 4 70 12 1 4 25 12 9 4 06 12 0 3 08 13 5 3 23 S 125PU1E5A U 125PEY1E5 U 125PEY1E8 220V 230V 240V 50Hz 1 phase 3 phase 16 14 5 4 81 15 2 4 35 16 2 4 16 15 1 3...

Страница 464: ...0V 230V 240V 50Hz 1 phase 3 phase 16 13 4 4 37 13 9 3 95 14 9 3 78 13 9 2 87 15 6 3 00 20 12 4 4 63 12 9 4 19 13 8 4 00 12 9 3 03 14 5 3 18 24 11 6 4 70 12 1 4 25 12 9 4 06 12 0 3 08 13 5 3 23 S 60PU1E5A 2 U 125PEY1E5 U 125PEY1E8 220V 230V 240V 50Hz 1 phase 3 phase 16 14 5 4 81 15 2 4 35 16 2 4 16 15 1 3 15 17 0 3 30 20 13 5 5 09 14 0 4 60 15 0 4 40 14 0 3 34 15 7 3 50 24 12 6 5 17 13 1 4 68 14 0 ...

Страница 465: ... 2 95 24 5 2 2 11 5 7 2 21 7 8 2 59 8 7 2 81 9 8 3 03 S 100PT2E5A U 100PEY1E5 U 100PEY1E8 220V 230V 240V 50Hz 1phase 3 phase 16 13 4 4 37 13 9 3 95 14 9 3 78 13 9 2 87 15 6 3 00 20 12 4 4 63 12 9 4 19 13 8 4 00 12 9 3 03 14 5 3 18 24 11 6 4 70 12 1 4 25 12 9 4 06 12 0 3 08 13 5 3 23 S 125PT2E5A U 125PEY1E5 U 125PEY1E8 220V 230V 240V 50Hz 1phase 3 phase 16 14 5 4 81 15 2 4 35 16 2 4 16 15 1 3 15 17...

Страница 466: ...230V 240V 50Hz 1phase 3 phase 16 13 4 4 37 13 9 3 95 14 9 3 78 13 9 2 87 15 6 3 00 20 12 4 4 63 12 9 4 19 13 8 4 00 12 9 3 03 14 5 3 18 24 11 6 4 70 12 1 4 25 12 9 4 06 12 0 3 08 13 5 3 23 S 60PT2E5A 2 U 125PEY1E5 U 125PEY1E8 220V 230V 240V 50Hz 1phase 3 phase 16 14 5 4 81 15 2 4 35 16 2 4 16 15 1 3 15 17 0 3 30 20 13 5 5 09 14 0 4 60 15 0 4 40 14 0 3 34 15 7 3 50 24 12 6 5 17 13 1 4 68 14 0 4 47 ...

Страница 467: ... 5 7 2 07 7 0 2 20 8 1 2 46 9 2 2 68 24 5 2 2 09 5 5 2 13 6 7 2 27 7 8 2 53 8 8 2 76 S 71PK1E5A U 71PEY1E5 220V 230V 240V 50Hz 1 phase 16 5 6 1 98 6 1 2 07 8 3 2 42 9 4 2 63 10 6 2 84 20 5 5 2 08 6 0 2 18 8 1 2 55 9 1 2 77 10 2 2 99 24 5 2 2 14 5 7 2 24 7 8 2 63 8 7 2 85 9 8 3 08 S 100PK1E5A U 100PEY1E5 U 100PEY1E8 220V 230V 240V 50Hz 1 phase 3 phase 16 10 2 3 28 10 6 2 97 11 3 2 83 10 6 2 15 11 9...

Страница 468: ...V 230V 240V 50Hz 1 phase 3 phase 16 12 0 4 37 12 5 3 95 13 4 3 78 12 5 2 87 14 0 3 00 20 11 1 4 63 11 6 4 19 12 4 4 00 11 6 3 03 13 0 3 18 24 10 4 4 70 10 9 4 25 11 6 4 06 10 8 3 08 12 2 3 23 S 60PK1E5A 2 U 125PEY1E5 U 125PEY1E8 220V 230V 240V 50Hz 1 phase 3 phase 16 14 5 5 25 15 2 4 75 16 2 4 54 15 1 3 44 17 0 3 60 20 13 5 5 55 14 0 5 02 15 0 4 80 14 0 3 64 15 7 3 81 24 12 6 5 64 13 1 5 10 14 0 4...

Страница 469: ...59 10 2 2 79 24 5 2 2 00 5 7 2 09 7 8 2 45 8 7 2 66 9 8 2 88 S 100PF1E5A U 100PEY1E5 U 100PEY1E8 220V 230V 240V 50Hz 1 phase 3 phase 16 13 4 4 37 13 9 3 95 14 9 3 78 13 9 2 87 15 6 3 00 20 12 4 4 63 12 9 4 19 13 8 4 00 12 9 3 03 14 5 3 18 24 11 6 4 70 12 1 4 25 12 9 4 06 12 0 3 08 13 5 3 23 S 125PF1E5A U 125PEY1E5 U 125PEY1E8 220V 230V 240V 50Hz 1 phase 3 phase 16 14 5 4 81 15 2 4 35 16 2 4 16 15 ...

Страница 470: ...8 220V 230V 240V 50Hz 1 phase 3 phase 16 13 4 4 37 13 9 3 95 14 9 3 78 13 9 2 87 15 6 3 00 20 12 4 4 63 12 9 4 19 13 8 4 00 12 9 3 03 14 5 3 18 24 11 6 4 70 12 1 4 25 12 9 4 06 12 0 3 08 13 5 3 23 S 60PF1E5A 2 U 125PEY1E5 U 125PEY1E8 220V 230V 240V 50Hz 1 phase 3 phase 16 14 5 4 81 15 2 4 35 16 2 4 16 15 1 3 15 17 0 3 30 20 13 5 5 09 14 0 4 60 15 0 4 40 14 0 3 34 15 7 3 50 24 12 6 5 17 13 1 4 68 1...

Страница 471: ... 3 26 24 5 2 2 34 5 7 2 45 7 8 2 86 8 7 3 11 9 8 3 36 S 100PN1E5A U 100PEY1E5 U 100PEY1E8 220V 230V 240V 50Hz 1 phase 3 phase 16 13 4 4 48 13 9 4 05 14 9 3 87 13 9 2 94 15 6 3 08 20 12 4 4 74 12 9 4 29 13 8 4 10 12 9 3 11 14 5 3 26 24 11 6 4 82 12 1 4 36 12 9 4 17 12 0 3 16 13 5 3 31 S 125PN1E5A U 125PEY1E5 U 125PEY1E8 220V 230V 240V 50Hz 1 phase 3 phase 16 14 5 5 03 15 2 4 55 16 2 4 35 15 1 3 30 ...

Страница 472: ...30V 240V 50Hz 1 phase 3 phase 16 13 4 4 48 13 9 4 05 14 9 3 87 13 9 2 94 15 6 3 08 20 12 4 4 74 12 9 4 29 13 8 4 10 12 9 3 11 14 5 3 26 24 11 6 4 82 12 1 4 36 12 9 4 17 12 0 3 16 13 5 3 31 S 60PN1E5A 2 U 125PEY1E5 U 125PEY1E8 220V 230V 240V 50Hz 1 phase 3 phase 16 14 5 5 03 15 2 4 55 16 2 4 35 15 1 3 30 17 0 3 45 20 13 5 5 32 14 0 4 81 15 0 4 60 14 0 3 49 15 7 3 65 24 12 6 5 41 13 1 4 89 14 0 4 67...

Страница 473: ... U 71PEY1E5 220V 230V 240V 50Hz 1 phase 16 5 6 2 09 6 1 2 19 8 3 2 57 9 4 2 79 10 6 3 01 20 5 5 2 20 6 0 2 31 8 1 2 70 9 1 2 93 10 2 3 17 24 5 2 2 27 5 7 2 37 7 8 2 78 8 7 3 02 9 8 3 26 S 50PY2E5A 2 U 100PEY1E5 U 100PEY1E8 220V 230V 240V 50Hz 1 phase 3 phase 16 12 0 4 68 12 5 4 23 13 4 4 04 12 5 3 07 14 0 3 21 20 11 1 4 95 11 6 4 48 12 4 4 28 11 6 3 25 13 0 3 40 24 10 4 5 03 10 9 4 55 11 6 4 35 10...

Страница 474: ... Heating K SCOP round up to one decimal Heating L Annual Energy Consumption rounded up to the nearest integer Heating M Sound Power level for all indoor units dB cooling N Sound Power level for all outdoor units dB cooling O Sound Power level for all indoor units dB heating P Sound Power level for all outdoor units dB heating Q backup heating capacity X YZ kW R name of refrigerant and GWP R410A GW...

Страница 475: ... one decimal Heating L Annual Energy Consumption rounded up to the nearest integer Heating M Sound Power level for all indoor units dB cooling N Sound Power level for all outdoor units dB cooling O Sound Power level for all indoor units dB heating P Sound Power level for all outdoor units dB heating Q backup heating capacity X YZ kW R name of refrigerant and GWP R410A GWP 1975 S Refrigerant leakag...

Страница 476: ... decimal Heating L Annual Energy Consumption rounded up to the nearest integer Heating M Sound Power level for all indoor units dB cooling N Sound Power level for all outdoor units dB cooling O Sound Power level for all indoor units dB heating P Sound Power level for all outdoor units dB heating Q backup heating capacity X YZ kW R name of refrigerant and GWP R410A GWP 1975 S Refrigerant leakage co...

Страница 477: ...n Load kW round up to one decimal Cooling H SEER round up to one decimal I Annual Energy Consumption rounded Cooling up to the nearest integer J Design Load kW round up to one decimal Heating K SCOP round up to one decimal Heating L Annual Energy Consumption rounded up to the nearest integer Heating M Sound Power level for all indoor units dB cooling N Sound Power level for all outdoor units dB co...

Страница 478: ...n Load kW round up to one decimal Cooling H SEER round up to one decimal I Annual Energy Consumption rounded Cooling up to the nearest integer J Design Load kW round up to one decimal Heating K SCOP round up to one decimal Heating L Annual Energy Consumption rounded up to the nearest integer Heating M Sound Power level for all indoor units dB cooling N Sound Power level for all outdoor units dB co...

Страница 479: ...ad kW round up to one decimal Cooling H SEER round up to one decimal I Annual Energy Consumption rounded Cooling up to the nearest integer J Design Load kW round up to one decimal Heating K SCOP round up to one decimal Heating L Annual Energy Consumption rounded up to the nearest integer Heating M Sound Power level for all indoor units dB cooling N Sound Power level for all outdoor units dB coolin...

Страница 480: ...nd up to one decimal I Annual Energy Consumption rounded Cooling up to the nearest integer J Design Load kW round up to one decimal Heating K SCOP round up to one decimal Heating L Annual Energy Consumption rounded up to the nearest integer Heating M Sound Power level for all indoor units dB cooling N Sound Power level for all outdoor units dB cooling O Sound Power level for all indoor units dB he...

Страница 481: ...onsumption rounded Cooling up to the nearest integer J Design Load kW round up to one decimal Heating K SCOP round up to one decimal Heating L Annual Energy Consumption rounded up to the nearest integer Heating M Sound Power level for all indoor units dB cooling N Sound Power level for all outdoor units dB cooling O Sound Power level for all indoor units dB heating P Sound Power level for all outd...

Страница 482: ...d up to one decimal I Annual Energy Consumption rounded Cooling up to the nearest integer J Design Load kW round up to one decimal Heating K SCOP round up to one decimal Heating L Annual Energy Consumption rounded up to the nearest integer Heating M Sound Power level for all indoor units dB cooling N Sound Power level for all outdoor units dB cooling O Sound Power level for all indoor units dB hea...

Страница 483: ...onsumption rounded Cooling up to the nearest integer J Design Load kW round up to one decimal Heating K SCOP round up to one decimal Heating L Annual Energy Consumption rounded up to the nearest integer Heating M Sound Power level for all indoor units dB cooling N Sound Power level for all outdoor units dB cooling O Sound Power level for all indoor units dB heating P Sound Power level for all outd...

Страница 484: ...Colder optional G Design Load kW round up to one decimal Cooling H SEER round up to one decimal I Annual Energy Consumption rounded Cooling up to the nearest integer J Design Load kW round up to one decimal Heating K SCOP round up to one decimal Heating L Annual Energy Consumption rounded up to the nearest integer Heating M Sound Power level for all indoor units dB cooling N Sound Power level for ...

Страница 485: ...optional G Design Load kW round up to one decimal Cooling H SEER round up to one decimal I Annual Energy Consumption rounded Cooling up to the nearest integer J Design Load kW round up to one decimal Heating K SCOP round up to one decimal Heating L Annual Energy Consumption rounded up to the nearest integer Heating M Sound Power level for all indoor units dB cooling N Sound Power level for all out...

Страница 486: ... MEMO 1 476 SM830231 02 Single 欧州 indb 476 SM830231 02 Single 欧州 indb 476 2014 09 19 13 22 27 2014 09 19 13 22 27 ...

Страница 487: ... REGARDING TEST RUN 2 2 n CHECKS AFTER INSTALLATION HAVE COMPLETED 2 3 n REGARDING DELIVERY TO THE CUSTOMER 2 3 2 TEST RUN SM830231 02 Single 欧州 indb 1 SM830231 02 Single 欧州 indb 1 2014 09 05 11 27 54 2014 09 05 11 27 54 ...

Страница 488: ... value is more than 1 MΩ Use the 500 V mega testers to measure the insulation or 380 415V Do not use the mega tester for any other circuit except for voltage of 220V to 240V Are the wire connections for the indoor outdoor units connected as described in the instructions Are there any looped wires Was the N phase surely connected when connecting the power supply wire on the connection compressor op...

Страница 489: ...ed Is the earth wire securely connected Is the front panel and the indoor unit air conditioner firmly fixed and was the installation completed without any leakage from the refrigerant Are the indoor and outdoor units secured firmly installed with bolts at secured locations REGARDING DELIVERY TO THE CUSTOMER Request the customer to review the instruction manual and explain the operating method for ...

Страница 490: ... MEMO 2 4 SM830231 02 Single 欧州 indb 4 SM830231 02 Single 欧州 indb 4 2014 09 05 11 28 19 2014 09 05 11 28 19 ...

Страница 491: ... 2 4 Way Cassette Type 3 2 4 Way Cassette 60 60 Type 3 3 Ceiling Type 3 4 Wall Mounted Type 3 5 Low Silhouette Ducted Type 3 6 Ducted Type 3 7 3 2 Outdoor Units Electric Wiring Diagram 3 9 SM830231 02 Single 欧州 indb 1 SM830231 02 Single 欧州 indb 1 2014 09 05 16 32 03 2014 09 05 16 32 03 ...

Страница 492: ...y Cassette Type S 36PU1E5A S 45PU1E5A S 50PU1E5A S 60PU1E5A S 71PU1E5A S 100PU1E5A S 125PU1E5A S 140PU1E5A Electric Wiring Diagram SM830231 02 Single 欧州 indb 2 SM830231 02 Single 欧州 indb 2 2014 09 05 16 33 00 2014 09 05 16 33 00 ...

Страница 493: ...CUIT SWITCHING POWER SUPPLY CIRCUIT L N POWER SUPPLY 220 230 240V 50Hz Terminal No are D C signal circuit Do not supply 220 230 240V DP BLU OP1 YEL 1 1 3 3 3 Y G Y Y WIRE COLOR RED YELLOW BLUE PINK GREEN ORANGE WHITE BROWN R Y B P G O W BR BL Y G BLACK YELLOW GREEN M 1 R2 R1 U2 U1 FAN MOTOR M BL BL CAUTION 1 2 WHT CHK 1 2 WHT DISP 1 2 WHT TEST RY001 R W Y B BL INDOOR HEAT EXCHANGER TEMP SENSOR E1 ...

Страница 494: ...L BL BL t t INDOOR HEAT EXCHANGER TEMP SENSOR E2 BL BL t TERMINAL BOARD TERMINAL BOARD NOISE FILTER CIRCUIT RECTIFICATION CIRCUIT CONTROL BOARD MAIN AC IN BL OP1 Y 1 3 1 3 E L BR LT G FUSE F301 T5A L250V 1 2 1 2 1 2 1 2 1 2 1 2 TP6 W TP3 Y TP1 R TEST BL 1 10 TOOL BL DISP BL CHK BL N ELECTRIC CIRCUIT DIAGRAM 3WAY BL DP W FS R 1 2 1 3 1 3 1 5 7 OPTION W 1 6 T10 Y 1 6 PMV W 1 1 6 BL EXCT R FAN DRIVE ...

Страница 495: ...r Units 䡵 Wall Mounted Type S 36PK1E5A S 45PK1E5A S 50PK1E5A S 60PK1E5A S 71PK1E5A S 100PK1E5A Electric Wiring Diagram SM830231 02 Single 欧州 indb 5 SM830231 02 Single 欧州 indb 5 2014 09 05 16 33 01 2014 09 05 16 33 01 ...

Страница 496: ...lhouette Ducted Type S 36PF1E5A S 45PF1E5A S 50PF1E5A S 60PF1E5A S 71PF1E5A S 100PF1E5A S 125PF1E5A S 140PF1E5A Electric Wiring Diagram SM830231 02 Single 欧州 indb 6 SM830231 02 Single 欧州 indb 6 2014 09 05 16 33 01 2014 09 05 16 33 01 ...

Страница 497: ...3 7 3 3 1 Indoor Units Ducted Type S 36PN1E5A S 45PN1E5A S 50PN1E5A Electric Wiring Diagram SM830231 02 Single 欧州 indb 7 SM830231 02 Single 欧州 indb 7 2014 09 05 16 33 01 2014 09 05 16 33 01 ...

Страница 498: ...3 1 Indoor Units Ducted Type S 60PN1E5A S 71PN1E5A S 100PN1E5A S 125PN1E5A S 140PN1E5A Electric Wiring Diagram SM830231 02 Single 欧州 indb 8 SM830231 02 Single 欧州 indb 8 2014 09 05 16 33 01 2014 09 05 16 33 01 ...

Страница 499: ...3 9 3 3 2 Outdoor Units Single phase U 50PE1E5 SM830231 02 Single 欧州 indb 9 SM830231 02 Single 欧州 indb 9 2014 09 05 16 33 02 2014 09 05 16 33 02 ...

Страница 500: ...3 10 3 3 2 Outdoor Units Single phase U 50PE1E5 SM830231 02 Single 欧州 indb 10 SM830231 02 Single 欧州 indb 10 2014 09 05 16 33 02 2014 09 05 16 33 02 ...

Страница 501: ...3 11 3 3 2 Outdoor Units 䡵 Single phase U 60PE1E5A U 71PE1E5A SM830231 02 Single 欧州 indb 11 SM830231 02 Single 欧州 indb 11 2014 09 05 16 33 02 2014 09 05 16 33 02 ...

Страница 502: ...2 Outdoor Units 䡵 Single phase U 100PE1E5A U 125PE1E5A U 140PE1E5A SM830211 05 PAC i indb 11 2012 10 10 0 32 28 SM830231 02 Single 欧州 indb 12 SM830231 02 Single 欧州 indb 12 2014 09 05 16 33 02 2014 09 05 16 33 02 ...

Страница 503: ...3 13 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 SM830231 02 Single 欧州 indb 13 SM830231 02 Single 欧州 indb 13 2014 09 05 16 33 02 2014 09 05 16 33 02 ...

Страница 504: ...3 14 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 SM830231 02 Single 欧州 indb 14 SM830231 02 Single 欧州 indb 14 2014 09 05 16 33 02 2014 09 05 16 33 02 ...

Страница 505: ... B BR G W W W W W W W CN HIC1 W W W W W CN HIC3 W W BL O BL W GR CN RELAY W CN PAM W RE1 R U2 U1 P B BL CN PAM BL RE2 R RE1 R RE2 R R B Y CN TO BL BL BL RECTIFICATION CIRCUIT T3 15A L250V T3 15A L250V M RY900 RY901 DC2 BL TERMINAL BOARD CONTROL BOARD HIC CONTROL BOARD CR W W W W EXPANSION VALVE W W W W W W TERMINAL BOARD FAN MOTOR 1 2 6 1 CN OPT2 Y CN OPT1 R BR R 1 2 1 2 LV1 COM LV3 LV2 B BL P GR ...

Страница 506: ...3 16 3 3 2 Outdoor Units 3 phase U 71PE1E8A SM830231 02 Single 欧州 indb 16 SM830231 02 Single 欧州 indb 16 2014 09 05 16 33 02 2014 09 05 16 33 02 ...

Страница 507: ...3 17 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 SM830231 02 Single 欧州 indb 17 SM830231 02 Single 欧州 indb 17 2014 09 05 16 33 03 2014 09 05 16 33 03 ...

Страница 508: ...3 18 3 3 2 Outdoor Units 3 phase U 100PE1E8A U 125PE1E8A U 140PE1E8A U 140PEY1E8 SM830231 02 Single 欧州 indb 18 SM830231 02 Single 欧州 indb 18 2014 09 05 16 33 03 2014 09 05 16 33 03 ...

Страница 509: ... 4 8 4 7 Filter Sign 4 8 4 8 Fan Control during Dry Mode 4 9 4 9 Ventilation Fan Output 4 9 4 10 T10 Terminal 4 9 4 11 Parameter 4 10 4 12 Control Functions 4 11 4 13 Outdoor Unit Control PCB 4 23 4 14 Functions of Outdoor Unit PCB 4 43 4 15 Self Diagnostics Function Table 4 46 4 CONTROL FUNCTIONS SM830231 02 Single 欧州 indb 1 SM830231 02 Single 欧州 indb 1 2014 09 09 21 15 08 2014 09 09 21 15 08 ...

Страница 510: ...this difference in temperature the correction temperature is used The factory setting for the correction temperature is different depending on the model Refer to 4 11 Parameter Example Cooling temperature correction 4 Way Cassette correction temperature 0 degrees Body sensor is enabled Set temp in remote controller 28 28 28 Detected temp by sensor 30 0 27 5 27 0 Detected temp by body sensor 30 0 2...

Страница 511: ...controller sensor 17 0 17 0 20 5 20 5 21 0 21 0 T 3 0deg 0 5deg 1 0deg Thermostat ON Thermostat OFF Thermostat OFF Ԙ The thermostat does not turn OFF for 3 minutes after it turns ON ԙ The thermostat does not turn ON 1 to 3 minutes after it turns OFF 㽴 The thermostat does not turn OFF for 60 minutes during the test run mode Forced thermostat ON However the thermostat turns OFF if an alarm occurs N ...

Страница 512: ...6 minutes ղ The fan mode increases when the heat exchanger liquid temperature E1 or discharge air temperature increases The fan mode is selected based on the discharge air temperature and E1 temperature as shown in the below figure If the E1 temperature and discharge air temperature are different the higher temperature is used The function of HH is identical to the automatic fan speed mode Operati...

Страница 513: ...ing cooling operation and 1 minute during heating operation once it is changed 㽴 The values in the parenthesis are when the remote controller sensor is enabled 3 2 1 deg Indoor fan mode HH H L HH H Cooling Set temp Set temp 1 2 2 4 deg Indoor fan mode HH H L HH H Heating SM830231 02 Single 欧州 indb 5 SM830231 02 Single 欧州 indb 5 2014 09 09 21 15 22 2014 09 09 21 15 22 ...

Страница 514: ...ned on when the cooling thermostat is OFF if the setting is made to prevent water collected in the drain pan for a long time For details refer to 7 3 Detailed Settings Function Ԝ The indoor unit heat exchanger liquid temperature E1 is less than 0 C when the cooling thermostat is OFF or the indoor unit is stopped The drain pump operates for 20 minutes once it starts operating SM830231 02 Single 欧州 ...

Страница 515: ... 22 C Set temp in remote controller 20 C Control temp for heating 18 C 㽴 Condition for mode change Heating Cooling Room temperature Control temperature for cooling 0 5 degree Cooling Heating Room temperature Control temperature for heating 1 0 degree When setting temperature in remote controller is 20 C in the cooling mode Heating Heating thermostat OFF Cooling Cooling thermostat OFF Heating conti...

Страница 516: ...he filter sign appears on the remote controller Clean the filter Refer to 7 3 Detailed Setting Function Simple setting items and Filter sign ON times for each model After cleaning the filter press the filter button on the remote controller once The filter sign turns off Operating mode Flap position Cooling Dry 1 2 3 Fan 1 1 2 3 4 5 Heating 2 3 4 5 1 2 2 3 3 4 4 5 Fully open 5 1 Fully open Close Cl...

Страница 517: ...or unit turns ON Also when the indoor unit turns OFF the output of the ventilation turns OFF The ventilation fan can also be turned ON and OFF using the ventilation button on the remote controller Refer to the operating instructions supplied with the remote controller To enable this function set the indoor EEPROM DN31 to 0001 in advance 4 10 T10 Terminal Using the T10 terminal each indoor unit can...

Страница 518: ...of factory shipment Setting at time of factory shipment U1 4 Way Cassette 4 deg 2 deg Y2 4 Way Cassette 60 60 4 deg 2 deg T2 Ceiling 4 deg 2 deg K1 Wall Mounted 2 deg 2 deg F1 Low Silhouette Ducted 4 deg 2 deg N1 Ducted 4 deg 2 deg SM830231 02 Single 欧州 indb 10 SM830231 02 Single 欧州 indb 10 2014 09 09 21 15 23 2014 09 09 21 15 23 ...

Страница 519: ...r 1 2 3 Once the thermostat has been switched on it cannot be switched off again by indoor air temperature control for a period of 10 minutes Once the thermostat has been switched off it cannot be switched on again for a period of 3 minutes When in the test run operation mode the thermostat will not be switched off by indoor air temperature control and the operation will continue 4 12 2 Compressor...

Страница 520: ...requency is controlled in accordance with the model and operation mode The maximum and minimum frequencies for each model are shown in the table below There are cases in which frequency is limited with other control functions depending on operational conditions so operations are not always carried out in accordance with the maximum frequencies listed below There is a case in which the frequency is...

Страница 521: ...rmal operations no control b a c d e Control point 50PE 60PEY 71PEY a b c d e 64 61 59 58 53 64 59 58 57 53 64 59 58 57 53 Control point a b c 50PE 65 54 56 52 60PEY 65 54 56 52 71PEY 65 54 56 52 C C max E1 E2 a b c 5 Heating High Load Prevention Control This system control is performed to limit the inverter frequency in order to restrict high pressure s abnormal increase and high load operating p...

Страница 522: ...zone normal operation zone normal operations are performed If the temperature is continuously in the J zone with the compressor s operating frequency reaches 0 then temperature A which is temperature for changing from the J zone to the H zone is raised from 5 C to 8 C and operation continues with the thermostat off until the temperature enters the H zone K operating frequency increase prevention z...

Страница 523: ...ring the heating operation The control is performed to prevent the deterioration of the heating capabilities attributed to the adherence of frost and to prevent the crack or crush of pipes attributed to the accretion of ice The following control is performed in accordance with the ambient temperature and the outdoor heat exchanger temperature sensor C1 Overall Flow Chart of Defrosting Control Norm...

Страница 524: ... circuit Control range of operations 2P and 3P 1P and 3P 0 0 1 0 1 1 No ristricted 0 1 Rated current restricted to A A 100 at factory shipment Rated current restricted to B B 70 at factory shipment Control OFF The operational current is restricted to either A or B as a general indicator during demand input A and B can be amended in calibrations of 5 between 70 and 100 with the outdoor unit s maint...

Страница 525: ... operation The setting can be modified between 0 C and 6 C with mode 06 Simple Settings Function on the remote controller 1 2 3 Once the thermostat has been switched on it cannot be switched off again by indoor air temperature control for a period of 10 minutes Once the thermostat has been switched off it cannot be switched on again for a period of 3 minutes When in the test run operation mode the...

Страница 526: ...verter is controlled in accordance with T and fluctuations in indoor air temperature Inverter frequency is controlled as follows Maximum and Minimum Frequency When T is high not yet reached the temperature set with the remote controller Controlled so that the inverter frequency is increased When T is low approximately 1 0 or less in the cooling mode or approximately 1 0 or more in the heating mode...

Страница 527: ... than normal β 54 α 52 X Setting No EEPROM setting in outdoor unit Outdoor EEPROM Amendment of X values can be made due to 4B Outdoor EEPROM Amendment of X values can be made due to 4B CODE 4B X C 2 52 1 56 5 0 58 5 1 PE type Setting at factory shipment 1 1 PEY type Setting at factory shipment 2 PE type Setting at factory shipment 1 PEY type Setting at factory shipment 2 2 60 C max E2 E1 Outdoor u...

Страница 528: ...arted after 3 minutes If this start stop activity is repeated 5 times the alarm P03 abnormal discharge temperature occurs min E1 E2 Frequency increased Frequency increases prevented Frequency decreased 5 β 2 α Setting No EEPROM setting in outdoor unit CODE 3F for α setting α 15 15 0 0 Setting at factory shipment 9 9 Setting No CODE 40 for β setting β 15 15 0 0 9 9 TD Discharge Temperature Outdoor ...

Страница 529: ...operations commenced No No No Frost adherence detection If the following conditions are satisfied during heating operations it is regarded as frost adherence is detected Frost adherence detection is performed in accordance with the ambient temperature TO and the outdoor heat exchanger temperature sensor C1 Frost adherence detection conditions a c Following satisfied condition is detected for accum...

Страница 530: ...ons There are cases where the aperture opens wider than normal operation if the discharge temperature increases 11 Demand Control There are two styles of demand operations available as methods of restraining power consumption 1 Demand input from an external source is carried out from the outdoor unit EXCT CN026 PCB or the outdoor unit s serial parallel I O optional Demand control with EXCT input S...

Страница 531: ... D007 LED1 S003 R C ADD TERMINAL S002 R C ADD C CHK CN033 COOL_CHECK A ADD CN041 MODE CN031 PUMP DOWN CN042 JP001 JP007 RC plug RC P POWER LED D225 EEPROM memory IC IC006 LED for EEPROM memory IC D014 HIC CN01 SM830231 02 Single 欧州 indb 23 SM830231 02 Single 欧州 indb 23 2014 09 09 21 15 24 2014 09 09 21 15 24 ...

Страница 532: ... temp TD 4P pin 1 2 RC plug RC P Suction temp TS 4P pin 3 4 High pressure switch plug 63PH OC plug OC MOV plug MOV Intermediate temperature sensor in heat exchanger C2 Inlet temperature sensor in heat exchanger C1 SM830231 02 Single 欧州 indb 24 SM830231 02 Single 欧州 indb 24 2014 09 09 21 15 26 2014 09 09 21 15 26 ...

Страница 533: ...S002 R C ADD C CHK CN033 COOL_CHECK A ADD CN041 MODE CN031 PUMP DOWN CN042 JP001 JP007 RC plug RC P POWER LED D225 EEPROM memory IC IC006 LED for EEPROM memory IC D014 HIC CN01 CR 60PEY1E5 SM830231 02 Single 欧州 indb 25 SM830231 02 Single 欧州 indb 25 2014 09 09 21 15 28 2014 09 09 21 15 28 ...

Страница 534: ...e temp TD 4P pin 1 2 RC plug RC P Suction temp TS 4P pin 3 4 High pressure switch plug 63PH OC plug OC MOV plug MOV Intermediate temperature sensor in heat exchanger C2 Inlet temperature sensor in heat exchanger C1 SM830231 02 Single 欧州 indb 26 SM830231 02 Single 欧州 indb 26 2014 09 09 21 15 29 2014 09 09 21 15 29 ...

Страница 535: ...S002 R C ADD C CHK CN033 COOL_CHECK A ADD CN041 MODE CN031 PUMP DOWN CN042 JP001 JP007 RC plug RC P POWER LED D225 EEPROM memory IC IC006 LED for EEPROM memory IC D014 HIC CN01 CR 71PEY1E5 SM830231 02 Single 欧州 indb 27 SM830231 02 Single 欧州 indb 27 2014 09 09 21 15 31 2014 09 09 21 15 31 ...

Страница 536: ...e temp TD 4P pin 1 2 RC plug RC P Suction temp TS 4P pin 3 4 High pressure switch plug 63PH OC plug OC MOV plug MOV Intermediate temperature sensor in heat exchanger C2 Inlet temperature sensor in heat exchanger C1 SM830231 02 Single 欧州 indb 28 SM830231 02 Single 欧州 indb 28 2014 09 09 21 15 33 2014 09 09 21 15 33 ...

Страница 537: ... IC D330 POWER LED D514 Outdoor air temp CN TO Comp discharge temp CN TD RC plug CN RC PUMP DOWN Suction temp CN TS High pressure switch plug CN 63PH OC plug CN OC MOV plug CN MOV1 EEPROM memory IC IC18 CHK Intermediate temperature sensor in heat exchanger CN C2 Inlet temperature sensor in heat exchanger CN C1 SM830231 02 Single 欧州 indb 29 SM830231 02 Single 欧州 indb 29 2014 09 09 21 15 35 2014 09 ...

Страница 538: ... D514 Outdoor air temp CN TO Comp discharge temp CN TD RC plug CN RC PUMP DOWN Suction temp CN TS High pressure switch plug CN 63PH OC plug CN OC MOV plug CN MOV1 EEPROM memory IC IC18 CHK Intermediate temperature sensor in heat exchanger CN C2 Inlet temperature sensor in heat exchanger CN C1 SM830231 02 Single 欧州 indb 30 SM830231 02 Single 欧州 indb 30 2014 09 09 21 15 36 2014 09 09 21 15 36 ...

Страница 539: ...ER LED D514 Outdoor air temp CN TO Comp discharge temp CN TD RC plug CN RC PUMP DOWN Suction temp CN TS High pressure switch plug CN 63PH OC plug CN OC MOV plug CN MOV1 EEPROM memory IC IC18 CHK Intermediate temperature sensor in heat exchanger CN C2 Inlet temperature sensor in heat exchanger CN C1 SM830231 02 Single 欧州 indb 31 SM830231 02 Single 欧州 indb 31 2014 09 09 21 15 36 2014 09 09 21 15 36 ...

Страница 540: ...EEPROM memory IC IC18 Inlet temperature sensor in heat exchanger CN C1 Intermediate temperature sensor in heat exchanger CN C2 MOV plug CN MOV1 EMG plug CN EMG High pressure switch plug CN 63PH OC plug CN OC STOP MODE A ADD RUN PUMP DOWN S002 S003 CN SILENT Suction temp CN TS RC plug CN RC SM830231 02 Single 欧州 indb 32 SM830231 02 Single 欧州 indb 32 2014 09 09 21 15 37 2014 09 09 21 15 37 ...

Страница 541: ...EEPROM memory IC IC18 Inlet temperature sensor in heat exchanger CN C1 Intermediate temperature sensor in heat exchanger CN C2 MOV plug CN MOV1 EMG plug CN EMG High pressure switch plug CN 63PH OC plug CN OC STOP MODE A ADD RUN PUMP DOWN S002 S003 CN SILENT Suction temp CN TS RC plug CN RC SM830231 02 Single 欧州 indb 33 SM830231 02 Single 欧州 indb 33 2014 09 09 21 15 38 2014 09 09 21 15 38 ...

Страница 542: ...4 34 4 HIC PCB A746895 U 60PE1E5A U 71PE1E5A CN VDC U P V W N CN VDC 4WAY Valve CN 20S SM830231 02 Single 欧州 indb 34 SM830231 02 Single 欧州 indb 34 2014 09 09 21 15 39 2014 09 09 21 15 39 ...

Страница 543: ...4 35 4 HIC PCB continued A746846 U 100PE1E5A CN VDC U V W CN VDC 4WAY Valve CN 20S P NU SM830231 02 Single 欧州 indb 35 SM830231 02 Single 欧州 indb 35 2014 09 09 21 15 39 2014 09 09 21 15 39 ...

Страница 544: ...4 36 4 HIC PCB continued A746847 U 125PE1E5A U 140PE1E5A CN VDC U V W CN VDC 4WAY Valve CN 20S P NU SM830231 02 Single 欧州 indb 36 SM830231 02 Single 欧州 indb 36 2014 09 09 21 15 40 2014 09 09 21 15 40 ...

Страница 545: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU SM830231 02 Single 欧州 indb 37 SM830231 02 Single 欧州 indb 37 2014 09 09 21 15 41 2014 09 09 21 15 41 ...

Страница 546: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU SM830231 02 Single 欧州 indb 38 SM830231 02 Single 欧州 indb 38 2014 09 09 21 15 42 2014 09 09 21 15 42 ...

Страница 547: ... CN SILENT LED for EEPROM memory IC D330 POWER LED D514 High pressure sensor CN HPS Outdoor air temp CN TO Comp discharge temp CN TD RC plug CN RC Intermediate temperature sensor in heat exchanger CN C2 Suction temp CN TS High pressure switch plug CN 63PH OC plug CN OC MOV plug CN MOV1 EEPROM memory IC IC18 Inlet temperature sensor in heat exchanger CN C1 SM830231 02 Single 欧州 indb 39 SM830231 02 ...

Страница 548: ...Inlet temperature sensor in heat exchanger CN C1 Intermediate temperature sensor in heat exchanger CN C2 MOV plug CN MOV1 EMG plug CN EMG High pressure switch plug CN 63PH OC plug CN OC STOP CN PRY2 CN PRY1 MODE A ADD RUN PUMP DOWN S002 S003 SILENT CN SILENT Suction temp CN TS RC plug CN RC CR PCB A747247 U 100PEY1E8 U 125PEY1E8 SM830231 02 Single 欧州 indb 40 SM830231 02 Single 欧州 indb 40 2014 09 0...

Страница 549: ...A746970 U 71PE1E8A A746969 U 100PE1E8A U 125PE1E8A U 140PE1E8A U 140PEY1E8 U P CN VDC CN VDC V W NU 4WAY Valve CN 20S SM830231 02 Single 欧州 indb 41 SM830231 02 Single 欧州 indb 41 2014 09 09 21 15 45 2014 09 09 21 15 45 ...

Страница 550: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU SM830231 02 Single 欧州 indb 42 SM830231 02 Single 欧州 indb 42 2014 09 09 21 15 47 2014 09 09 21 15 47 ...

Страница 551: ... second or longer to automatically set the addresses at the indoor units that are connected to that outdoor unit and are within the same system The system address is 1 at the time of shipment Automatic address setting is necessary even for communications lines in a single system where the inter unit control wiring does not cross to any other systems While automatic address setting is in progress t...

Страница 552: ...eted close the valves and open circuit this pin to stop the operation 3P plug black Indoor unit Heating Cooling mode change pin When operating the compressors to perform automatic address setting operation in Heating mode can be normally used However short circuiting this pin performs operation in Cooling mode Static signal Short circuiting this pin during ordinary operation changes the mode from ...

Страница 553: ...OFF OFF OFF OFF OFF ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON ON Table 1 Setting the System Address S002 Rotary switch yellow S003 2P DIP black Outdoor system address No 1 refrigerant system only Link wiring 2P 20s digit 1P 10s digit S002 setting system address switch S003 setting 0 SM830231 02 Single 欧州 indb 45 SM830231 02 Single ...

Страница 554: ...rted LED 1 and 2 on the outdoor unit control PCB indicate that automatic address setting is in progress the LEDs blink alternately for several minutes after automatic address setting is started the compressors may also start and stop several times however LED 1 and 2 never indicate that automatic address setting is completed turn OFF Check the Alarm Displays table and correct the problem Check the...

Страница 555: ...e table below and correct the problem location Cause E01 E02 E09 Remote controller display Nothing is displayed The remote controller is not connected correctly remote controller receiving trouble The remote controller of an indoor unit where the indoor unit address is not set is inadvertently operated Communications with the outdoor unit are not possible The remote controller is not connected cor...

Страница 556: ...er Trouble Inlet Temperature Sensor C1 in Heat Exchanger Trouble Compressor Discharge Temperature Sensor TD Trouble F04 F06 F07 F08 F12 F31 Outdoor Unit Nonvolatile Memory EEPROM Trouble Compressor Inlet Suction Temperature Sensor TS Trouble Outdoor Air Temperature Sensor TO Trouble H01 H02 H03 H31 HIC Trouble Primary Current CT Sensor current sensor Failure Outdoor Unit Capacity not Set or Invali...

Страница 557: ...lay 5 4 5 3 PAC System Alarm Codes 5 5 5 4 Inspection of Parts Outdoor Unit 5 68 5 5 Symptom Thermostat in OFF continues or cycles OFF ON too frequently 5 69 5 6 How to Clean Heat Exchanger 5 70 5 7 How to Replace Fan Motor 5 71 SM830231 02 Single 欧州 indb 1 SM830231 02 Single 欧州 indb 1 2014 09 11 15 43 35 2014 09 11 15 43 35 ...

Страница 558: ...n Automatic address setting start is prohibited Duplication of main unit in group control Automatic Address Alarm The total capacity of indoor units is too low Automatic Address Alarm The total capacity of indoor units is too high Automatic Address Alarm No indoor unit connected Disconnection of wiring between main unit and additional units Contact failure of wiring Faulty indoor unit control PCB ...

Страница 559: ...unit EEPROM trouble F29 F31 F12 Primary current control Activation of compressor s protective device Primary current CT sensor failure H03 Compressor overcurrent trouble P16 Inverter compressor trouble P29 P22 Activation of high pressure switch Compressor discharge pressure trouble P04 P05 O2 sensor error O2 sensor detected Power supply failure Open phase detected AC power supply trouble Fan motor...

Страница 560: ...indoor units connected to that system matches the number that was set and regular communications are occurring Automatic address setting is in progress Blinking alternately Alarm display LED 1 blinks M times then LED 2 blinks N times The cycle then repeats M 2 P alarm 3 H alarm 4 E alarm 5 F alarm 6 L alarm N Alarm No Example LED 1 blinks 2 times then LED 2 blinks 16 times The cycle then repeats A...

Страница 561: ...rge Temperature Sensor TD Trouble F08 F12 F31 Outdoor Unit Nonvolatile Memory EEPROM Trouble Compressor Inlet Suction Temperature Sensor TS Trouble Outdoor Air Temperature Sensor TO Trouble H01 H02 H03 H31 HIC Trouble Primary Current CT Sensor current sensor Failure L04 L10 L18 Outdoor Unit Capacity not Set or Invalid 4 way Valve Operation Failure L13 Indoor Unit Type Setting Error Outdoor Unit Ad...

Страница 562: ...ip 1 time 1 Check 4 way valve 2 Check 4 way valve wiring 3 Check outdoor unit control PCB P04 P22 P29 H31 High pressure protection error High pressure switched ON Alarm is output when switch opened Pre trip 4 times OFF Recovery at restart Recovery at restart Recovery at restart Recovery at restart Recovery at restart Recovery at restart Overload operation of refrigerant cycle Outdoor unit fan moto...

Страница 563: ...nd outdoor units are connected with correct combination written in catalog 3 1 3 3 3 6 Is the indoor outdoor control line connected to more than one outdoor unit Network wired 3 2 3 4 Correct the setting Is the Terminal resistor select switch on the outdoor control PC board set to just one unit 3 3 3 5 2 1 Power on 2 3 3 1 3 2 Correct the connection Yes Yes Yes Yes Yes Yes Yes No No No No No No No...

Страница 564: ...trol group s wiring 2 2 Are the CHK pin and TEST pin on the indoor unit control board short circuited 3 1 3 3 3 5 Is the wireless remote controller connected to on the indoor unit s control PC board 3 2 3 4 3 5 Disconnect the connector mentioned above on the PC board of the indoor unit control PC board and see whether the E01 goes off after several minutes When doing so if two remote controllers a...

Страница 565: ...e 60 x 60 Type Indoor Unit Control Board TEST Pin OPTION CHK Pin RC EEPROM A747931 4 Way Cassette Type Indoor Unit Control Board Ceiling Type T2 type Indoor Unit Control Board RC EEPROM TEST Pin OPTION CHK Pin SM830231 02 Single 欧州 indb 9 SM830231 02 Single 欧州 indb 9 2014 09 11 15 43 55 2014 09 11 15 43 55 ...

Страница 566: ...ing so if two remote controllers are being used and the wireless remote controller is the main remote controller set the other remote controller as the main 2 2 1 2 2 1 Correct the wiring 2 1 2 3 2 4 Yes Yes Yes No No No Replace wireless remote control parts including wiring 2 3 Is there a short miswiring open wrong contact or grounding in the remote control s wiring 2 4 Correct the wiring Replace...

Страница 567: ...cation adaptor ON OFF controller 1 4 Remote controller 3 Indoor unit control PC board 1 Central control unit E03 Error in Indoor Unit Receiving Signal from Remote Controller central Error Detection Method When indoor unit s are connected Error Diagnosis It is judged an error when there is no communication from any remote controller collectively in a 3 minute period or if there is no communication ...

Страница 568: ...n RC EEPROM A747931 4 Way Cassette Type Indoor Unit Control Board Ceiling Type T2 type Indoor Unit Control Board A747336 4 Way Cassette 60 x 60 Type Indoor Unit Control Board RC EEPROM TEST Pin OPTION CHK Pin SM830231 02 Single 欧州 indb 12 SM830231 02 Single 欧州 indb 12 2014 09 11 15 43 56 2014 09 11 15 43 56 ...

Страница 569: ... the indoor unit addresses from the remote control s detailed settings mode Is it Not Set 99 or is the indoor unit s address duplicated 3 3 When the network of indoor outdoor operation line was wired was the SHORT setting of the terminal resistor switch on the outdoor control PC board set on multiple units four or more 2 2 Indoor outdoor control line 4 Indoor unit control PC board 3 No of Indoor U...

Страница 570: ... the indoor unit service board TERMINAL EEPROM TERMINAL EEPROM Outdoor Unit Control PCB A747898 U 60PE1E5A U 71PE1E5A for single phase outdoor unit PCB CR 50PE1E5 Up side U 50PE1E5 for single phase outdoor unit PCB EEPROM TERMINAL A747895 U 100PE1E5A for single phase outdoor unit PCB A747896 U 125PE1E5A U 140PE1E5A for single phase outdoor unit PCB TERMINAL EEPROM SM830231 02 Single 欧州 indb 14 SM8...

Страница 571: ...ngle phase outdoor unit PCB TERMINAL EEPROM CR 60PEY1E5 Up side U 60PEY1E5 for single phase outdoor unit PCB CR 71PEY1E5 Up side U 71PEY1E5 for single phase outdoor unit PCB TERMINAL EEPROM TERMINAL EEPROM SM830231 02 Single 欧州 indb 15 SM830231 02 Single 欧州 indb 15 2014 09 11 15 43 59 2014 09 11 15 43 59 ...

Страница 572: ...E8A U 125PE1E8A U 140PE1E8A A747596 U 140PEY1E8 for 3 phase outdoor unit PCB TERMINAL EEPROM A747247 U 100PEY1E8 U 125PEY1E8 for 3 phase outdoor unit PCB TERMINAL EEPROM TEST pin RC OPTION CHK pin EEPROM EEPROM TEST pin RC OPTION CHK pin EEPROM TEST pin RC OPTION CHK pin SM830231 02 Single 欧州 indb 16 SM830231 02 Single 欧州 indb 16 2014 09 11 15 44 00 2014 09 11 15 44 00 ...

Страница 573: ...oard set to OPEN Is the indoor outdoor operation line opened or shorted 1 3 1 4 Replace the indoor unit control PC board 1 5 Is the indoor outdoor operation line connected to more than one outdoor unit Network wired 1 1 Is the SHORT on the terminal resistor select switch on the outdoor main PC board set to one unit and the others are OPEN 1 2 Make the SHORT setting 1 4 Yes No 1 2 1 3 Yes No 1 4 Se...

Страница 574: ... outdoor unit PCB CR 60PEY1E5 Up side U 60PEY1E5 for single phase outdoor unit PCB CR 71PEY1E5 Up side U 71PEY1E5 for single phase outdoor unit PCB TERMINAL EEPROM TERMINAL EEPROM TERMINAL EEPROM EEPROM TERMINAL SM830231 02 Single 欧州 indb 18 SM830231 02 Single 欧州 indb 18 2014 09 11 15 44 02 2014 09 11 15 44 02 ...

Страница 575: ...t PCB TERMINAL EEPROM A747899 U 71PE1E8A A747897 U 100PE1E8A U 125PE1E8A U 140PE1E8A A747596 U 140PEY1E8 for 3 phase outdoor unit PCB TERMINAL EEPROM A747247 U 100PEY1E8 U 125PEY1E8 for 3 phase outdoor unit PCB TERMINAL EEPROM SM830231 02 Single 欧州 indb 19 SM830231 02 Single 欧州 indb 19 2014 09 11 15 44 04 2014 09 11 15 44 04 ...

Страница 576: ...nd the wireless remote controller is the main remote controller set the other remote controller as the main 3 3 Replace wireless remote control parts including wiring 3 4 3 5 3 4 3 5 Yes No Indoor units control PC board 1 Indoor unit power 2 Indoor outdoor operation line Yes No The indoor unit is not turned on The DISP pin of the indoor unit is shorted The signal output control PC board optional c...

Страница 577: ...ort 1 2 Is the DISP pin on the indoor unit control PC board shorted 1 1 Conduct checks prior to auto address setting Does E08 fail to go off even after running auto address setting again 1 2 1 3 1 4 Yes Yes No No 1 3 Do not make changes to indoor unit addresses with the detailed settings of the remote controller Make them in the remote control address change mode 1 4 Indoor unit control PC board T...

Страница 578: ...d hold both buttons for 4 seconds or longer Press button Once the display changes from flashing to steady the setting is complete Once you press button the remote controller returns to its normal display This will display the item 01 and the setting data 0001 or the like on the remote controller s display Press Timer 1 4 5 2 3 buttons to switch the setting data to 0000 0000 SUB 0001 Main Wireless ...

Страница 579: ...r unit and operating lines among the indoor outdoor units networked wiring when an instruction to start auto address setting is given from another controller during the auto address setting process When one controller in a networked system is running auto address setting it is not possible to start auto address setting from another controller Wait until the auto address setting in progress finishe...

Страница 580: ...s made in the indoor unit group control setting of the remote control detailed settings mode 1 2 Carry out the auto address setting 2 2 Are multiple indoor units set up as the main unit 1 1 Set up only one indoor unit as the main unit and other indoor units to the sub unit 2 1 2 1 2 2 Yes No 2 Installation Setting 1 Group Control Address SM830231 02 Single 欧州 indb 24 SM830231 02 Single 欧州 indb 24 ...

Страница 581: ...d the wireless remote controller is the main remote controller set the other remote controller as the main Replace wireless remote control parts including wiring 4 3 4 4 Is the LED blinking on the indoor unit s control PC board 4 5 Check all items under the section Check Prior to Auto Address Setting 5 1 The nonvolatile memory EEPROM on the indoor unit s control board is either not installed impro...

Страница 582: ...y of indoor units is too high or the total number of indoor units is too many 1 2 1 The total capacity of indoor units is too high The total number of indoor units is too many Check all items under the section Check Prior to Auto Address Setting 1 1 Auto Address SM830231 02 Single 欧州 indb 26 SM830231 02 Single 欧州 indb 26 2014 09 11 15 44 08 2014 09 11 15 44 08 ...

Страница 583: ...indoor unit in the control group are shorted Remote control group wiring is opened More than one indoor unit in the control group is set to Main An indoor unit in the control group is set to Separate The DISP pin of an indoor unit sub remote controller in the control group is shorted 1 2 Replace wireless remote control parts including wiring Replace the indoor unit control PC board 3 3 Is the wire...

Страница 584: ...er of indoor units is too many Indoor unit is not turned On Be sure that the indoor and outdoor units are connected with correct combination written in catalog Are the address es of indoor unit s assigned correctly 1 1 Are the indoor units turned on 1 2 1 3 The indoor outdoor control line may be disconnected somewhere between the indoor unit s and the outdoor unit Make sure the indoor outdoor cont...

Страница 585: ...Operating status Yes No Resistance between connector pins on PC board is less than 1 k ohm 2 1 Replace PC board 2 2 Yes No Peripheral temperature of outdoor unit is over 46 C 3 1 Check noise 3 3 Correct 3 2 Yes No Tends to have insufficient refrigerant charge in the system 3 2 Adjust the amount of refrigerant 3 3 Yes No Abnormal temperature exists even after replacing PC board 2 2 3 1 See what hap...

Страница 586: ...t control PCB failure Replace PCB with a new one Is the connector properly connected to PCB 1 1 Is the resistor between the sockets infinity or 0Ω 1 2 2 1 1 2 Reconnect check Replace sensor 2 1 Yes No 1 Sensor Trouble 2 Control PCB Failure Yes No SM830231 02 Single 欧州 indb 30 SM830231 02 Single 欧州 indb 30 2014 09 11 15 44 10 2014 09 11 15 44 10 ...

Страница 587: ... circuit 1 2 Sensor connector is connected to PC board properly 1 1 1 2 Reconnect and check Yes No 1 Sensor 2 PC board Replace PC board because of outdoor control PC board failure 2 1 Resistance between sockets is infinity or 0 ohm 1 2 Replace sensor 2 1 Yes No SM830231 02 Single 欧州 indb 31 SM830231 02 Single 欧州 indb 31 2014 09 11 15 44 10 2014 09 11 15 44 10 ...

Страница 588: ... 2 Sensor connector is connected to PC board properly 1 1 1 2 Reconnect and check Yes No 1 Sensor 2 PC board Replace PC board because of outdoor control PC board failure 2 1 Resistance between sockets is infinity or 0 ohm 1 2 Replace sensor 2 1 Yes No SM830231 02 Single 欧州 indb 32 SM830231 02 Single 欧州 indb 32 2014 09 11 15 44 10 2014 09 11 15 44 10 ...

Страница 589: ...2 Sensor connector is connected to PC board properly 1 1 1 2 Reconnect and check Yes No 1 Sensor 2 Outdoor control PC board Replace PC board because of outdoor control PC board failure 2 1 Resistance between sockets is infinity or 0 ohm 1 2 Replace sensor 2 1 Yes No SM830231 02 Single 欧州 indb 33 SM830231 02 Single 欧州 indb 33 2014 09 11 15 44 10 2014 09 11 15 44 10 ...

Страница 590: ...OM is not installed Read values after writing onto nonvolatile memory EEPROM is inconsistent 1 2 Does EEPROM exist on the control PC board 1 1 1 2 Install EEPROM Yes No 1 PC board Incorrect EEPROM Replace with correct EEPROM 1 3 Is EEPROM installed properly Check Bent IC pin or incorrect installation etc 1 2 1 3 Correct Yes No SM830231 02 Single 欧州 indb 34 SM830231 02 Single 欧州 indb 34 2014 09 11 ...

Страница 591: ... 1 2 2 2 3 2 2 Loose electrical wire connection 2 1 Correct wiring 2 3 Has FUSE 1 FUSE 2 blown Check the electrical conduction with tester 2 2 Yes Yes No No Replace CR board 2 3 PC board wiring Check not only in the outdoor unit stop mode but in the drive mode Heating Cooling 2 5 hp 20 0A 18 5A 3 hp 20 0A 18 5A 4 hp 27 0A 27 0A 5 hp 29 0A 29 0A 6 hp 30 0A 30 0A Trip current value 3 phase model hp ...

Страница 592: ...E1E5A for single phase outdoor unit PCB CR 60PEY1E5 bottom U 60PEY1E5 for single phase outdoor unit PCB F001 CR 71PEY1E5 bottom U 71PEY1E5 for single phase outdoor unit PCB F001 FUSE1 FUSE1 SM830231 02 Single 欧州 indb 36 SM830231 02 Single 欧州 indb 36 2014 09 11 15 44 11 2014 09 11 15 44 11 ...

Страница 593: ... unit PCB FUSE1 FUSE1 A747899 U 71PE1E8A A747897 U 100PE1E8A U 125PE1E8A U 140PE1E8A A747596 U 140PEY1E8 for 3 phase outdoor unit PCB A747247 U 100PEY1E8 U 125PEY1E8 for 3 phase outdoor unit PCB FUSE1 FUSE1 SM830231 02 Single 欧州 indb 37 SM830231 02 Single 欧州 indb 37 2014 09 11 15 44 12 2014 09 11 15 44 12 ...

Страница 594: ...Yes No 2 PC board wiring Yes No Extreme voltage fluctuations Extreme distortion of voltage waveform Check power supply 2 1 Yes No Check power supply Loose electrical wire connection Is HIC PC board connector CN PAM poorly connected or opened with wire Replace HIC PC board Check not only in the outdoor unit stop mode but in the drive mode Not satisfied with 10 rated supply voltage SM830231 02 Singl...

Страница 595: ...current sensor Failure Error Detection Method Error Diagnosis If 18A or greater is detected when the compressor is stopped alarm triggered even if the connector is unplugged If no current is detected even though a compressor is running 1 2 It is judged an error based on the criteria listed below SM830231 02 Single 欧州 indb 39 SM830231 02 Single 欧州 indb 39 2014 09 11 15 44 13 2014 09 11 15 44 13 ...

Страница 596: ...erature just before starting 1 In case of outdoor temperature less than 5 C For 30 minutes since started variation of discharge temperature is always detected within 2 C comparing with the temperature just before starting 1 1 1 2 Reinstall correctly Yes No 1 Sensor Trouble Replace the sensor with a new one 1 2 Is the sensor properly installed at the holder side SM830231 02 Single 欧州 indb 40 SM8302...

Страница 597: ...e between the HIC and the outdoor CR board Check the wiring one by one with a tester if there is opened and grounding The heat dissipating surface on the back of the HIC is in good contact with the heat sink heat dissipating fins of the electrical box Check for looseness in the fastening screws and the condition of the heat conducting putty 1 2 Tighten screw s add putty Yes No 3 2 Refer to alarm c...

Страница 598: ... HIC 5 k to 20 k U 20 k to V 20 k to W 20 k to HIC 20 k to C I H C I H Tester terminals Resistance value ohm C I H C I H U 20 k to 20 k to V 20 k to W 20 k to CR 50PE1E5 bottom U 50PE1E5 for single phase outdoor unit PCB Outdoor Unit Control PCB Outdoor Unit Control HIC PCB A746895 U 60PE1E5A U 71PE1E5A for single phase outdoor unit HIC PCB N W V U P NU P W V U SM830231 02 Single 欧州 indb 42 SM8302...

Страница 599: ...B P U V W NU for single phase outdoor unit HIC PCB A746846 U 100PE1E5A P U V W NU CR 60PEY1E5 bottom U 60PEY1E5 for single phase outdoor unit PCB CR 71PEY1E5 bottom U 71PEY1E5 for single phase outdoor unit PCB NU P W V U NU P W V U SM830231 02 Single 欧州 indb 43 SM830231 02 Single 欧州 indb 43 2014 09 11 15 44 14 2014 09 11 15 44 14 ...

Страница 600: ...1E5 for single phase outdoor unit HIC PCB A747247 U 100PEY1E8 U 125PEY1E8 for 3 phase outdoor unit PCB U V W P NU A747248 U 100PEY1E8 U 125PEY1E8 for 3 phase outdoor unit HIC PCB U V W P NU U V W P NU CN PRY1 for 3 phase outdoor unit HIC PCB A746969 U 100PE1E8A U 125PE1E8A U 140PE1E8A U 140PEY1E8 A746970 U 71PE1E8A P U V W NU SM830231 02 Single 欧州 indb 44 SM830231 02 Single 欧州 indb 44 2014 09 11 1...

Страница 601: ...es within 3 minutes 1 2 Are other outdoor units using a duplicate setting 1 1 2 1 2 2 Yes No 2 When units are networked first set the system address for each outdoor unit in the order 1 2 3 and then run auto address setting 2 1 Run the auto address setting 2 2 Installation or setting related 1 System address SM830231 02 Single 欧州 indb 45 SM830231 02 Single 欧州 indb 45 2014 09 11 15 44 17 2014 09 11...

Страница 602: ...setup or systematically unauthorized setting Check Connect the outdoor maintenance remote controller and check whether item code 81 outdoor capacity value shows 0 or unauthorized capacity is set on the detailed settings mode display of the outdoor EEPROM If the capacity value of the item code 81 with the outdoor maintenance remote controller is incorrect recorrect and set it again After setting th...

Страница 603: ...th the remote control detailed settings mode 2C code and commercial indoor unit is set to 2 and multiple indoor unit is 0 2 1 Check whether or not indoor and outdoor unit operating wires are short circuit disconnection loose connection or earth fault 3 1 Installation Failure 3 Operating Wires for Indoor Outdoor Units 1 Discordance Unit Discordance model s between outdoor and indoor units are detec...

Страница 604: ...d to the 4 way valve 1 3 4 way valve 1 PC board wiring Correct wiring 1 3 Yes No 2 1 Correct connector Yes No During heating mode Comp ON insert and remove the connector wired from the 4 way valve into or from CN 20S connector on the HIC PC board At the same time does the ON OFF sounds occur from the 4 way valve 2 1 2 2 Replace HIC PC board Yes No During heating mode Comp ON does the alarm code L1...

Страница 605: ...e in the system Service valve inside the outdoor unit closed Additional refrigerant charge 2 2 Yes No Open service valve Replace CR board Yes No Replace the strainer Are the tubes clogged Is the outdoor unit s electronic control valve operating correctly Check for debris clogging the electronic control valve a problem with the electronical coil and or the control PC board Is it observable differen...

Страница 606: ... checking finished without fail 3 4 4 1 Replace the outdoor unit fan Correct connection and or wiring Yes No While heating is operating an alarm is occurred 3 5 3 6 4 1 Yes No 2 Service valve 3 Problem around the heat exchanger P04 High Pressure Trouble Error Detection Method Error Diagnosis It is judged an error if the internal circuit of the high pressure switch is dead The electronic circuitry ...

Страница 607: ... coil and or the control PC board 4 2 4 3 Repair the expansion valve of the indoor unit Yes No 3 Problem around the heat exchanger 4 Blockage in the refrigerant circuit Error occurs when the system is operating in cooling mode 5 1 5 3 5 2 Yes No An alarm is occurred with the high pressure at 3 80 MPa with the pressure measured either as displayed by the monitoring software or with a manifold gauge...

Страница 608: ...r unit HIC PC board 4 1 Yes No 3 Check the outdoor unit HIC PC board 2 Check the outdoor unit CR PC board There may be a instantaneous blackout failure If there is nothing abnormal see what happens 4 1 4 Final check P05 AC Power Supply Trouble Error Detection Method Error Diagnosis Instantaneous blackout Note The work involved in diagnosing each of the items is extremely dangerous so turn the powe...

Страница 609: ... Service valve Open the service valve 2 1 2 Adjustment to refrigerant change 3 Blockage in refrigerant circuit 3 1 Avoid clogging 3 2 Yes No Are the tubes clogged Not additional refrigerant charged 3 1 Yes No Additional refrigerant charge 3 2 3 3 Replace the electronic control valve Yes No Is the outdoor unit s electronic control valve operating correctly Check for debris clogging the electronic c...

Страница 610: ...the indoor unit With the indoor unit s EEPROM setting item code 0B set to 0001 the EXCT input was shorted 1 2 Is an O2 sensor being used Correct wiring 4 1 Yes No Is the indoor EXCT socket wire shorted 3 1 3 4 Indoor EXCT wiring 4 3 4 2 Yes No Is the alarm triggered if the indoor EXCT socket wire is disconnected and the power is reset Since there is no error see what happens 4 1 4 2 4 3 Indoor uni...

Страница 611: ...on valve is fully opened Compressor s discharge temperature exceeds 95 C Alarm occurs in the following cases 1 1 Yes No 1 Adjustment of refrigerant amount Recharge with additional refrigerant 1 2 1 2 Check leakage of refrigeration leak test See what happens Yes No Replace leaking part with a new one Insufficient gas level Check whether or not pressure level is normal SM830231 02 Single 欧州 indb 55 ...

Страница 612: ... and or in the connections of components that are connected by wiring from the CR board 2 2 Correct 2 3 Yes No Correct 2 4 Yes No 2 3 Disconnected parts miswiring and or poor connections loose are observed in the connections of outdoor board s that are connected by wiring from the HIC board Correct 2 5 Yes No 2 4 Disconnected parts miswiring and or poor connections loose are observed in the connec...

Страница 613: ...er is high The frequency Hz ends up dropping due to the current 5 6 Replace the compressor See what happens Yes No Tends to have insufficient refrigerant charge in the system 5 5 Adjust the amount of refrigerant 5 6 Yes No 4 Check the situation 5 Check operation Dividing the outdoor EEPROM INV operation time by the number of times oil was supplied to the system yields 3 hours or less 6 1 6 2 6 2 Y...

Страница 614: ... value is 0 short circuit it is acceptable if a small resistance value appears as a reference value unless the HIC board IPM Pass Fail Tests Tester terminals Resistance value ohm U 1 k to 5 k V 1 k to 5 k W 1 k to 5 k U 1 k to 5 k V 1 k to 5 k W 1 k to 5 k NU 5 k to 10 k U 100 k to V 100 k to W 100 k to P 100 k to P NU Tester terminals Resistance value ohm P NU U 100 k to 100 k to V 100 k to W 100...

Страница 615: ...71PE1E5A for single phase outdoor unit HIC PCB N W V U P NU P W V U Outdoor Unit Control HIC PCB A746847 U 125PE1E5A U 140PE1E5A for single phase outdoor unit HIC PCB P U V W NU for single phase outdoor unit HIC PCB A746846 U 100PE1E5A P U V W NU SM830231 02 Single 欧州 indb 59 SM830231 02 Single 欧州 indb 59 2014 09 11 15 44 19 2014 09 11 15 44 19 ...

Страница 616: ...om U 71PEY1E5 for single phase outdoor unit PCB NU P W V U A746846 U 100PEY1E5 for single phase outdoor unit HIC PCB A746847 U 125PEY1E5 for single phase outdoor unit HIC PCB U V W P NU U V W P NU Outdoor Unit Control HIC PCB SM830231 02 Single 欧州 indb 60 SM830231 02 Single 欧州 indb 60 2014 09 11 15 44 20 2014 09 11 15 44 20 ...

Страница 617: ...1E8 for 3 phase outdoor unit HIC PCB U V W P NU for 3 phase outdoor unit HIC PCB A746969 U 100PE1E8A U 125PE1E8A U 140PE1E8A U 140PEY1E8 A746970 U 71PE1E8A P U V W NU SM830231 02 Single 欧州 indb 61 SM830231 02 Single 欧州 indb 61 2014 09 11 15 44 22 2014 09 11 15 44 22 ...

Страница 618: ... cannot be detected normally 1 2 Are the connectors CN FMA CN FMB CN FM1 and CN FM2 firmly connected to the outdoor control PC board lock engaged 3 Turn the power on and run the unit again is P22 triggered again Or can you see or hear anything that is obviously wrong in its rotation Replace the outdoor control PC board If it fails to operate normally even after replacing the outdoor control PC boa...

Страница 619: ...rews must not be loose Does it operate normally Yes No See what happens See what happens The results of the pass fail tests for the following HIC PC board IPM show it to be outside the range of the resistance of a conforming part Checking for looseness of compressor terminals by wiggling them has the adverse effect of loosening them so do not do it Evaluate them by discoloration of wire insulation...

Страница 620: ...ection Method Other indoor unit alarms within the group 1 Survey the indoor unit that alarms other than P31 in the indoor unit group and specify the causes of failure SM830231 02 Single 欧州 indb 64 SM830231 02 Single 欧州 indb 64 2014 09 11 15 44 23 2014 09 11 15 44 23 ...

Страница 621: ...71PE1E5A for single phase outdoor unit HIC PCB N W V U P NU P W V U Outdoor Unit Control HIC PCB A746847 U 125PE1E5A U 140PE1E5A for single phase outdoor unit HIC PCB P U V W NU for single phase outdoor unit HIC PCB A746846 U 100PE1E5A P U V W NU SM830231 02 Single 欧州 indb 65 SM830231 02 Single 欧州 indb 65 2014 09 11 15 44 23 2014 09 11 15 44 23 ...

Страница 622: ...om U 71PEY1E5 for single phase outdoor unit PCB NU P W V U A746846 U 100PEY1E5 for single phase outdoor unit HIC PCB A746847 U 125PEY1E5 for single phase outdoor unit HIC PCB U V W P NU U V W P NU Outdoor Unit Control HIC PCB SM830231 02 Single 欧州 indb 66 SM830231 02 Single 欧州 indb 66 2014 09 11 15 44 24 2014 09 11 15 44 24 ...

Страница 623: ...1E8 for 3 phase outdoor unit HIC PCB U V W P NU for 3 phase outdoor unit HIC PCB A746969 U 100PE1E8A U 125PE1E8A U 140PE1E8A U 140PEY1E8 A746970 U 71PE1E8A P U V W NU SM830231 02 Single 欧州 indb 67 SM830231 02 Single 欧州 indb 67 2014 09 11 15 44 25 2014 09 11 15 44 25 ...

Страница 624: ...is used Set the tester to the 12 V range if the value displayed is approximately 4 V then the voltage is normal If the voltage is normal measure the resistance between connector pin 5 and pins 1 through 4 Resistance between pin 5 and pins 1 through 4 should be approximately 46 for all If the result is 0 or then replace the coil SM830195 00 indb 52 2011 09 30 15 41 52 SM830231 02 Single 欧州 indb 68 ...

Страница 625: ...tatus 2 2 Yes No 2 2 Discharge temperature is over 80 C in stop mode and does not decrease Connect outdoor maintenance remote controller to RC socket on outdoor unit main control PC board and check alarm messages Replace discharge temperature sensor 2 3 Yes No 2 3 Demand value always stays low The value is lower than 70 Excluding 1 unlimited Connect outdoor maintenance remote controller to RC sock...

Страница 626: ...rt a high pressure cleaner from the opening Fig 2a and clean the heat exchanger Fig 2b 5 When finished cleaning install the drain plug and lid drain pump WARNING ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH lid Drain plug Opening Heat exchanger Fig 1 Fig 2a Fig 2b SM830231 02 Single 欧州 indb 70 SM830231 02 Single 欧州 indb 70 2014 09 11 15 44 26 2014 09 11 15 44 26 ...

Страница 627: ...e Fig 4 5 Disconnect two 2 clutches Fig 5a fixing the lower side of the fan casing and pull out the protrusion part Fig 5c placed onto the side of the main unit Fig 5b Then remove the fan casing Clutches Fan casing e d i s t i n u n i a M t r a p n o i s u r t o r P Screws x 5 locations Connector Bottom plate Screw WARNING ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH Fig 1 Fig 2 Fig ...

Страница 628: ...over 100mm in length and remove the fan 9 Remove the rubber attached to the wiring of the fan motor Fig 9 1 For installation reverse the procedure above 2 Fine tune so that the fan can be positioned in the center of the fan casing Bracket Fan motor Fixed screw Fan Hexagon wrench Rubber Screws M6 Fig 6 Fig 7 Fig 8 Fig 9 Installing Fan Motor SM830231 02 Single 欧州 indb 72 SM830231 02 Single 欧州 indb 7...

Страница 629: ...Operations Display of Indoor Unit and Outdoor Unit Sensor Temperatures 6 6 6 5 Monitoring the Outdoor Unit Alarm History Display of Outdoor Unit Alarm History 6 7 6 6 Settings Modes Setting the Outdoor Unit EEPROM 6 7 Sec6 indd 1 2012 02 28 11 49 48 SM830231 02 Single 欧州 indb 1 SM830231 02 Single 欧州 indb 1 2014 09 09 21 16 54 2014 09 09 21 16 54 ...

Страница 630: ...d a separate remote controller or other control device must be connected to the indoor unit 6 2 Functions Normal display functions 1 Functions Button operations can be used to perform the following functions Start stop of all indoor units Switching between cooling and heating Test run of all indoor units High speed operation of indoor units Do not use with actual units This may damage the devices ...

Страница 631: ...stop Fig 6 1 Operation The button can be used to start and stop all the indoor units The LED turns ON when 1 or more indoor units is operating The LED blinks when an alarm has occurred at 1 or more indoor units during operation Switching between cooling heating Fig 6 1 Operation The button switches between heating and cooling modes The specifications are equivalent to the heating cooling input tha...

Страница 632: ...nits in that refrigerant system 2 07 Operating status of outdoor units in that refrigerant system blinks when alarms occur 2 08 09 0A 0b 0C 0d 0E 0F 10 Total compressor operating time in 1 h units 3 11 12 13 14 15 16 Total power ON time of outdoor unit in 1 h units 17 Compressor start count 18 19 FE Outdoor unit microcomputer firmware version FF Outdoor unit microcomputer software version See foll...

Страница 633: ...e not lit The display of the first 4 and last 4 digits changes automatically every 10 seconds It can also be changed by pressing the button NOTE With the outdoor unit maintenance remote controller when connected to the outdoor unit the unit remote controller check functions will not operate Display for unit Nos 1 20 Not lit Lit Not lit Lit Not lit Lit Not lit Lit Meaning of display colon is not di...

Страница 634: ...d the temperature data are displayed 4 To end monitoring press the button The display returns to the normal display The display does not blink e d o C f o g n i n a e M e d o c m e t I Indoor unit data 02 Indoor unit intake temp 03 Indoor unit heat exchanger temp E1 04 Indoor unit heat exchanger temp E2 05 06 07 08 09 Outdoor unit data 0A Discharge temp TD 0b 0C 0d Intake temp TS 0E Outdoor unit h...

Страница 635: ...ve been no alarm codes is displayed 4 To clear the alarm history press the button The outdoor unit alarm history will be cleared 5 To end press the button The display returns to the normal remote controller display 6 6 Settings Modes Setting the Outdoor Unit EEPROM Setting mode 1 Operating procedure 1 Press and hold the button and button simultaneously for 4 seconds or longer 2 Use the temperature...

Страница 636: ...the unit was thermo on or thermo off 6 Doing the action 4 and 5 7 During cooling only Doing the action 6 0 Heat pump 1 Cooling only Cooling only E 0 12 Silent mode 0 Disable at shipment 1 At any times 2 Capacity priority 3 Timer setting 4 2 3 13 22 22 o clock at shipment 14 00 00 minute at shipment 15 28 28 o clock at shipment 16 00 00 minute at shipment 1A 40㧑 㨪 130㧑 1 no control 1B 40㧑 㨪 130㧑 1 ...

Страница 637: ...tailed Setting Items 7 7 7 5 Simple Setting Items 7 11 7 6 Detaild Setting Items 7 13 7 7 Remote Controller Servicing Functions 7 17 7 8 Test Run Function 7 19 7 REMOTE CONTROLLER FUNCTIONS SECTION Sec7 indd 1 2012 02 28 15 07 14 SM830231 02 Single 欧州 indb 1 SM830231 02 Single 欧州 indb 1 2014 09 09 21 19 19 2014 09 09 21 19 19 ...

Страница 638: ...1 At this time the indoor unit fan or all indoor unit fans in the case of group control begins operating 3 If group control is in effect press the button and select the address unit No of the indoor unit to set At this time the fan at the indoor unit begins operating If unit No is displayed the same setting will be made for all indoor units 4 Press the temperature setting buttons to select the ite...

Страница 639: ...rm 20 30 THU 7 Simple settings Simple settings Unit no Code no Set data 01 3 1 0001 Sel Next 20 30 THU 3 Select the Code no by pressing the or button Change the Code no by pressing the or button 4 Select the Set data by pressing the or button Select one of the Set data by pressing the or button Then press the button 5 Select the Unit no by pressing the or button and press the button The Exit simpl...

Страница 640: ... 0 0 Lo LL 6 0 0 0 Heating intake temperature shift 0000 No shift 0001 Shifts intake temperature 1 C down 0002 Shifts intake temperature 2 C down 0003 Shifts intake temperature 3 C down 0004 Shifts intake temperature 4 C down 0005 Shifts intake temperature 5 C down 0006 Shifts intake temperature 6 C down Electric heater installation 0000 No heater 0001 Heater installed Humidifying when heater ther...

Страница 641: ...ller LCD display Fig 7 3 At this time the indoor unit fan or all indoor unit fans in the case of group control begins operating 3 If group control is in effect press the button and select the address unit No of the indoor unit to set At this time the fan at the indoor unit begins operating 4 Press the temperature setting buttons to select the item code to change 5 Press the timer time buttons to s...

Страница 642: ...imple settings Detailed settings Unit no Code no Set data 10 3 1 0001 Sel Next 20 30 THU 3 Select the Code no by pressing the or button Change the Code no by pressing the or button or keeping it pressed 4 Select the Set data by pressing the or button Select one of the Set data by pressing the or button Then press the button 5 Select the Unit no by pressing the or button and press the button The Ex...

Страница 643: ...group control indoor units Sub unit All group control indoor units except for main unit Not set Cooling intake temperature shift 010 Shifts intake temperature 10 C down 009 Shifts intake temperature 9 C down 001 Shifts intake temperature 1 C down 0000 0001 No intake temperature shift Shifts intake temperature 1 C up 0009 0010 Shifts intake temperature 9 C up Shifts intake temperature 10 C up Autom...

Страница 644: ...er limit at shipment Upper limit Lower limit Auto heat cool 0017 17 C Lower limit at shipment 0018 18 C 0026 26 C 0027 27 C Upper limit at shipment Humidifier operation 0000 Normal 0001 Ignore heat exchanger temperature conditions Filter CN70 input switching 0000 Filter input differential pressure switch input 0001 Alarm input for trouble input about air cleaner or similar device 0002 Humidifier i...

Страница 645: ... Output linked with fan ON when indoor unit fan is operating 0001 Fan mode operation output Drain pump delayed start time 0000 No delayed start 0001 1 minute delayed start 0002 2 minutes delayed start 0058 58 minutes delayed start 0059 59 minutes delayed start 0060 60 minutes delayed start Humidifier setting 0000 Humidifier output OFF Drain pump stopped 0001 Humidifier output ON Drain pump operate...

Страница 646: ...er Antibacterial high performance filter 90 Antibacterial high performance filter 65 Air cleaning unit air cleaning unit optical regenerative deodorizing filter deodorant activated charcoal filter For air blocking material For 3 Way discharge when discharge duct is connected 0006 For air blocking material For 2 Way discharge Humidifier ON time ON time per 60 seconds 0000 No humidifier output 0001 ...

Страница 647: ...g filter indicates the filter sign ON time that is set at shipment High fouling Set when is selected for the degree of filter fouling item code n o i t p i r c s e D m e t I e d o c m e t I 03 Central control address Set when using a central control device Used when setting the central control address manually from the remote controller 04 Operating mode priority change Note 1 NOTE There are other...

Страница 648: ...ture during heating Can be set when the body thermostat is used 07 Electric heater installation Set when cost distribution is performed using an AMY central control system or similar system and when an optional electric heater is installed This is unrelated to control of the electric heater 08 Humidifying when heater thermostat is OFF Normally humidifying does not occur when the thermostat is OFF ...

Страница 649: ...stat ON time Use this setting to change the time for forced operation at installation or servicing from 5 minutes to 4 minutes Enabled only with PAC models 1E Temperature shift for cooling heating change in auto heat cool mode Auto heat cool selects the operating mode automatically based on the difference between the room temperature and the temperature set on the remote controller This setting es...

Страница 650: ...m remote controller It is possible to install a total heat exchanger and ventilation fan in the system which can be started and stopped by the wired remote controller The ventilation fan can operate linked with the start and stop of the indoor unit or can be operated even when the indoor unit is stopped Use a ventilation fan that can accept the no voltage A contact as the external input signal In ...

Страница 651: ...mode for the flap 5d DC fan tap setting Sets the DC fan tap according to the purpose of use Change the settings data at the same time 5E Humidifier ON time Sets the humidifier output ON time for when the humidifier is operating ON OFF control is performed during humidifier operation This setting therefore sets the ON time per 60 second interval 5F Stop at time set for OFF timer after operation sta...

Страница 652: ...ection discharge CZ CFU2 2 Setting No 3 Open the cover of the electrical component box and connect the supplied short circuit connector 2P yellow to short circuit pin TP3 2P yellow on the indoor unit control PCB 3 Setting No 6 Open the cover of the electrical component box and connect the supplied short circuit connector 2P yellow to short circuit pin TP6 2P white on the indoor unit control PCB DC...

Страница 653: ...onger Simple settings Filter lifetime operating mode priority central control address and other settings Press and hold the and buttons for 4 seconds or longer When settings are made from a remote controller the indoor unit where that remote controller is connected stops Detailed settings System address indoor unit address central control address and other settings Press and hold the and buttons f...

Страница 654: ...4 Test run Press the button Sensor temperature display Temperature display from each sensor 5 Sensor info Servicing check display Alarm history display 6 Service check Simple settings Filter lifetime operating mode priority central control address and other settings 7 Simple settings Press the button Restart When settings are made from a remote controller the indoor unit where that remote controll...

Страница 655: ... Select 4 Test run on the LCD display and press the button Change the display from OFF to ON by pressing the or button Then press the button Fig 7 8 3 Press the button TEST will be displayed on the LCD display 4 Press the button Test run will be started Test run setting mode screen appears on the LCD display Maintenance func 1 Outdoor unit error data 2 Service contact 3 RC setting mode 4 Test run ...

Страница 656: ...If monitor mode is engaged while normal operation is in progress only the parts of the LCD display shown in the figure will change Other parts continue to display the same information as during normal operation Fig 7 9 Indoor unit sensors Outdoor unit sensors 02 Intake temp Unit No 1 Unit No 2 Unit No 3 Unit No 4 03 E1 0A 2A 4A 6A Discharge temp 1 04 E2 0B 2B 4B 6B Discharge temp 2 05 E3 0C 2C 4C ...

Страница 657: ...it Refer the information by pressing the or button Fig 7 10 Maintenance func 1 Outdoor unit error data 2 Service contact 3 RC setting mode 4 Test run Sel Page Confirm 20 30 THU Maintenance func 5 Sensor info 6 Servicing check 8 Detailed settings Sel Page Confirm 20 30 THU 7 Simple settings Sensor info Unit no Code no Data Sel Next 20 30 THU 01 02 00 0028 0026 0026 1 1 Sensor info Unit no Code no D...

Страница 658: ... display 2 Press the or button to see each menu If you wish to see the next screen instantly press the or button Select 7 Simple settings on the LCD display and press the button The Simple settings screen appears on the LCD display Select the Unit no by pressing the or button for changes The indoor unit fan operates only at the selected indoor unit Automatic address setting Checking indoor unit ad...

Страница 659: ...e Remote Control 8 9 For Best Results 8 10 Addresses 8 9 8 11 8 12 8 13 8 14 8 14 8 11 Emergency Operation 8 12 Miscellaneous Settings 8 13 Before Requesting Service How to Install the Wireless Remote Controller Receiver 8 14 Common to All Models 8 15 CZ RWSU2 8 16 8 16 CZ RWST2 8 18 8 17 CZ RWSL2 8 21 8 18 CZ RWSC2 8 24 8 20 CZ RWST3 8 30 8 32 8 21 Common to All Models 8 HOW TO INSTALL THE WIRELE...

Страница 660: ...op the system and turn the power off if you sense unusual smells or other irregularities Do not swallow the battery Do not repair Contact your dealer before moving the system Moving and Repair Precautions Electric shock and damage to the system can result Continuing operation when the system is out of order can result in electric shock fire and damage to the system Contact your dealer Never repair...

Страница 661: ...an Pressing this button starts and stops the fan When the air conditioner is started or stopped the fan starts or stops at the same time appears on the display of the remote control when the fan is operating 15 Sensor button Use this when switching to detect the temperature at the remote control At shipping the default setting is set to detect the temperature at the unit At this time is shown on t...

Страница 662: ...making the settings Test On switch This is used during service It is not for normal use Test Run On switch This is used during service It is not for normal use 7 Swing button 8 Normal Stop All switch 9 Address switch Differentiate between incoming and outgoing signals If a heat pump model is being used it will beep twice and the operating lamp will light up on the display if the timer and standby ...

Страница 663: ...eries NOTE NOTE 8 3 Setting the Current Time After changing the batteries and pressing reset be sure to reset the current time When reset is pressed the current time reverts to 1 Press for two seconds or more 2 Set the hour with of the If you press and hold the button the time changes quickly 3 Set the minutes with of the If you press and hold the button the time changes quickly 4 Pressing complet...

Страница 664: ...If you cannot turn the air conditioner off in the normal way Disconnect the power to the indoor unit and contact the dealer where the product was purchased Auto Operation If all the indoor units are identical in a cooling system and are under control as one group it heats or cools automatically via the differences between the set temperature and the room temperature Dry Operation Depending on the ...

Страница 665: ...y indicating settings are complete After the timer setting is displayed for three seconds the display reverts to the current time Combining ON and OFF Timers Setting the ON and OFF timers respectively Checking the timer setting If you press either for the or the the scheduled time is displayed for four seconds When no timer setting has been made it displays Initial Setting Changing a timer setting...

Страница 666: ... time you press the direction the flap faces changes Setting Flap to Swing If you press to set the flap up down wind direction plate in its most downward facing position and then press again is displayed and the flap swings automatically up and down Stopping Flap Swing If you press again while the flap is swinging you can stop the flap from swinging and set it in place as desired Thereafter if you...

Страница 667: ...d correctly Pull the remote control forward to remove it Don t get the remote control too far away from the receiver This may cause a malfunction Be sure to keep the remote control in the same room as the receiver remote control addresses can be set up to avoid crosstalk By setting the address switches on the receivers and matching them with the number of addresses on the remote control up to six ...

Страница 668: ... the left and for 4 5 and 6 to the right CZ RWSC2 Position of the Receiver s Address Switch The position of the receiver s address switch does not matter For 1 2 and 3 set the switch on the left and for 4 5 and 6 to the right 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 Setting Addresses CZ RWSY2 CZ RWSK2 Setting the address of the indoor unit 1 First of all set the address for the remote control with Sett...

Страница 669: ...alled and test run It is not for normal use If the Normal Stop ALL switch is on Stop ALL the unit cannot receive signals from the remote control CZ RWSC2 CZ RWSL2 1 Press Emergency Operation of the receiver If the indoor temperature is 24 C or greater when the unit starts running it will act as a cooling mode If the indoor temperature is less than 24 C when the unit starts running it will act as a...

Страница 670: ...is being displayed when you release is set Setting Item Operation Button Setting Content Remote Control Display Remote control operation mode display setting when is pressed Press while pressing Heat Pump with Auto Heat Pump without Auto Dedicated air conditioner Clock display setting Press while pressing 24 hour AM PM Max possible temperature setting in the Heat mode Press while pressing Maximum ...

Страница 671: ... set Make the settings when the remote control is in Operation Display If the problem persists even after you check the foregoing items stop the unit disconnect the power to the indoor unit and contact the dealer where the product was purchased with the model number and problem you are having As it is dangerous under no circumstances should you undertake repairs yourself Further when the receiver ...

Страница 672: ... units can be operated by the remotes When wiring remote controls be sure to double check the terminal numbers of the indoor unit before connecting them so there are no mistakes in the wiring Damage will occur if high voltage e g supply voltage is applied 1 It is not possible to use more than one wireless remote control kit with one indoor unit A receiver located separately can be used at the same...

Страница 673: ...ner Cap Receiver PCB ON 1 2 3 4 Bit 1 OFF ON S003 Screw CZ RWST2 CZ RWST3 S003 Bit 3 OFF ON DIP Switch 3 RCU MAIN RCU SUB CZ RWSC2 Sec8 indd 15 2012 02 28 16 14 01 SM830231 02 Single 欧州 indb 15 SM830231 02 Single 欧州 indb 15 2014 09 09 21 22 22 2014 09 09 21 22 22 ...

Страница 674: ...r the receiver is bundled with other wires such as the incoming line it may cause a malfunction so avoid putting them together 2 If something causes the unit s power source to make noise it will be necessary to resolve the problem such as by installing a noise filter For more information about wiring or test operation refer to Wiring the Receiver and Test Run Refer to the installation instructions...

Страница 675: ...error In fact it does receive signals but they are cancelled 5 Setting Address Switches When more than one receiver and remote control are installed in the same room setting up addresses allows them to avoid interfering with each other Refer to the Users Manual for information on how to change the addresses of the remote controls Changing the address of a receiver can be done after removing the sc...

Страница 676: ...s holding the wire from the louver motor Fig 8 8 5 Attach the side panel 6 Put the receiver s lead wire together with other wires such as the louver motor wire and fasten them with the wire saddle Fig 8 9 Use the hole in the upper part of the wiring box to lead it in Ceiling Suspended Model Fig 8 6 Fig 8 7 Fig 8 9 Fig 8 8 No Accessories Quantity No Accessories Quantity 1 1 Receiver 2 1 Remote Cont...

Страница 677: ...e receiver to the remote control terminal strip on the indoor unit Polarity does not matter If the wiring for the receiver is bundled with other wires such as the incoming line it may cause a malfunction so avoid putting them together Fasten the lead wire securely so it does not get wrapped up in the fan If something causes the unit s power source to make noise it will be necessary to resolve the ...

Страница 678: ...ith each other Refer to the Users Manual for information on how to change the addresses of the remote controls Changing the address of a receiver can be done after removing the screw to the receiver s PCB cover Once the change is complete put the cover back in place while holding the wiring with the cable clamp tighten its screw 5 Setting Address Switches This is hard on the device so only use thi...

Страница 679: ...hape so it does not come in contact with the louver shaft There is a groove in the circled part in diagram 3 that is for passing wire through press the lead wire into this groove so there is no slack in it 4 Attach cover A When doing so press it securely into the place indicated by the arrow in Fig 8 18 5 Shape the lead wire of the operation panel appropriately and fasten it with the enclosed plas...

Страница 680: ...wire of the operation panel and fasten it with the twist lock Fig 8 20 Install the ceiling panel Wiring Diagram Connections 1 2 Connect W1 to the remote control terminal strip on the indoor unit Polarity does not matter Connect the display and the operation panel with W2 If the wiring to the operation panel is bundled together with other wiring such as the incoming line from the power source it ca...

Страница 681: ...ach other Refer to the Users Manual for information on how to change the addresses of the remote controls 1 Turn the 1 DIP switch of the operation panel from OFF to ON Down 4 After completing a test run be absolutely sure to turn the 1 DIP switch from ON to OFF Up sure none of the display lamps are blinking Also replace the PCB cover back as it was and fasten it while holding the wiring in the cab...

Страница 682: ...g the receiver When wiring receivers be sure to double check the terminal numbers of the indoor unit before connecting them so there are no mistakes in the wiring Damage will occur if high voltage e g supply voltage is applied 4 Attach the face plate Fig 8 24 1 Receiver Enclosed 200 mm wiring 1 2 Remote Control 1 3 Remote Control Holder 1 4 2 Dry cell Batteries 1 Users Manual 4 5 Truss Self Tappin...

Страница 683: ...e tie connect it to the connector on the receiver 5 Shape the remote control cord at the top of the PCB so it fits inside the receiver and after configuring the wiring like it is in Fig 8 28 attach the lower case When doing this arrange the head of the cable tie so it face sideways 6 7 8 Remove the face plate and use the wood screws 2 to install the receiver unit Use the cord clip that comes enclo...

Страница 684: ...place temporarily with the 2 enclosed small screws M4 X 40 7 Bend parts A and B back so they fit in the opening and are in the gap between the surface of the ceiling and the receiver then tighten the screws Do not use too much force when tightening the screws Doing so may warp or damage the case Move the receiver by hand and check that it can move just a little Fig 8 31 8 Attach the face plate 3 W...

Страница 685: ...ing the wiring with the cable clamp tighten its screw 1 For instructions on how to install a remote control cord sold separately refer to the chapter on Using as an Embedded Model in Installing Separate Receivers 2 If a remote control cord sold separately is to be used refer to the Mounting Instructions attached to the remote control cord Receiver Terminal strip for wiring the remote control of th...

Страница 686: ...d in the corner where the panel wire comes out as shown in Fig 8 32 consideration should be given to orientation when fitting the panel to the indoor unit 1 Twist off the circled area shown in Fig 8 32 with pliers or similar 2 Remove the suction grille and corner cover Fig 8 33 Break off Panel wire Corner cover Panel wire Fig 8 32 Fig 8 33 Sec8 indd 28 2012 02 28 16 14 03 SM830231 02 Single 欧州 ind...

Страница 687: ...ied clamper Fig 8 35 7 Insert the receiver wire and panel wire into the wire saddles Fig 8 35 Refer to the Users Manual supplied with the panel Receiver Panel wire Pass wire through panel Panel wire Receiver wire Clamper CN130 WL WHT 10P Wire saddle 1 Do not twist the receiver wire and the power lead in wire together as this could lead to malfunction 2 If the unit power source is affected by noise...

Страница 688: ...he terminal board route through the cable tie accessory to the holding clamp and secure the remote control wiring Fig 8 40 Draw in the power wire and remote control wiring separately Mount the side cover and close the air intake grille Ceiling Suspended Model Fig 8 36 Fig 8 38 Fig 8 37 Fig 8 39 Fig 8 40 Receiver Remote Control Dry cell Batteries Users Manual No No Accessories Accessories Quantity ...

Страница 689: ...ely sure to turn the 1 DIP switch from ON to OFF and make sure none of the display lamps are blinking Also replace the PCB cover back as it was and fasten it while holding the wiring with the cable clamp tighten its screw When more than one receiver and remote control are installed in the same room setting up addresses allows them to avoid interfering with each other Refer to the Users Manual for ...

Страница 690: ... settings Alternately Oil Alarm Same as operation of outdoor protection device Alternately Test Run Simultaneously When using CZ RWSC2 If you have either an outdoor maintenance remote control or a wired remote control and a service checker special wiring 623 178 5082 for service use at hand you can get more detailed information about an alarm by connecting one to the service connecter as in the di...

Страница 691: ... Display of Set Temperature C F Setting Off Note 2 C 5 Time Display 24 hour No Display AM PM 24 hour 6 Ventilation Fan ON OFF Off No Display On OFF Note 3 7 Cool temp Max 05 35 C 30 8 Cool temp Min 05 35 C 18 9 Heat temp Max 05 35 C 26 Note 4 10 Heat temp Min 05 35 C 16 11 Dry temp Max 05 35 C 30 12 Dry temp Min 05 35 C 18 13 Auto temp Max 05 35 C 27 14 Auto temp Min 05 35 C 17 16 Address Setting ...

Страница 692: ... MEMO 8 34 SM830231 02 Single 欧州 indb 34 SM830231 02 Single 欧州 indb 34 2014 09 09 21 22 28 2014 09 09 21 22 28 ...

Страница 693: ...201409 SM830231 02 Single 欧州 indb 1 SM830231 02 Single 欧州 indb 1 2014 09 19 17 14 42 2014 09 19 17 14 42 ...

Отзывы: